PAD100-NAC

Notification Appliance Circuit

Features
• Monitored output module that provides an additional supervised
output
• Can be used as either a NAC or Releasing Output
• NAC can be wired Class A or Class B
• Monitors presence of 24 VDC Aux Power
• SLC Class A, Class X & Class B
• Mounts in a standard 4” or double gang box
• Wiring terminals accessible when mounted in box
• All wiring terminals accept 22 to 12 AWG
• Product includes a 5 year warranty
• UUKL Listed for Smoke Control

Description Technical Specifications


The PAD100-NAC module uses one (1) address on an SLC Loop. The Operating Voltage 24.0V
module provides a programmable source of power to supervise and
control one (1) Class B or Class A Notification Appliance or one (1) Max SLC Standby Current 200μA
Class B Releasing Circuit. The module requires and supervises a 24
VDC auxiliary power connection. The PAD100-NAC includes one red Max SLC Alarm Current 200μA
LED to indicate the module’s status. In normal condition, the LED Aux Power Required 16-33 VDC
flashes when the device is being polled by the control panel. Output Ratings 24 VDC, 2A
EOL Resistor 5.1K Ω
Application
Stock #3005012 Releasing
The PAD100-NAC is compatible with Potter’s IPA and AFC/ARC EOL Resistor Diode
Applications (Not Included)
series addressable fire alarm control panels. The PAD100-NAC is
a monitored Notification Appliance Circuit that wires to the SLC Operating Temperature Range 32 to 120ºF (0 to 49ºC)
loop to provide an additional notification circuit. When used with a
Potter addressable releasing panel, the PAD100-NAC can provide an Operating Humidity Range 0 to 93% (non-condensing)
additional releasing circuit.
Max no. of Module Per Loop 127 units
Setting the Address 4.17” (106mm)L × 4.17”
Each addressable SLC device must be assigned an address. The Dimensions
(106mm)W × 1.14” (29mm)D
address is set using the DIP switches on the PAD100-NAC module.
Standard 4” Square or
Before connecting a device to the SLC loop, take the following Mounting Options
Double Gang Box
precautions to prevent potential damage to the panel or device:
Shipping Weight 0.6 lbs
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.

Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com

8830086 - REV D • 12/18 page 1 OF 2


PAD100-NAC
Notification Appliance Circuit

Installation Using Compatible Electrical Box


Fig 1

Wiring Diagrams
Output Connected to a Notification Appliance Circuit
Typical Class B Wiring Diagram
Fig 2

FROM FACP OR
PAD100-NAC CLASS B
PREVIOUS MODULE
END-OF-LINE RESISTOR
TO NEXT MODULE + + + 5.1K OHM 1 W
2

AUXILIARY 24 - - - Part #3005013


NOT SUITABLE FOR
VOLT POWER
SYNCHRONIZATION OF
FROM FACP NOTIFICATION
APPLIANCES

Typical Class A Wiring Diagram


Fig 3
FROM FACP OR
PAD100-NAC CLASS A
PREVIOUS MODULE
+ + + NOTE: END-OF-LINE
- - -
TO NEXT MODULE RESISTOR IS NOT
24 VOLT POWER FROM FACP REQUIRED
OR PREVIOUS MODULE
NOT SUITABLE FOR
24 VOLT POWER TO FACP SYNCHRONIZATION OF
OR NEXT MODULE NOTIFICATION APPLIANCES

Releasing Application
Fig 4
PAD100-NAC Releasing Solenoid
NOTE: END-OF-LINE DIODE
ASSEMBLY REQUIRED Part #305012
FROM FACP OR
PREVIOUS MODULE
RED BLACK
TO NEXT MODULE
AUXILIARY
24 VOLT POWER SOLENOID
FROM FACP

NOTE: EOL DEVICE SHALL BE INSTALLED IN


THE SAME ELCTRICAL ENCLOSURE AS THE
RELEASING DEVICE.

It is possible that the internal relay in the PAD100-NAC may be shipped in the non-normal / activated state. To ensure that the internal relay is set to the
normal state, connect the module to the SLC loop and reset the control panel before terminating the wiring to the modules output.