Annexure-B 8/1

Page 1 of 1
96 KV LIGHTNING ARRESTER
A Name of the Traction Sub-Station QLM TSS
B Name of the Equipment 96 KV LIGHTNING ARRESTER
C Date of Testing 20/07/2022
D Equipment No. LA-15 LA-15A LA-16 LA-16A
I Name Plate Details :-
a Make LAMCO
b Maker's Sl. No. 992 991 990 993
c Year of Manufacturing 2020 2020 2020 2020
d Rating 96KV/10KV 96KV/10KV 96KV/10KV 96KV/10KV
e Type EMOH EMOH EMOH EMOH
f Rated voltage 96KV 96KV 96KV 96KV
g RDSO Specification No. ETI/PSI/137(8/89)
h P.O No. and Date 0720-46 ,04/07/2020
i Total Creapage clearance 3600 mm 3600 mm 3600 mm 3600 mm
j Continuous operating voltage 82 KV 82 KV 82 KV 82 KV
k continuous operating current 40 KA 40 KA 40 KA 40 KA
l Long duration dischare class 3 3 3 3
II Details of tests conducted:
1 External Condition Good Good Good Good
Checked & Checked & Checked & Checked &
2 Duplicate earth and earth continuity
Found OK Found OK Found OK Found OK
Terminal connectors (Check for tightness Checked & Checked & Checked & Checked &
3
and condition) Found OK Found OK Found OK Found OK
4 Insulation resistance (with 5 kV Megger):-
a Top Terminal to Earth above 10 GΩ 42 G ohms 59.9 G ohms 96 G ohms 78.3 G ohms
b Bottom to Earth above 1 GΩ 1.14 G ohms 1.53 G ohms 1.43 G ohms 1.79 G ohm
c Top Terminal to bottom terminal above 10 69.3 G ohm 52 G ohm 67.7 G ohms 41.2 G ohm
5 GΩ electrode
Earth
6 Surge counter:-
a Make LAMCO
b Maker's Sl. No.
III RITES Inspection Certificate Enclosed Enclosed Enclosed Enclosed
IV Manufacturer's test report Enclosed Enclosed Enclosed Enclosed

TTIPL/PM/SVM RE/E/PMC/SVM PM/PMC/SVM

Sr.Mgr/E/RVNL/UBL SSE/TRD/UBL DEE/TRD/UBL

JGM/E/RVNL/UBL Sr. DEE/TRD/UBL