Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

1.

POWER SUPPLY TO MAIN CIRCUIT BREAKER PER


ELEVATOR TO BE NEAR TO THE CONTROLLER ON TOP
FLOOR. AND ONE EARTHING WIRE TO BE SET NEAR TO
THE CONTROLLER TOO, THE SECTION OF EARTHING

,THE WIRE FROM GROUND TO


MACHINE ROOM SHOULD BE INSULATED.
2. MAIN POWER SUPPLY TO BE 3PHASE AC380V, 50HZ,

AC220V.
3. THE SHAFT TO BE OF GOOD VERTICALITY, THE SHAFT
SIZE INDICATED IN PLANE SHALL BE MIN. AVAILABLE
NET SIZE, VERTICAL DEFLECTION RANGE: 0
+25mm(SHAFT HEIGHT<30M), 0
SHAFT HEIGHT 60M), 0 +50mm(60M<SHAFT

4. PIT GROUND SHALL BE WATER-PROOF AND SMOOTH.


5. A POWER SOCKET (2P+ PE) SHALL BE SET IN THE PIT.
6. THERE SHALL BE CONCRETE BEAMS IN SHAFT WALL
WITH INTERVAL 2000MM (UNLESS THE INTERVAL HAS
SPECIAL REQUIREMENT IN CONTRACT), BEAM HEIGHT
SHALL MIN. 300MM, THE LOWEST BEAM SHOULD BE
700MM ABOVE THE PIT GROUND, THE HIGHEST BEAM
SHOULD BE 300MM BELOW THE SHAFT TOP SLAB.
7. THE DECORATION FOR LANDING DOOR ENTRANCE AND
OTHER RESERVED HOLES SHOULD BE DONE AFTER
ELEVATOR INSTALLATION COMPLETION.
8. IF THE SPACE UNDER PIT IS ACCESSABLE FOR PEOPLE,
THE PIT GROUND SHALL BE ABLE TO BEAR 5000N/M
LOAD, AND BUFFER SUPPORT SHALL BE SOLID
COLUMN EXTEND TO THE GROUND.
9. WHEN TWO ADJACENT LANDING DOOR SILL DISTANCE IS
ABOVE 11M, SAFETY EXIT TO BE SET ON THE SHAFT
WALL IN MIDDLE. AND THE EXIT DOOR SHALL COMPLY
WITH EN81.
10. CABLE FROM GUARDS' ROOM TO SHAFT PIT TO BE SET
BY OTHERS.
11. ON TOP OF CONTROLLER, PERMANENT LIGHT TO BE
SET, AND ILLUMINATION NOT SMALLER THAN 200LX.
12. SHAFT CONCRETE WALL TO BE SOUND, COMPRESSION
STRENGTH NOT BE LOWER THAN 30MPA, WALL
THICKNESS NOT BE SMALLER THAN 150MM.

Client Signature Supply Signature

Date Date
LG- Rise

You might also like