POWER TRANSFORMER.
A Name of the Traction Sub-Station QLM TSS
B Name of the Equipment 110 / 27 KV, 21.6/30.24 MVA Power Transformer - 1LIN40600100042
C Date of Testing 20/03/2022
III Details of Tests conducted:
Insulation resistance of windings ( With 5
a
KV Megger) :-
i HV to Earth 14.1 G ohm
ii LV to Earth 23.0 G ohm
iii HV to LV 13.7 G ohm
IV Polarisation Test:-
Polarisation values(with 5 KV IR Values PI Values
a
Megger) R60 R600 R600/R60= above 1.2
i HV to Earth 14.1 G ohm 43.6 3.09
i LV to Earth 23.0 G ohm 52.9 2.30
iii HV to LV windings 13.7 G ohm 39.6 2.89
V Voltage Ratio Test:- Tap-1 Tap-2 Tap-3 Tap-4 Tap-5
i Voltage applied on HV side ( in Volts) 243.5 243.5 243.5 243.5 243.5
ii Voltage measured on LV side ( in Volts) 54.32 57.01 59.86 62.91 66.2
iii Ratio specified 4.481 4.278 4.074 3.870 3.667
iv Ratio Obtained 4.483 4.271 4.068 3.871 3.678
v % Error specified (+/-) 0.5 0.5 0.5 0.5 0.5
vi % Error obtained 0.027 -0.154 -0.154 0.006 0.315
VI Polarity Test:-
Shorting 1.2 & 2.1, Voltage applied across
a
1.1 & 2.2 (Tap - 3 Normal Condition)
i Voltage applied at 1.1 & 2.2 terminals (X) 243.5V
iv X = Y + Z 243.5V
v Polarity Substractive
VII Magnetising current :-
HV side (Tap 1, 2, 3, 4, 5, 6) Applied Voltage 243.5V Current measured 1.0mA
VIII Short circuit Test:-
a LV Terminals 2.1 & 2.2 shorted
Applied Voltage on HV side (in volts) -
b Current measured on HV side -3.6A Current measured on LV side-14.8A
243.5 V
25 kV VACCUM INTERRUPTER
A Name of the Traction Sub- QLM TSS
B Stationof the Equipment
Name 25 KV Vaccum Interrupter
C Date of Testing 28/07/2022
D Equipment No. BM-133 BM-134 BM-135 BM-136 BX / 08
I Details of test conducted :-
1 External Condition Good Good Good Good Good
Insulation resistance (5 KV Meg)
2
bet (Min: 5 GΩ)
a Interruptor in Open position:-
i Top terminal to Earth 109.9 G ohm 64.6 G ohm 53.8 G ohm 64.3 G ohm 39.2 G ohm
ii Top terminal to bottom terminal 106 G ohm 22.4 G ohm 47.9 G ohm 79.3 G ohm 32.3 G ohm
ii Bottom terminal to Earth 80 G ohm 30.4 G ohm 31.9 G ohm 31.9 G ohm 22.5 G ohm
b Close position:-
i Top terminal to earth 85.4 G ohm 33.0 G ohm 33.5 G ohm 27.6 G ohm 20.4 G ohm
Insulation resistance of equipments
3 in optg. Mechanism (with 500V Meg.) -
(Min. 2 M.Ohms)
i Spring Charging motor 2.0 M ohm 3.7 M ohm 2.0 M ohm 3.8 M ohm 3.9 M oghm
ii Closing coil 6.4 M ohm 24.4 M ohm 11.4 M ohm 16.2 M ohm 5.5 M ohm
iii Triping coil 7.2 M ohm 21.4 M ohm 27.8 M ohm 15.9 M ohm 14.2 M ohm
4 Ohmic values of :-
i Motor coil 9.6 Ohm 14.7 Ohm 11.6 Ohm 14.0 Ohm 6.6 Ohm
ii Close coil 81.6 Ohm 81.2 Ohm 80.9 Ohm 80.2 Ohm 80.6 Ohm
iii Trip coil 81.4 Ohm 82.9 Ohm 82.8 Ohm 81.5 Ohm 81.0 ohm
Contact resistance (< 50 µΩ ) applied
5 30.3micro ohm 28.7 micro ohm 32.0 micro ohm 30.7 micro ohm 31.4 micro ohm
at 100A
6 Travel & Wipe:-
i Travel 22 ±1 mm 21 22 22 22 21
ii Wipe 8 +1/- 0 mm 8 8 8 8 8
Checked & Checked & Checked & Checked & Checked &
7 Condition of Sillicagel
Found Good Found Good Found Good Found Good Found Good
25 KV VACCUM INTERRUPTER
A Name of the Traction Sub-Station QLM TSS
B Name of the Equipment 25 KV Vaccum Interrupter
C Date of Testing 28/07/2022
D Equipment Number BM-133 BM-134 BM-135 BM-136 BX /08
8 Local operation:-
a close Operated Operated Operated Operated Operated
b Open Operated Operated Operated Operated Operated
9 Remote Operation From CRP:-
a Close Operated Operated Operated Operated Operated
b Open Operated Operated Operated Operated Operated
Provided & Good Provided & Good Provided & Good Provided & Good Provided & Good
10 Duplicate earth and earth continuity
Continuty Continuty Continuty Continuty Continuty
Tigtness checked & Tigtness checked & Tigtness checked & Tigtness checked & Tigtness checked &
Terminal connectors
2 Found Good Found Good Found Good Found Good Found Good
(Check for tightness & Condition)
condition condition condition condition condition
Checked alignment Checked alignment Checked alignment Checked alignment Checked alignment
Contacts (Check for
3 & Found good & Found good & Found good & Found good & Found good
alignment and condition)
condition condition condition condition condition
4 Operations:-
a Close Operated smoothly Operated smoothly Operated smoothly Operated smoothly Operated smoothly
b Open Operated smoothly Operated smoothly Operated smoothly Operated smoothly Operated smoothly
Checked alignment Checked alignment Checked alignment Checked alignment Checked alignment
Operation Mechanism (Check for alignment
5 & Operated & Operated & Operated & Operated & Operated
& smooth operation)
smoothly smoothly smoothly smoothly smoothly
Locks (Check whether bolt lock & pad lock fit
Bolt & Padlock Bolt & Padlock Bolt & Padlock Bolt & Padlock Bolt & Padlock
6 convenniently when isolator is in open or
provided provided provided provided provided
close position)
7 Interlocking with BM K9 K8 M2 J1 J6
8 Duplicate earth and earth continuity Provided Provided Provided Provided Provided
9 Insulation Resistance (with 2.5 kV Meg):-
Pole to Pole (Open position) 17.8 G ohms 11.4 G ohms 26.45 G ohms 19.2 G ohms 9.63 G ohms
a
Pole to Pole (Open position) 23.2 G ohms 29.2 G ohms 32.20 G ohms 29.3 G ohms 21.3 G ohms
Pole to Earth (Closed position) 4.2 G ohms 6.23 G ohms 9.22 G ohms 11.22 G ohms 7.53 G ohms
b
Pole to Earth (Closed position) 25.4 G ohms 34.42 G ohms 35.43 G ohms 27.63 G ohms 31.50 G ohms
c Pole to Pole (Close position) 72.3 G ohms 62.23 G ohms 58.32 G ohms 55.6 G ohms 47.32 G ohms
Clearence between male & female contacts in
d 5200 mm 5200 mm 5200 mm 5200 mm 5200 mm
open position ( Min: 500 mm).
10 Details of Insulators:-
25 kV Pedestal Insulators (Track side)
a
Make and Year of Mamufacture: IEC/02.2020 IEC/02.2020 IEC/02.2020 IEC/02.2020 IEC/02.2020
25 kV Pedestal Insulators (BM side)
b Make
IEC/02.2020 IEC/02.2020 IEC/02.2020 IEC/02.2020 IEC/02.2020
and Year of Mamufacture:
Operating Rod Insulator
c
Make and year of Mamufacture: IEC/02.2020 IEC/02.2020 IEC/02.2020 IEC/02.2020 IEC/02.2020
III RITES Inspection certificate Enclosed
IV Manufacturer's test report Enclosed
Tigtness checked & Tigtness checked & Tigtness checked & Tigtness checked &
Terminal connectors
2 Found Good Found Good Found Good Found Good
(Check for tightness & Condition)
condition condition condition condition
Checked alignment Checked alignment Checked alignment Checked alignment &
3 Contacts (Check for alignment and condition) & Found good & Found good & Found good Found good
condition condition condition condition
4 Operations:-
a Close Operated smoothly Operated smoothly Operated smoothly Operated smoothly
b Open Operated smoothly Operated smoothly Operated smoothly Operated smoothly
Checked alignment Checked alignment Checked alignment
Operation Mechanism (Check for alignment & Checked alignment &
5 & Operated & Operated & Operated
smooth operation) Operated smoothly
smoothly smoothly smoothly
Locks (Check whether bolt lock & pad lock fit
Bolt & Padlock Bolt & Padlock Bolt & Padlock Bolt & Padlock
6 convenniently when isolator is in open or
provided provided provided provided
close position)
7 Interlocking with BM YE YL YK YC
8 Duplicate earth and earth continuity Provided Provided Provided Provided
9 Insulation Resistance (with 2.5 kV Meg):-
a Pole to Pole (Open position) 3.25 G ohms 2.75 G ohms 2.79 G ohms 2.46 G ohms
b Pole to Earth (Closed position) 5.72 G ohms 6.69 G ohms 7.42 G ohms 4.23 G ohms
Clearence between male & female contacts in
d 520 mm 520 mm 520 mm 520 mm
open position ( Min: 500 mm).
10 Details of Insulators:-
25 kV Pedestal Insulators
a
Make and Year of Mamufacture: IEC/02.2020 IEC/02.2020 IEC/02.2020 IEC/02.2020
Operating Rod Insulator
b
Make and year of Mamufacture: IEC/02.2020 IEC/02.2020 IEC/02.2020 IEC/02.2020
III RITES Inspection certificate Enclosed
IV Manufacturer's test report Enclosed
Tigtness checked & Tigtness checked & Tigtness checked & Tigtness checked &
Terminal connectors
2 Found Good Found Good Found Good Found Good
(Check for tightness & Condition)
condition condition condition condition
Checked alignment & Checked alignment & Checked alignment & Checked alignment &
Contacts (Check for alignment and
3 Found good Found good Found good Found good
condition)
condition condition condition condition
4 Operations:-
a Close Operated smoothly Operated smoothly Operated smoothly Operated smoothly
b Open Operated smoothly Operated smoothly Operated smoothly Operated smoothly
Operation Mechanism (Check for alignment Checked alignment & Checked alignment & Checked alignment & Checked alignment &
5
& smooth operation) Operated smoothly Operated smoothly Operated smoothly Operated smoothly
Operation Mechanism (Check for Checked alignments Checked alignments Checked alignments Checked alignments Checked alignments
5
alignment & smooth operation) & Operated smoothly & Operated smoothly & Operated smoothly & Operated smoothly & Operated smoothly
AC DISTRIBUTION BOARD
A Name of the Traction Sub-Station QLM TSS
B Name of the Equipment ACDB
C Date of Testing 19/07/2022
I Make Supreme swithgear & Transformers
i Drawing .No. ACDB 1118/251
ii RDSO Specification No. ETI/PSI/29 (12/79 with A&C slip No. 1))
II In coming HRC Fuse:-
a Identification No. 25 KV AT-01
b Make Surdhi
c Rating 63A
d Vlotage 240V AC
e Identification No. 25 KV AT-02
f Make Surdhi
g Rating 63A
h Vlotage 240V AC
III Out going HRC Fuse:-
a Identification No. Heater Circuit
b Make Surdhi
c Rating 16A
d Vlotage 240V AC
e Identification No. Control Board
f Make Surdhi
g Rating 32A
h Vlotage 240V AC
i Identification No. Control Room & Yard Lighting
j Make Surdhi
k Rating 32A
l Vlotage 240V AC
m Identification No. Charger
n Make Surdhi
o Rating 32A
p Vlotage 240V AC
Terminal connectors (Check for tightness and Tightness checked Tightness checked Tightness checked Tightness checked
9
general condition) &Good condition &Good condition &Good condition &Good condition
10 Height of Live part from Ground level 4950 mm 4950 mm 4950 mm 4950 mm
11 Details of Cable on secondary side
a Size of Cable 2 Core X 4 Sq.mm
12 IR Values:-
a Between Cores ( Red & Black) 1 G ohm 1 G ohm 1 G ohm 1 G ohm
b Red Core to Earth (S1) 1 G ohm 1 G ohm 1 G ohm 1 G ohm
c Black core to Earth ( S2) 1 G ohm 1 G ohm 1 G ohm 1 G ohm
III RITES Inspection Certificate Enclosed
IV Manufacturer's Material Test Report Enclosed
POWER TRANSFORMER.
A Name of the Traction Sub-Station QLM TSS
B Name of the Equipment 10 / 27 KV, 21.6/30.24 MVA Power Transformer - 1LIN20600100042
C Date of Testing 21/03/2022
IX Bushing CTs :-
HV/BCT-1 HV/BCT-2 LV/BCT-1 LV/BCT-2 WTI/BCT-5
Ohmic Value & Insulation resistance of
(1.1) " " Ph. (1.2) " " Ph. (2.1) " " Ph. (2.2) " " Ph (2.1) " " Ph
a Ohmic value of Secondary of BCT 0.4 Ohm 0.1 Ohm 0.5 Ohm 0.5 Ohm 0.9/1.1/1.3 Ohm
b Insulation Resistance of Sec of BCTs 42.5 G ohm 200 G ohm 13.6 G ohm 21.7 G ohm 75.4 G ohm