Optimization of Transformers For Solar or Battery Storage Installations Based On A Cyclic Loading Pattern

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

CIRED 2021 Conference 20 – 23 September 2021

Paper 0261

OPTIMIZATION OF TRANSFORMERS FOR SOLAR


OR BATTERY STORAGE INSTALLATIONS BASED
ON A CYCLIC LOADING PATTERN
Gokhan Kalkan1*, Radoslaw Szewczyk2
1
KYTE Powertech, Cavan, Ireland
2 ®
Nomex Electrical Infrastructure, DuPont, Lodz, Poland
*gokhan.kalkan@kytepowertech.com

Keywords: STEP-UP TRANSFORMER, SOLAR PHOTOVOLTAIC INSTALLATION, BATTERY


STORAGE, CYCLIC LOADING, ARAMID ENHANCED CELLULOSE PAPER

Abstract
The popularity of distributed generation forces suppliers to offer more price competitive equipment. This study is aimed at
optimization of photovoltaic inverter connected step-up transformers. It also applies to other associated installations, e.g.
battery storage. The daily loading patterns in both cases are known. Hence, the effect of this loading would be predicted.

The study is for developing a peak load transformer based on the real data collected in a solar farm. The first task is to find out
a suitable transformer rating that is equal to average “dissipated” power. The peak generation and the peak loading only occur
for a short time during each day. Hence, the equipment does not have to be designed to this maximum capability of the solar
panels and the inverter. The transformer rating could be reduced, to reduce the cost of the equipment while keeping the
performance and reliability at the highest level.

The second aim is to find optimal transformer design, including the most suitable insulation system for handling the expected
cyclic loading. The analysed insulation systems included Kraft papers, thermally upgraded papers and the thermally upgraded
cellulose paper enhanced with aramid. That last solution appears to be the best option for transformers experiencing repetitive
loading cycles.

1 Introduction The study is for developing a sustainable peak load


transformer based on the real data collected in a solar farm
Continuously growing number of distributed generation in The Netherlands. Data covers twelve days period from
sites drives development of components for these June 24th to July 5th, 2019. This paper concentrates on two
installations. The first installations could use the “out-of- main tasks. First task is to find out a suitable transformer
shelf” components. For example, the regular distribution rating that is equal to average “dissipated” power of the
transformers were used in first wind turbine step-up given curves. The peak generation, and consequently, peak
applications, or in solar inverter connected step-up loading of power equipment only occurs for short time
applications. The increasing popularity of distributed during each day. Hence, the equipment does not have to be
generation pushes towards more and more optimal designs designed to this maximum generation capability of the
and forces suppliers of solutions to offer more and more solar panels and the inverter. The transformer power rating
price competitive equipment and systems. This popularity could be reduced, in order to reduce the size and cost of
also means there are increasing numbers of equipment the equipment while keeping the performance and
installed, and the return of experience from their operation reliability at the highest required level.
is growing. It is important to analyse findings from
existing installations and use them for equipment design The second aim is to standardize transformer ratings based
optimization. on the expected loading curves and find optimal solution
for transformer design, including the most suitable
This study is aimed at optimization of solar photovoltaic insulation system for handling the expected cyclic loading
(PV) inverter connected step-up transformers. Although, it during the day. The study analyses a couple of transformer
could be also applicable to other associated installations, designs and includes comparative insulation life
e.g. battery storage. This is because the daily loading calculations. The analysed insulation systems include
pattern in both cases could be similar. Hence, the effect of Kraft papers, thermally upgraded papers and the thermally
this specific loading pattern on design would be similar. upgraded cellulose paper enhanced with aramid. That last
solution appears to be the best option for transformers
experiencing repetitive loading cycles.

1
CIRED 2021 Conference 20 – 23 September 2021

Paper 0261

2. Optimised power rating of transformer

2.1 Typical loading curves in photovoltaic installations


Typical solar photovoltaic installation load curve is
associated with a particular shape and depends on many
parameters. These parameters affect the curve shape and
the power that can be extracted. Among these parameters
are:

• Location of solar panels


• Season of the year Fig. 2. Loading data measured over twelve days period
• Existence of tracking system (load given in kVA vs. time of measurement)
• Cloud cover

A typical load vs. time curves for solar panels are given in
Fig. 1. The typical curve is symmetric about mid axis and
resembles a half sinusoid. It is almost impossible to predict
cloud cover and location of the solar panels and therefore,
maximum loading condition will be assumed to find out a
transformer power rating. This study will also be limited to
solar panels without tracking system as the actual data
collected was for solar panels without tracking system.

Fig. 3. Data measured on fifth and sixth day

The data from the sixth day looks symmetric and fitting a
curve will yield better results towards more generalized
case. If suitable curve fitting technique and values for
average power can be found for sixth day measured data,
the procedure can be generalized and cover fifth day and
others, too. Before attempting to fit a curve, some rules are
necessary to be developed based on the observation:

• Averaging the data over 24-hour period is not


representative of the average load. Average load will
be calculated between the time the solar power is fed
Fig. 1. Typical load vs. time curves for solar power for into network and the time solar power stops generation.
different seasons
• It seems like the average power is not representative as
the power dissipated at average load will be high due to
2.2 Analysis of measured loading data
loading shape. Instead, once the average power is
Measured data for twelve days period is given in Fig. 2 calculated, a new power rating will be found so that
(data from June 24th to July 5th, 2019). The maximum load total dissipated power is equal to average load’s
reaches 1100 kVA. Data per day shows scattering trend for dissipated power without overloading.
most of the days probably caused by cloud cover.
Therefore, instead of analysing the day with maximum • High order splines will be used to fit a curve. Once this
peak, it is better to analyse a day where morning and curve is generated, it will be easier to calculate the
afternoon generation curves show a similar trend. It is felt average power and losses dissipated.
that this approach will generate the data with maximum
average loading. Fitting a curve to this data will enable to • Curve looks like a half sine wave and attempt will be
construct a curve fitting technique that will cover the made to fit a sine curve and compare it to curve that
worst-case scenario. Once the curve is fit, equivalent aging has been generated by spline. If half sine wave
and hot-spot temperatures can be analysed. To be able to approach is successful, this will simplify the
analyse the curves in more depth, the fifth and sixth days calculations towards generalization greatly.
are selected and plotted separately (Fig. 3).

2
CIRED 2021 Conference 20 – 23 September 2021

Paper 0261

2.3 Curve fitting and average load calculation sine wave still be equal to the area under the curve of
MATHCAD software was used for curve fitting and measured values.
analysing purposes. Regression analysis followed high
Measured Data, Curve Fitted & Average Load
order spline curve fitting. A simple code was generated to 1.5 10
3

refine the measured data by simply ignoring the cases Measured Data
Curve Fitted
where the feed into network is zero and load vs. time data Average Value
Half Sine Curve
was generated in two column vector form. Fig. 4 shows the

Feed-in Network (kVA)


curve fitted. It can be seen that the curve fits the measured 110
3

data very well.

500

0
3 3
400 600 800 110 1.2 10

Time (Minutes)
Fig. 5. Sine wave fitted with time interval between the start
of feed-in and the end of feed-in network time

One way to find out the modified start and end time is to
search for the gradient. Sine wave’s gradient at the start is
unity (slope is 45º in other words). At half period, the
gradient is negative (-1). Between the 4th and 5th time
steps, the measured gradient is 1.05 and we can take
Fig. 4. Measured data vs. fitted curve beginning of this time step as our modified beginning of
load. That corresponds to minute 405 starting from
Average load was calculated by integrating the curve midnight. Same calculations reveal that after 1265 minutes
obtained by curve fitting techniques divided by the time from the midnight, the gradient is negative (almost -1) and
between the start and end of feed-in network. The average therefore, modified beginning of load is also found. The
value was found to be 620 kVA, which can be rounded up final form of the curve is then shown in equation (1) and
to 630 kVA typical transformer rating. However, this the curve is shown in Fig. 6.
average value should not be used for sizing the
transformer. This value can be used to calculate a power (1)
rating that will result in the same losses as average losses
without any overloading. where:
S - load in kVA
Calculations show that transformer rated 733 kVA t – time in minutes
subjected to measured loading will result in in same losses
as the 630 kVA unit with uniform loading. Therefore, it
can be concluded that the transformer of 750 kVA
optimised power rating can be proposed to cope with
the measured load profile that has a maximum peak of
1100 kVA.

2.4 Generalisation of loading profile


To be able to fit a sine wave, a peak amplitude, a shift in
time variable and a time interval must be known. Among
these parameters, peak amplitude is the maximum
expected peak feed in network value and time shift is the
modified beginning of load.

Fig. 5 shows the half sine wave fit with existing time
interval. This half sine wave overestimates the measured Fig. 6. Half sine wave curve fitted
loading curve. Therefore, it needs to be corrected in a way
that it will envelope the measured data. A new start and This greatly simplifies the results as the square of the area
end times for loading will be found and area under the half under the curve is related to the power dissipated. Because
this is a sine wave, the transformer power rating with same

3
CIRED 2021 Conference 20 – 23 September 2021

Paper 0261

dissipation will be: Smax/√2 = 776 kVA. This simplifies • Restricted oil flow assumed in order to estimate the
estimation for transformer power rating to be derived. worst-case scenario

These calculations for summer period also cover the • Top oil temperature calculated at the end of the 24-
maximum cases: both the timescale (length of a day) and hour cycle and inserted as initial condition for the cycle
the solar irradiation are at the maximum. If a transformer start
is designed to withstands these loading conditions, it can
be ensured that the transformer will be less loaded during • Mineral oil used in order to reduce the cost vs. ester
the rest of the year. liquids

Power rating of transformer calculated above is different • Transformer completely filled with oil and sealed
than the one calculated in section 2.3. This is because the hermetically
time intervals for power dissipation in both calculations
are different. To be able to provide a cost-effective • Risers, internal connections, bushings and tap changer
approach, it is proposed to use the time interval derived in rated for 1100 kVA loading
section 2.3 for further considerations. Therefore, our
simplified formula Smax/√2 has to be corrected by a factor • Internal pressure at 1100 kVA load kept below
related to the difference in time intervals as shown in 250 mbar
equation (2).
3.2 Thermal calculations and insulation aging
(2) Thorough thermal analysis of the design including
insulation aging modelling was made for the given loading
profile. The maximum hot-spot temperature was limited to
where:
130°C and the top oil temperature was limited to 115°C for
k - correction factor for equivalent kVA
mineral oil. Hot spot temperature could exceed 118°C if
The equivalent power rating is then 776x0.946=735 kVA. the cumulative ageing over 24-hour period is equal to or
Again, the transformer rated 750 kVA can be assumed less than unity.
to cope with the measured load profile and calculations
The cumulative insulation ageing was calculated based on
on both sections above agree with each other. Therefore,
the loading curves. It would be ok to exceed the
we have a simple enough formula to estimate transformer
cumulative ageing rate of 1 during the 24-hour period, as
power rating for the studied solar PV application.
the load profile used was only for a limited time in a year,
but this decision would be left to the user. This study
3 Optimising transformer design limited the cumulative ageing rate to 1.
3.1 Transformer specification, design assumptions Evaluated insulation systems used:
For the analysis, the 750 kVA transformer was used
instead of 1100 kVA unit. Specification details of the final • thermally upgraded Kraft paper (TUP), or
optimised design are listed below:
• thermally upgraded paper enhanced with aramid
HV/LV: 21 000 / 400 V, Dyn5 (Nomex® 910). This new paper solution allows for
Impedance @ 750 kVA (1000 kVA): 4.5% (6.0%) additional 10°C in winding temperature vs. regular
No-load losses: 635 W (0% positive tolerance) thermally upgraded cellulose papers. It gives additional
Load Losses: 7841 W (0% positive tolerance) cost optimisation possibilities. [1-4]
DC bias: 0.5%
Voltage harmonics: <5% First, the calculations were made for the design based on
K-factor for current harmonics: not assumed (no data is TUP. The temperature limits for maximum temperatures
available) were met and the cumulative aging of the insulation was
calculated to be 1. Then, the calculations were made for
Several assumptions and rules were introduced: the design based on TUP enhanced with aramid. The
temperatures calculated are presented in Fig. 7. The
• Hot-spot factor assumed as 1.12 cumulative aging of the insulation enhanced with aramid
reduced from 1 down to 0.37. This indicated a large safety
• Maximum ambient temperature 40°C margin on aging of the insulation system. The expected
lifetime of the transformer would be significantly
• Transformer to be installed in 10 K enclosure (as a extended. Alternatively, the transformer could have an
result, the 10 K temperature increase superimposed to additional loading capability.
the ambient temperature)

4
CIRED 2021 Conference 20 – 23 September 2021

Paper 0261

If that spare loading capability is not needed at the different seasons and different locations will be useful in
customer, further transformer design optimisation is future to refine the calculations for further rating
possible. The temperature limits acceptable by the optimisation.
insulation enhanced with aramid are higher than for
regular TUP insulation. After re-designing the transformer Thorough thermal analysis of the design including
to meet these higher acceptable temperature limits and still cumulative insulation aging modelling was made for the
staying within the normal insulation aging, the transformer given loading profile. The cumulative aging of the
cost could be reduced by 8%. This is in comparison to the insulation enhanced with aramid reduced from 1 down
transformer designed with regular thermally upgraded to 0.37, as compared to the regular thermally upgraded
paper. paper. This indicated a large safety margin on aging in
case of this insulation system. The expected lifetime of the
transformer would be significantly extended and such
transformer would have an additional loading capability.

After re-designing the transformer to meet the higher


temperature limits acceptable for aramid enhanced
paper and still staying within the normal insulation
aging, the transformer cost could be reduced by 8%.
This is in comparison to the transformer designed with
regular thermally upgraded paper. The re-designed
transformer would also be smaller and lighter. This could
be of significant advantage for application in containerised
solar solutions. More power could be available from the
Fig. 7. Temperatures and cumulative insulation aging
system confined in a given size of the container.
calculated for 24-hour period for transformer designed
with mineral oil and paper enhanced with aramid The analysis was made for the specific case of solar
application. However, due to similar loading pattern, the
4 Conclusions methodology is also applicable to battery storage
installations, for transformer power rating determination
Transformer power rating calculated in section 2 is based and for transformer thermal design and insulation system
on the measured loading data that represents a general selection.
pattern for solar photovoltaic installations. The time of the
year when the data was measured (summer) was the 5 References
maximum expected solar power. As a result, it was
reasonable to use this single data to predict overall worst- [1] Marek, R., Wicks, R., Szewczyk, R., et al.: 'New
case scenario pattern. In other seasons loading will not be
cellulose paper enhanced with aramid - practical example
as high and the time exposure will be shorter, resulting in
lower yearly average load values. However, due to lack of of material thermal evaluation acc. to IEEE Std C57.100-
data and to provide a transformer that will not dissipate 2011', CIGRE SC D1 Colloquium, Rio de Janeiro, Brazil,
higher losses in peak seasons, this study is considered 2015, paper ID27
sufficient. [2] Szewczyk, R., Duart, J.-C., Trifigny, P.: 'Mitigation of
lock-in effect for compact substations with transformers
For the analysed loading pattern reaching maximum
meeting future EU efficiency regulations', CIRED,
load of 1100 kVA, the optimised power rating of the
transformer was derived to be 750 kVA. This rating Madrid, Spain, 2019, paper #2089
reduction could result in significant transformer [3] Szewczyk, R., Marek, R., Ballard, R., et al.: 'Innovative
investment savings. The cost of losses would also be lower insulation materials helping in cost reduction of modern
due to lower no-load losses in the smaller unit. transformers', CIRED, Madrid, Spain, 2019, paper #2108
[4] Szewczyk, R., Duart, J.-C.: ' Improved reliability and
The time interval and max output can vary based on the
performance of transformers in solar installations by use of
location. But this figure will not change significantly in
case of The Netherlands and the time interval values that advanced insulation materials', Matpost, Lyon, France,
has been calculated can be used without affecting the 2019, paper #51
accuracy of the study for the given country/region. If the
loading curve is subject to a change as a result of solar DuPont™ and Nomex® are trademarks owned by DuPont
panels with tracking system, then separate calculations and
de Nemours, Inc.
curves are necessary. In this case, the top part of the curve
will flatten for extended period of time. More data of

You might also like