개정 기술표준원고시 제2003 - 0000호 (2003. 5. 24)
개정 기술표준원고시 제2007 - 0319호 (2007. 12.27)
개정 기술표준원고시 제2008 - 0120호 (2008. 3.21)
전기용품안전기준
K 60269-2
[IEC 2006-11, 제3판]
저전압 퓨즈
제 2 부 : 전문가용 퓨즈(공업용)의
추가 요구 사항
- 퓨즈 표준 시스템 A ~ I의 예
목 차
1 일반 적용범위 ···································································································································· 13
2 인용규격 ·············································································································································· 14
1 일반사항 ·············································································································································· 15
1.1 적용범위 ······································································································································· 15
2 용어와 정의 ········································································································································ 15
3 사용조건 ·············································································································································· 16
4 분류 ······················································································································································ 16
5 퓨즈의 특성 ········································································································································ 16
5.2 정격전압 ····································································································································· 16
5.3.1 퓨즈-링크의 정격전류 ································································································· 16
5.3.2 퓨즈-홀더의 정격전류 ································································································· 17
5.5 퓨즈-링크의 정격 전력 손실과 퓨즈-홀더의
정격 허용 전력 손실 ························································································································ 17
5.6 시간-전류 특성의 한계 ············································································································ 17
5.6.1 시간-전류 특성, 시간-전류 영역과 과부하 곡선 ·················································· 17
5.6.2 협약시간과 협약전류 ···································································································· 17
5.6.3 게이트 ······························································································································ 17
5.7.2 정격 차단 용량 ·············································································································· 18
6 표시사항 ·············································································································································· 18
6.1 퓨즈-홀더의 표시사항 ·············································································································· 18
6.2 퓨즈-링크의 표시사항 ·············································································································· 18
7 구조의 표준조건 ································································································································ 19
7.1 기계적 설계 ································································································································· 19
7.1.2 단자를 포함한 접속부 ·································································································· 19
7.1.3 퓨즈-접촉부 ··················································································································· 20
7.1.5 퓨즈-베이스의 구조 ····································································································· 20
7.1.7 퓨즈-링크의 구조 ········································································································· 21
7.2 절연 특성 ····································································································································· 21
7.7 I 2t 특성 ········································································································································ 21
7.8 “gG”퓨즈-링크의 과전류 판별 ······························································································· 22
7.9 전기적 충격에 대한 보호 ········································································································· 23
8 시험 ······················································································································································ 23
8.1.4 퓨즈의 배치와 치수 ······································································································ 23
8.1.6 퓨즈-홀더의 시험 ········································································································· 23
8.2.2.1 시험전압의 인가 지점 ······························································································· 24
- 1 -
8.2.3.2 시험전압값 ··················································································································· 24
8.2.3.3 시험방법 ······················································································································· 24
8.2.4 시험결과의 판정 ············································································································ 25
8.2.5 트래킹에 대한 내성 ······································································································ 25
8.3 온도상승과 전력 손실의 검증 ································································································· 25
8.3.1 퓨즈의 배치 ···················································································································· 25
8.3.2 온도상승의 측정 ············································································································ 25
8.5.8 시험결과의 판정 ············································································································ 27
8.7.4 과전류 판별의 검증 ······································································································ 27
8.9 열에 대한 내성의 검증 ············································································································· 29
8.9.1 퓨즈-베이스 ··················································································································· 29
8.9.2 주조물 또는 주조물에 고정된 금속의 취부용 러그를 가진 퓨즈-링크 ··········· 30
8.10 접촉부와 단자 클램프 성능의 검증 ····················································································· 30
8.10.1 퓨즈의 배치 ·················································································································· 30
8.10.2 시험방법 ························································································································ 32
8.10.3 시험결과의 판정 ·········································································································· 34
8.11 기계적 시험과 기타 시험 ······································································································· 36
1 일반사항 ·············································································································································· 59
1.1 적용범위 ······································································································································· 59
2 용어와 정의 ········································································································································ 59
3 사용조건 ·············································································································································· 59
4 분류 ······················································································································································ 59
5 퓨즈의 특성 ········································································································································ 59
5.2 정격전압 ······································································································································· 60
5.3.1 퓨즈-링크의 정격전류 ································································································· 60
5.3.2 퓨즈-홀더의 정격전류 ································································································· 60
5.5 퓨즈-링크의 정격 전력 손실과 퓨즈-홀더의
정격 허용 전력 손실 ························································································································ 60
5.6 시간-전류 특성의 한계 ············································································································ 60
5.7.2 정격 차단 용량 ·············································································································· 60
6 표시사항 ·············································································································································· 60
7 구조의 표준조건 ································································································································ 60
7.1 기계적 설계 ································································································································· 60
7.1.2 단자를 포함한 접속부 ·································································································· 61
7.1.3 퓨즈-접촉부 ··················································································································· 61
- 2 -
7.1.7 퓨즈-링크의 구조 ········································································································· 61
2
7.7 I t 특성 ········································································································································ 61
7.8 “gG" 퓨즈-링크의 과전류 판별 ······························································································ 61
7.9 전기적 충격에 대한 보호 ········································································································· 61
8 시험 ······················································································································································ 61
8.1.6 퓨즈-홀더의 시험 ········································································································· 62
8.3 온도상승과 전력 손실의 검증 ······························································································· 62
8.7.4 과전류 판별의 검증 ······································································································ 62
8.9 열에 대한 내성의 검증 ············································································································· 62
8.9.1 퓨즈-베이스 ··················································································································· 63
1 일반사항 ·············································································································································· 72
1.1 적용범위 ······································································································································· 72
2 용어와 정의 ········································································································································ 72
3 사용조건 ·············································································································································· 72
4 분류 ······················································································································································ 72
5 퓨즈의 특성 ········································································································································ 72
5.2 정격전압 ······································································································································· 72
5.3.2 정격전류 ·························································································································· 73
5.5.1 정격 허용 전력 ·············································································································· 73
6 표시사항 ·············································································································································· 73
7 구조의 표준조건 ································································································································ 73
7.1 기계적 설계 ································································································································· 73
7.1.2 단자를 포함한 접속부 ·································································································· 73
7.2 절연 특성 ····································································································································· 74
8 시험 ······················································································································································ 74
8.1.6 퓨즈-홀더의 시험 ········································································································· 74
8.3 온도상승과 전력 손실의 검증 ································································································· 75
8.3.1 퓨즈의 배치 ···················································································································· 75
8.10 접촉부와 단자 클램프 성능의 검증 ····················································································· 76
8.10.1 퓨즈의 배치 ·················································································································· 76
1 일반사항 ·············································································································································· 82
1.1 적용범위 ······································································································································· 82
2 용어와 정의 ········································································································································ 82
3 사용조건 ·············································································································································· 82
- 3 -
4 분류 ······················································································································································ 82
5 퓨즈의 특성 ········································································································································ 83
5.2 정격전압 ······································································································································· 83
5.3.2 정격전류 ·························································································································· 83
5.5.2 일렬 퓨즈-베이스의 정격 허용 전력 손실 ····························································· 83
6 표시사항 ·············································································································································· 83
7 구조의 표준조건 ································································································································ 83
7.1 기계적 설계 ································································································································· 83
7.1.2 단자를 포함한 접속부 ·································································································· 83
7.1.5 동대 고정용 퓨즈-베이스의 구조 ············································································· 84
8 시험 ······················································································································································ 85
8.3 온도상승과 전력 손실의 검증 ································································································· 85
8.3.1 퓨즈의 배치 ···················································································································· 85
8.9.1 퓨즈-베이스 ··················································································································· 86
8.10 접촉부와 단자 클램프 성능의 검증 ····················································································· 86
8.10.1 퓨즈의 배치 ·················································································································· 86
8.10.2 시험방법 ························································································································ 86
8.11 기계적 시험과 기타 시험 ······································································································· 87
1 일반사항 ·············································································································································· 95
1.1 적용범위 ······································································································································· 95
2 용어와 정의 ········································································································································ 95
3 사용조건 ·············································································································································· 95
4 분류 ······················································································································································ 95
5 퓨즈의 특성 ········································································································································ 95
5.3.1 퓨즈-링크의 정격전류 ································································································· 95
5.3.2 퓨즈-홀더의 정격전류 ································································································· 96
5.5 퓨즈-링크의 정격 전력 손실과 퓨즈-홀더의
정격 허용 전력 손실 ························································································································ 96
5.6 시간-전류 특성의 한계 ············································································································ 96
5.6.1 시간-전류 특성, 시간-전류 영역과 과부하 곡선 ·················································· 96
5.6.2 협약시간과 협약전류 ···································································································· 96
5.6.3 게이트 ······························································································································ 96
5.7.2 정격 차단 용량 ·············································································································· 97
6 표시사항 ·············································································································································· 97
6.1 퓨즈-홀더의 표시사항 ·············································································································· 97
6.2 퓨즈-링크의 표시사항 ·············································································································· 97
7 구조의 표준조건 ································································································································ 97
- 4 -
7.1 기계적 설계 ································································································································· 97
7.1.2 단자를 포함한 접속부 ············································································································ 98
7.9 전기적 충격에 대한 보호 ········································································································· 98
8 시험 ······················································································································································ 98
8.3 온도상승과 전력 손실의 검증 ································································································· 98
8.3.1 퓨즈의 배치 ···················································································································· 98
8.3.3 퓨즈-링크 전력 손실의 측정 ····················································································· 98
8.4 동작의 검증 ································································································································· 98
8.4.1 퓨즈의 배치 ···················································································································· 98
8.5 차단 용량의 검증 ······················································································································· 98
8.5.1 퓨즈의 배치 ···················································································································· 98
8.5.8 시험결과의 판정 ············································································································ 98
8.9 열에 대한 내성의 검증 ············································································································· 99
8.10 접촉부 성능의 검증 ················································································································· 99
8.10.1 퓨즈의 배치 ·················································································································· 99
8.10.2 시험방법 ························································································································ 99
8.10.3 시험결과의 판정 ·········································································································· 99
8.11 기계적 시험과 기타 시험 ····································································································· 100
- 5 -
7 구조의 표준조건 ······························································································································ 114
7.1 기계적 설계 ······························································································································· 114
7.1.2 단자를 포함한 접속부 ································································································ 114
2
7.7 I t 특성 ······································································································································ 115
7.8 “gG” 퓨즈-링크의 과전류 판별 ··························································································· 115
7.9 전기적 충격에 대한 보호 ······································································································· 116
8 시험 ···················································································································································· 116
8.1.6 퓨즈-홀더의 시험 ······································································································· 116
8.3.1 퓨즈의 배치 ·················································································································· 116
8.7.4 과전류 판별의 검증 ···································································································· 118
8.9 열에 대한 내성의 검증 ··········································································································· 119
8.10 접촉부 성능의 검증 ··············································································································· 119
8.10.1 퓨즈의 배치 ················································································································ 120
8.10.2 시험방법 ······················································································································ 120
8.10.3 시험결과의 판정 ········································································································ 120
- 6 -
7.9 전기적 충격에 대한 보호 ······································································································· 129
8 시험 ···················································································································································· 129
8.3.3 퓨즈-링크 전력 손실의 측정 ··················································································· 129
8.4.1 퓨즈의 배치 ·················································································································· 129
8.5.1 퓨즈의 배치 ·················································································································· 129
8.7.4 과전류 판별의 검증 ···································································································· 129
8.9 열에 대한 내성의 검증 ··········································································································· 130
8.10 접촉부 성능의 검증 ··············································································································· 130
8.10.1 퓨즈의 배치 ················································································································ 130
8.10.2 시험방법 ······················································································································ 130
8.10.3 시험결과의 판정 ········································································································ 130
8.11 기계적 시험과 기타 시험 ··········································································································· 131
퓨즈 시스템 H -
“gD”와 “gN” 특성의 퓨즈-링크로 된 퓨즈
(J 등급과 L 등급 시간 지연형 퓨즈와 비시간 지연형 퓨즈)
- 7 -
8 시험 ···················································································································································· 141
8.3 온도상승과 전력 손실의 검증 ······························································································· 142
8.3.1 퓨즈의 배치 ·················································································································· 142
8.4 동작의 검증 ······························································································································· 142
8.4.1 퓨즈의 배치 ·················································································································· 142
8.6 컷-오프 전류 특성의 검증 ···································································································· 143
8.7 I 2t 특성과 과전류 판별의 검증 ···························································································· 143
8.9 열에 대한 내성의 검증 ··········································································································· 144
8.10 접촉부 성능의 검증 ··············································································································· 144
8.10.1 퓨즈의 배치 ················································································································ 144
8.10.2 시험방법 ······················································································································ 145
8.10.3 시험결과의 판정 ········································································································ 145
8.11 기계적 시험과 기타 시험 ····································································································· 145
8.11.2 기타 시험 ···················································································································· 145
- 8 -
8.1.1 시험의 종류 ·················································································································· 163
8.3.1 퓨즈의 배치 ·················································································································· 163
8.3.3 퓨즈-링크 전력 손실의 측정 ··················································································· 164
8.4.1 퓨즈의 배치 ·················································································································· 164
8.5.1 퓨즈의 배치 ·················································································································· 164
8.5.2 시험 회로의 특성 ········································································································ 164
8.5.5 시험방법 ························································································································ 164
8.5.8 시험결과의 판정 ·········································································································· 165
8.7.3 0.01 s에서 퓨즈-링크의 적합성 검증 ···································································· 165
8.9 열에 대한 내성의 검증 ··········································································································· 165
8.11 기계적 시험과 기타 시험 ····································································································· 165
- 9 -
그림 502 - 볼트 결합형 퓨즈-링크- 크기 A와 B ······································································· 102
그림 503 - 대표적인 퓨즈-홀더 ······································································································· 103
그림 504 - “gG” 퓨즈-링크의 시간 전류 영역 ············································································ 105
그림 505 - “gG” 퓨즈-링크의 시간 전류 영역 ············································································ 106
그림 506 - 전력 손실 시험 리그(rig) ····························································································· 107
그림 507 - 볼트 결합형 퓨즈-링크의 차단 용량 시험 리그 ····················································· 108
그림 601 - 실린더 캡형 퓨즈-링크 ································································································· 121
그림 602 - 스트라이커가 있는 실린더 접촉 캡형 퓨즈-링크
- 크기 14 × 51와 22 × 58에만 해당하는 추가 치수 ·································································· 122
그림 603 - 실린더 캡형 퓨즈-링크용 베이스 ··············································································· 123
그림 701 - 오프셋 블레이드 접촉형 퓨즈-링크, 크기 E1, F1, F2와 F3 ································ 132
그림 702 - 대표적인 퓨즈-홀더 ······································································································· 133
그림 703 - “gG” 퓨즈-링크의 시간-전류 영역 ············································································ 134
그림 703 - “gG” 퓨즈-링크의 시간-전류 영역 ············································································ 135
그림 705 - 전력 손실 시험 리그 ····································································································· 136
그림 801 - 퓨즈-링크 (1 - 600 A) ··································································································· 147
그림 802 - 퓨즈-링크 (700 - 6 000 A) ··························································································· 148
그림 803 - 1 - 600 A 퓨즈-링크용 퓨즈-베이스와 접촉부 ······················································· 149
그림 804 - 700 - 6 000 A 퓨즈-링크용 퓨즈-베이스와 접촉부 ··············································· 150
그림 805 - 더미 퓨즈-링크 ··············································································································· 151
그림 806 - 시험 배치 ························································································································· 152
그림 807 - “gN” 퓨즈-링크의 시간-전류 영역 ············································································ 153
그림 808 - “gN” 퓨즈-링크의 시간-전류 영역 ············································································ 154
그림 809 - “gN” 퓨즈-링크의 시간-전류 영역 ············································································ 155
그림 810 - “gD” 퓨즈-링크의 시간-전류 영역 ············································································ 156
그림 811 - “gD” 퓨즈-링크의 시간-전류 영역 ············································································ 157
그림 812 - “gD” 퓨즈-링크의 시간-전류 영역 ············································································ 158
그림 901 - 100 A, 200 A, 355 A와 630 A 전류 정격에 대한 시간-전류 영역 ·················· 166
그림 902 - 160 A와 315 A 전류 정격에 대한 시간-전류 영역 ··············································· 167
그림 903 - 250 A와 500 A 전류 정격에 대한 시간-전류 영역 ··············································· 168
그림 904 - 200 A와 400 A 전류 정격에 대한 시간-전류 영역 ··············································· 169
그림 905 - L형 태그와 U형 태그를 가진 퓨즈-링크의 치수 ··················································· 170
그림 906 - 전력 손실 시험 리그 ····································································································· 171
그림 907 - 차단 용량 시험 리그 ····································································································· 172
- 10 -
표 106 - “gG” 퓨즈-링크에 대한 0.01 s에서 용단 I 2t 값과 동작 I 2t 값 ································ 22
표 107 - “aM” 퓨즈-링크에 대한 최대 동작 I 2t 값 ····································································· 22
표 108 - 판별을 위한 용단 I 2t 값 ····································································································· 23
표 109 - 퓨즈-홀더의 시험 항목과 시료수 대조표 ······································································· 24
표 110 - 정격 임펄스 내전압 ············································································································· 24
표 111 - 단자 나사에 적용하는 토크 ······························································································· 25
표 112 - 시험 전류 ······························································································································· 27
표 113 - 판별 시험을 위한 시험전류와 I 2t의 제한값 ··································································· 28
표 114 - 제조자가 제시한 값이 없는 경우에 적용하는 토크 ····················································· 31
표 115 - 8.10에 해당하는 시험을 위한 알루미늄 도체의 단면적 ·············································· 32
표 116 - 단자 클램프에 대한 시험 시퀀스 ····················································································· 34
표 117 - 허용되는 저항의 변화 ········································································································· 35
표 118 - 퓨즈-베이스 접촉부로부터 퓨즈-링크의 인출력 ··························································· 36
표 201 - 스트라이커의 위치와 힘 ····································································································· 62
표 301 - 퓨즈-레일을 위한 미처리 도체의 최소 단면적 범위 ··················································· 73
표 302 - 퓨즈-레일의 시험 항목과 시료수 대조표 ······································································· 75
표 401 - 동대 고정용 퓨즈-베이스를 위한 미처리 도체의 최소 단면적 범위 ······················· 84
표 402 - 접속용 나사에 적용하는 토크 ··························································································· 85
표 403 - 시험 전류 ······························································································································· 86
표 404 - 퓨즈-베이스 접촉부로부터 퓨즈-링크의 인출력 ··························································· 87
표 501 - “gG” 퓨즈-링크에 대한 협약시간과 협약전류 ······························································ 96
표 502 - “gG” 퓨즈-링크의 규정 용단시간에 대한 게이트 ························································ 97
표 601 - 실린더 캡형 퓨즈-링크의 최대 정격전류 ····································································· 111
표 602 - 퓨즈-홀더의 최대 정격전류 ····························································································· 112
표 603 - 퓨즈-링크에 대한 정격 전력 손실의 최대값 ······························································· 112
표 604 - 퓨즈-홀더의 정격 허용 전력 손실 ················································································· 112
표 605 - 정격전류가 16 A 미만인 “gG” 퓨즈-링크에 대한 협약시간과 협약전류 ············· 113
표 606 - 정격전류가 16 A 미만인 “gG” 퓨즈-링크의
규정 용단시간과 동작시간에 대한 게이트 ······················································································ 113
표 607 - 최소 정격 차단 용량 ········································································································· 113
표 608 - 표시사항의 색 ····················································································································· 114
표 609 - 단단한 동 도체에 대한 단면적의 최소 범위 ······························································· 115
표 610 - “gG” 퓨즈-링크에 대한 0.01 s에서 용단 I 2t 값과 동작 I 2t 값 ······························ 115
표 611 - “aM” 퓨즈-링크에 대한 최대 동작 I 2t 값 ··································································· 115
표 612 - 단자 나사에 적용하는 토크 ····························································································· 116
표 613 - 시험 전류 ····························································································································· 118
표 614 - 판별 시험을 위한 시험 전류와 I 2t 제한값 ··································································· 119
표 701 - “gG” 퓨즈-링크에 대한 협약시간과 협약전류 ···························································· 127
표 702 - “gG” 퓨즈-링크의 규정 용단시간에 대한 게이트 ······················································ 127
표 703 - 동도체의 크기 ····················································································································· 128
표 704 - “gG” 퓨즈-링크에 대한 0.01 s에서 용단 I 2t 값 ························································· 128
- 11 -
표 801 - “gD”와 “gN” 퓨즈-링크에 대한 협약시간과 협약전류 ············································· 139
표 802 - “gD”와 “gN” 퓨즈-링크의 규정 용단시간에 대한 게이트 ······································· 139
표 803 - “gD”와 “gN” 퓨즈-링크에 대한 0.01 s에서 용단 I 2t 값 ·········································· 141
표 804 - 8.3과 8.4에 해당하는 시험을 위한 동도체의 단면적 ················································· 142
표 805 - 예상 전류 200 ㎄에서 “gD”와 “gN” 퓨즈-링크에 대한
최대 컷-오프 전류(I c) ························································································································· 143
표 806 - “gD”와 “gN” 퓨즈-링크에 대한 200 ㎄의
예상 전류에서 최대 동작 I 2t 값 ······································································································· 144
표 901 - 최대 전력 손실값 ··············································································································· 161
표 902 - 최소 정격 차단 용량 ········································································································· 161
표 903 - gU 퓨즈-링크에 대한 0.01 s에서 용단 I 2t 값 ···························································· 163
표 904 - 전력 손실 시험과 온도상승 시험을 위한 도체의 단면적 ········································· 164
- 12 -
저전압 퓨즈
제 2 부 : 전문가용 퓨즈(공업용)의 추가 요구 사항
- 퓨즈 표준 시스템 A ~ I의 예
1 일반 적용범위
전문가용 퓨즈는 일반적으로 전문가에 의해서만 접근이 가능한 위치에 설치하여 사용하고
교환이 가능하도록 설계된다.
- 13 -
퓨즈 시스템 I : 웨지(wedge) 접촉형 gU 퓨즈-링크
참 조: 이전에 이 시스템의 K 60269-2-1의 Ⅵ절에서 기술되었다.
2 인용규격
다음에 언급하는 문서들은 이 기준의 적용을 위해 반드시 필요하다. 연도가 표시된 문헌에
대해서는 인용판(edition)만이 적용된다. 연도가 표시되지 않은 문헌은 최신판(개정안 포함)
이 적용된다.
IEC 60060-1: High-voltage test techniques - Part 1: General definitions and test
requirements
IEC 60112: Method for the determination of the proof and the comparative tracking
indices of solid insulating materials
IEC 60999 (all parts): Connecting devices - Electrical copper conductors - Safety
requirements for screw-type and screwless-type clamping units
ISO 6988: Metallic and other non organic coatings - Sulfur dioxide test with general
condensation of moisture
- 14 -
퓨즈 시스템 A -
블레이드 접촉형 퓨즈-링크로 된 퓨즈
(NH 퓨즈 시스템)
참 조: 이전에 이 시스템은 K 60269-2-1의 Ⅰ절에서 기술되었다.
1 일반사항
1.1 적용범위
• 최소 정격 차단 용량
• 시간-전류 특성
• I 2t 특성
• 구조의 표준조건
• 전력 손실과 허용 전력 손실
2 용어와 정의
비 고: IEC 60947-3 참조
- 15 -
2.1.103 통전 취부용 러그(live gripping-lugs)
참 조: 이전에 K 60269-2-1의 Ⅰ절 2.1.13.1
3 사용조건
K 60269-1을 적용한다.
4 분류
K 60269-1을 적용한다.
5 퓨즈의 특성
5.2 정격전압
교류인 경우에 정격전압의 표준값은 400 V, 500 V와 690 V이다. 직류인 경우에 정격전압은
250 V와 440 V이다. 직류 정격전압의 표준값은 교류 정격전압의 표준값과는 관계가 없다.
예를 들면, 다음의 표준값의 조합이 가능하다: 교류 500 V - 직류 250 V, 교류 500 V - 직
류 440 V, 교류 500 V, 기타.
- 16 -
K 60269-1의 5.3.1에서 제시한 값 이외에 224 A의 정격전류가 추가된다.
In ≤ 4 1 1.5 I n 2.1 I n
4 < In ≤ 16 1 1.5 I n 1.9 I n
5.6.3 게이트
- 17 -
표 102 - “gG” 퓨즈-링크의 규정 용단시간과 동작시간에 대한 게이트
참 조: 이 표는 K 60269-1의 표 3과 관련 있으며, 이전에 K 60269-2-1의 Ⅰ절, 표 Ⅲ과 같다.
5.7.2 정격 차단 용량
표 103 - 최소 정격 차단 용량
참 조: 이 표는 이전에 K 60269-2, 2판의 표 B와 같다.
정격전압 최소 정격 차단 용량
≤ 교류 690 V 50 kA
≤ 직류 750 V 25 kA
6 표시사항
• 크기
- 18 -
K 60269-1 이외에 다음의 표시사항을 적용한다.
• 크기 또는 기준
• 정격 차단 용량
정격전류와 정격전압의 표시는 정면에서 식별이 가능해야 한다. 또한, 퓨즈-링크는 표 104
에서 기술한 것과 같이 표시되어야 한다.
특성 gG aM
표시사항의 색상 흑색 녹색
음각 인쇄된 음각 인쇄된
인쇄 종류 일반 인쇄 일반 인쇄
스트립(strip) 스트립
전압
a)
400 V × ×
500 V × ×
690 V × ×
a)
400 V의 gG인 경우에, 파란색이 허용된다.
7 구조의 표준조건
7.1 기계적 설계
- 19 -
미처리 도체를 위해 설계된 단자는 표 105에서 제공된 단면적 범위 내에서 최소 3개의 연속
적인 크기인 도체의 접속이 가능해야 한다. 러그 단자인 경우에(IEC 60999 참조) 표 111에서
제공된 토크를 적용해야 한다. 다른 단자에 대한 토크값은 제조자의 사용설명서에 제공되어
야 한다.
단면적의 범위
퓨즈-링크의 정격전류 범위 ㎟
크기
A
동 알루미늄
3 315에서 630
4a 500에서 1 250
a)
스트라이커를 가진 퓨즈-링크를 제외하고 신규 설치 시에는 허용되지 않는다.
7.1.3 퓨즈-접촉부
7.1.5 퓨즈-베이스의 구조
- 20 -
제공한 컷-오프 전류와 일치해야 한다.
7.1.7 퓨즈-링크의 구조
권장하는 구조는 다음과 같다; 블레이드 접촉부는 단단한 금속으로 제작되어야 한다. 만일
블레이드 접촉부의 구조가 다른 경우에 제조자는 이 구조가 이 취지에 적합하다는 것을 검
증해야 한다.
7.2 절연 특성
7.7 I 2 t 특성
- 21 -
표 106 - “gG” 퓨즈-링크에 대한 0.01 s에서 용단 I 2 t 값과 동작 I 2 t 값
참 조: 이 표는 K 60269-1의 표 7과 관련 있으며,
이전에 K 60269-2-1의 ⅡA절, 표 Ⅵ와 같다.
In I 2t min I 2 t max
2
A As A2s
2 1.00 23.00
4 6.25 90.25
6 24.00 225.00
8 49.00 420.00
10 100.00 576.00
12 160.00 750.00
224 200 000 520 000
정격전압 U n I 2 t max
V A2s
Un ≤ 400 18 I n2
400 < Un ≤ 500 24 I n2
500 < Un ≤ 690 35 I n2
- 22 -
표 108 - 판별을 위한 용단 I 2 t 값
참 조: 이 표는 이전에 K 60269-2-1의 Ⅰ절, 표 E와 같다.
In I 2t min I p 에서
A A2s A
16 250 500
20 450 670
25 810 900
32 1 400 1 180
40 2 500 1 580
50 4 000 2 000
63 6 300 2 510
80 10 000 3 160
100 16 000 4 000
125 24 000 4 900
160 42 500 6 520
200 78 000 8 830
8 시험
8.1.6 퓨즈-홀더의 시험
- 23 -
표 109 - 퓨즈-홀더의 시험 항목과 시료수 대조표
참 조: 이 표는 K 60269-1의 표 14와 관련 있으며, 이전에 K 60269-2-1의 Ⅰ절, 표 Ⅷ과 같다.
퓨즈-홀더의 시료수
시험 항목
1 1 1 1 1 1 5
8.9 열에 대한 내성의 검증 ×
8.2.2.1 시험전압의 인가 지점
8.2.3.2 시험전압값
400 4
500 4
690 6
8.2.3.3 시험방법
- 24 -
8.2.4 시험결과의 판정
8.2.5 트래킹에 대한 내성
8.3.1 퓨즈의 배치
In 크기 나사의 크기 토크
A Nm
160 00 M 8 10
a)
160 0 M 8 10
250 1 M 10 32
400 2 M 10/12 32
630 3 M 10/12 32
1 000 4 M 12 56
1 250 4a 2 × M 12/16 56
a)
스트라이커를 가진 퓨즈-링크를 제외하고 신규 설치 시에는 허용되지 않는다.
8.3.2 온도상승의 측정
- 25 -
8.3.4.1 퓨즈-홀더의 온도상승
8.3.4.2 퓨즈-링크의 전력 손실
8.5.5.1.1 퓨즈의 배치
- 26 -
표 112 - 시험 전류
참 조: 이 표는 이전에 K 60269-2-1, Ⅰ절의 표 G와 같다.
크기 컷-오프 전류
㎄
00 22...24
0 22...24
1 34...37
2 44...48
3 65...70
8.5.5.1.2 시험방법
8.5.5.1.3 시험결과의 판정
8.5.8 시험결과의 판정
- 27 -
는 K 60269-1의 표 20을 따른다.
n
690 V 퓨즈에 대하여 시험전압은 × 이다.
n
다른 모든 퓨즈에 대하여 시험전압은 × 이다.
최소 용단 I 2t 최대 동작 I 2t
In 예상 I 예상 I
I 2t I 2t 판별비
A r.m.s 2 r.m.s
As A 2s
㎄ ㎄
2 0.013 0.67 0.064 16.4
4 0.035 4.90 0.130 67.6
6 0.064 16.40 0.220 193.6
계산할 수 없음
8 0.100 40.00 0.310 390.0
10 0.130 67.60 0.400 640.0
12 0.180 130.00 0.450 820.0
16 0.270 291.00 0.550 1 210.0
20 0.400 640.00 0.790 2 500.0
25 0.550 1 210.00 1.000 4 000.0
32 0.790 2 500.00 1.200 5 750.0
40 1.000 4 000.00 1.500 9 000.0
50 1.200 5 750.00 1.850 13 700.0
63 1.500 9 000.00 2.300 21 200.0
80 1.850 13 700.00 3.000 36 000.0
100 2.300 21 200.00 4.000 64 000.0
125 3.000 36 000.00 5.100 104 000.0
160 4.000 64 000.00 6.800 185 000.0 1 : 1.6
200 5.100 104 000.00 8.700 302 000.0
224 5.900 139 000.00 10.200 412 000.0
250 6.800 185 000.00 11.800 557 000.0
315 8.700 302 000.00 15.000 900 000.0
400 11.800 557 000.00 20.000 1 600 000.0
500 15.000 900 000.00 26.000 2 700 000.0
630 20.000 1 600 000.00 37.000 5 470 000.0
800 26.000 2 700 000.00 50.000 10 000 000.0
1 000 37.000 5 470 000.00 66.000 17 400 000.0
1 250 50.000 10 000 000.00 90.000 33 100 000.0
- 28 -
8.9 열에 대한 내성의 검증
본체나 필터에 유기물을 포함한 퓨즈-링크는 위에서 기술한 것과 동일한 시험을 해야 한다.
이와 같은 퓨즈-링크는 I 1과 I 5의 시험전류를 차단해야 한다.
8.9.1 퓨즈-베이스
8.9.1.1 시험 배치
8.9.1.2 시험방법
부하를 차단하고 3 분 후에, 인장력 F max(표 118 참조)를 더미에 천천히 인가한다. 인장력
F max를 15 s간 가한다.
8.9.1.3 시험결과의 판정
- 29 -
칠 정도의 움직임이 없어야 한다. 더미의 인출 후에 그림 102의 치수를 고려한다. 퓨즈-베
이스의 절연 고정부는 부서지거나 균열의 흔적이 나타나지 않아야 한다.
8.9.2.1 시험 배치
8.9.2.2 시험방법
8.9.2.3 시험결과의 판정
8.10.1 퓨즈의 배치
8.10.1.1 접촉부
- 30 -
K 60269-1의 8.10.1을 적용한다.
8.10.1.2 단자 클램프
나사산 토크
Nm
M5 2.6
M6 4.5
M8 11
M10 21
M12 38
- 31 -
표 115 - 8.10에 해당하는 시험을 위한
알루미늄 도체의 단면적
참 조: 이 표는 이전에 K 60269-2-1, Ⅰ절의 표 R과 같다.
정격전류 단면적
A ㎟
40 25
50 25
65 35
80 50
100 70
125 95
160 95
200 150
250 185
315 240
400 300
8.10.2 시험방법
}
시험전류: 협약 불용단 전류 I nf
- 32 -
정격전압 보다 낮은 시험전압을 사용해도 좋다.
무부하 주기 동안 시료는 35 ℃이하로 냉각한다; 부가적인 냉각 장치(예를 들면, 팬)가 허용
된다.
T
8.10.2.1 접촉부
8.10.2.2 단자 클램프
- 33 -
단단한 도체인 경우에는 중앙에 구멍을 뚫어야 하고 연성(stranded) 도체인 경우에는 도체
외부에 나선을 감고 중앙에 구멍을 뚫어야 한다. 알루미늄 도체인 경우에 예를 들면 용접된
조정장치(welded equalizer)와 같은 기구(알루미늄 케이블을 자른다; 도체 각각의 부분을 합
쳐서 용접한다. 그 다음에 용접된 두 부분을 용접하고 용접된 부분에 구멍을 뚫어서 측정한
다.)를 사용하는 것과 같은 특별한 사전 조치가 필요하다.
I n에서 온도상승의 검증
R cl 0의 측정
50 주기
R cl 50의 측정
200 주기
R cl 250의 측정
I n에서 온도상승의 검증
250 주기
R cl 500의 측정
250 주기
R cl 750의 측정
I n에서 온도상승의 검증
8.10.3 시험결과의 판정
8.10.3.1 접촉부
- 34 -
≤
≤
≤
8.10.3.2 단자 클램프
허용되는 변화
%
- 35 -
8.11 기계적 시험과 기타 시험
적절한 시험 설비로 천천히 인출할 때, 측정한 인출력 F (그림 108 참조)는 표 118에 규정된
제한값 이내이어야 한다.
인출력
크기 F min F max
N N
00 60 250
0 80 300
1 110 350
2 150 400
3 210 400
- 36 -
우에는, 적절한 방법으로 너트가 도는 것을 예방하기 위한 조치가 필요하다.
8.11.1.8.1 시험 배치
8.11.1.8.2 시험방법
8.11.1.8.3 시험결과의 판정
8.11.2.3 녹에 대한 내성의 검증
8.11.2.3.1 ISO 6988에 따른 0.2 %의 SO2(SFW 0.2 S)를 포함한 순환식 가습 대기로 시험
을 실시해야 한다; 반복 주기 : 1
- 37 -
IEC 60664-1에 따른 오손등급≥3의 환경에서 사용하기 위한 퓨즈-링크와 퓨즈-베이스는
SFW 2.0 S로 5 주기 동안 시험해야 한다. 이것은 적절하게 표시되어야 한다.
8.11.2.4.1 시험방법
168 시간 동안
통전부를 지지하기 위한 부품이 주조물로 된 장치에 대하여 (150 ± 5) ℃
커버에 대하여 (100 ± 5) ℃
1 시간 이상
밀폐용 화합물(sealing compound); 표시사항의 안정성에 대하여 (150 ± 5) ℃
8.11.2.4.2 시험결과의 판정
- 38 -
기호
A 지시 장치
B 접촉부
C 끝단(endplate)
D 끝면(stop face)
E 상세도 Y (단면도)
F 둥근 모양, 비고 참조
G 접촉면
그림에서 나타낸 비고와 치수를 제외하고 그림에 의해서 설계가 제한되지는 않는다.
- 39 -
정격 전력 손실 P n의 최대값
gG gM
교류 400 V 교류 500 V 교류 690 V 교류 400 V와 교류 690 V
크기 교류 500 V
In Pn In Pn In Pn In Pn In Pn
A W A W A W A W A W
000 100 5.5 100 7.5 63 12 100 7.5 80 12
00 160 12 160 12 100 12 100/160 7.5/12 160 12
0 160 12 160 16 100 25 160 16 100 25
1 250 18 250 23 200 32 250 23 250 32
2 400 28 400 34 315 45 400 34 400 45
3 630 40 630 48 500 60 630 48 630 60
4 - - 1 000 90 800 90 1 000 90 1 000 90
4a 1250 90 1 250 110 1 000 110 1 250 110 1 250 110
그림 101 - (계속)
- 40 -
a1 a2 a3 a4 b1 b2 b3 b4 c1 c2 d e1 e2 e3 e4 f z
크기 최소 최소 최대 최소 ±0.8 최대 최대 ±0.2 최대 최대
1) 2) 1) 1) 12) 12) 12) 12) 5) 6) 6)
78.5 54 45 49 15 4.5 5 12 35 10 2 41 21 16 6 8 3
000 ±1.5 -6 ±1.5 ±1.5 -1 +1 +5
-0.5 -2
78.5 54 45 49 15 4.5 5 12 35 10 2 48 30 20 6 15 3
00 ±1.5 -6 ±1.5 ±1.5 -1 +1 ±5
-0.5
125 68 62 68 15 4.5 5 12 35 11 2 48 40 20 6 15 3
0 ±2.5 -8 +3 +1.5 -2 +1.5 ±5
-1.5 -3 -0.5
135 75 62 68 20 5 6 17 40 11 2.5 53 52 20 6 15 5
1 ±2.5 -10 ±2.5 ±2.5 -2 +1.5 +5
-0.5 -2
150 75 62 68 25 8 6 22 48 11 2.5 61 60 20 6 15 5
2 ±2.5 -10 ±2.5 ±2.5 -2 +1.5 +5
-0.5 -2
150 75 62 68 32 11 6 29 60 11 2.5 76 75 20 6 18 5
3 ±2.5 -10 ±2.5 ±2.5 -2 +1.5 +5
-0.5 -2
1)
치수 a1, a3와 a4의 중심은 a2의 중심으로부터 1.5 ㎜ 이상 벗어나지 않아야 한다.
2)
치수 a2는 블레이드 양쪽 끝면(stop face)의 전체 면적(b2 × 최소 4)에 대하여 측정해야 한다. 이 면적 밖은
a2의 최대 치수를 적용한다.
3)
절연물.
4)
블레이드 접촉부는 축방향으로 일직선이어야 하고 접촉부 표면은 평면이어야 한다.
5)
교체 핸들을 위한 부착물(상세도 X).
6)
퓨즈-링크 외함의 최대 치수, 이 제한값 내에서 퓨즈-링크는 예를 들면 정사각형, 직사각형, 원형, 타원형,
다각형 등 어떠한 형태이어도 좋다.
7)
크기 4인 퓨즈-링크에 대하여 슬롯(slot)은 의무사항이다.
8)
지시 장치. 지시 장치의 위치는 제조자에 의해 선택.
9)
통전부, 취부용 러그는 절연할 수도 있다.
10)
교체 핸들(상세도 X)을 위한 부착물 외에 절연부로부터 돌출되는 것은 허용되지 않는다.
11)
인터록(interlock) 장치가 있는 회전 설비(swivel unit)에만 사용됨.
12)
크기 0, 1, 2와 3 내에서 정격 전류가 중복되는 부분이 존재한다. 더 작은 크기의 치수가 허용된다.
13)
모든 모서리는 베이스 접촉부의 접촉면에 손상을 주지 않기 위해서 둥글어야 한다.
그림 101 - (마지막)
참 조: 이 그림은 이전에 K 60269-2-1, Ⅰ절의 그림 1 (Ⅰ)와 같다.
- 41 -
기호
A 격벽
B 통전부로 간주되는 영역
C 접촉부
D 접촉면
단위 : ㎜
그림에서 나타낸 비고와 치수를 제외하고 그림에 의해서 설계가 제한되지는 않는다.
Size g h n1 n2 p1 p2 r s t v w1 w2 x y z
±1 ±1.5 최대 최대 최대 ±1.5 최소 최대 최소 최소 ±0.5 최대
8) 7) 7) 7) 7) 7)
- 42 -
크기 정격전류 정격 허용 전력 손실
A W
00 160 12
13)
0 160 25
1 250 32
2 400 45
3 630 60
4 1 000 90
4a 1 250 100
단위 : ㎜
9) 12) 9) 11)
d ± 0.25
a b c
Size 구멍 e ± 0.5
최소 최소 최소 나사산
지름
00 20 20 3 9 M8 10
13)
0 23 20 3 9 M8 10
1 24 25 4 11 M10 12.5
10) 10)
2 28 25 4 11 M10 12.5
10) 10)
3 35 30 5 11 M10 15
4 45 40 8 14 M12 20
4a 45 40 10 18 M16 20
그림 102 - (계속)
- 43 -
1)
이 부분은 통전부로 간주한다.
2)
치수 v의 최대값은 접촉 지점을 정의하기 위한 것이다. 최소한 2개의 b2 × 최소 4인 면적 내에서 하나의 퓨
즈-링크 접촉 지점이 있어야 한다. 또한, 치수 v는 절연 접촉 커버로 접촉되어도 좋다.
3)
접촉면의 높이. 또한 비록 접촉면이 평탄하지 않고 홈이 있거나 분리되어 있더라도 그림 101에 따른 블레이
드 접촉형 퓨즈-링크의 삽입이 가능해야 한다.
4)
크기 4에 대한 치수. 크기 4에 대하여 고정 나사는 의무사항이다; M12 나사산일 때.
5)
크기 4를 제외하고 탄성 있는 접촉면. 보조 수단에 의한 접촉력.
6)
인터록(interlock) 장치가 있는 회전 설비(swivel unit)에만 사용됨.
7)
이와 같은 값들은 퓨즈-베이스의 호환성이 요구되는 경우에만 의무사항이다.
8)
단극 퓨즈-베이스를 조합하여 다극으로 구성할 때, 안전상 n1에 규정된 최대 치수에서 함께 사용할 수 있는
절연 배리어(예를 들면, 권장 치수 “g ”인 격벽)를 설치할 필요가 있다.
9)
“d ”와 “e ”의 치수를 따른다면 “a”와 “b”가 더 큰 치수이거나 형태의 변형, 예를 들면 모서리가 둥글거나 원
형과 같은 변형은 구조적 특색으로 허용된다.
10)
구멍 지름 14에 M12의 나사산은 허용한다.
11)
도체를 연결할 때 발생하는 기계적 스트레스를 접속의 변형 없이 견딜 수 있다면, 치수 “c”는 작아도 좋다.
나사산의 형태는 시험-토크 요구 사항을 따라야 한다.
12)
치수 “a”는 접속부의 상단에서 측정해야 한다.
13)
스트라이커를 가진 퓨즈-링크를 제외하고 신규 설치 시에는 허용되지 않는다.
그림 102 - (마지막)
- 44 -
그림에서 나타낸 비고와 치수를 제외하고 그림에 의해서 핸들의 설계가 제한되지는 않는다.
단위 : ㎜
크기 거리
L M-M1 M-M2
00 160 0±3 -
0 ... 3 160 - 11 ± 3
크기 00인 경우 M1
크기 0 ... 3인 경우 M2
M = 결합의 중심
L = 퓨즈-링크의 삽입과 인출을 위한 리프트(lift)
그림 103 - 교체 핸들
참 조: 이 그림은 이전에 K 60269-2-1, Ⅰ절의 그림 3 (Ⅰ)와 같다.
- 45 -
그림 104 - “gG” 퓨즈-링크에 대한 시간-전류 영역 (다음 쪽에 그림 계속)
참 조: 이 그림은 이전에 K 60269-2-1, Ⅰ절의 그림 4 (Ⅰ)와 같다.
- 46 -
그림 104 - (계속)
- 47 -
그림 104 - (계속)
- 48 -
그림 104 - (계속)
- 49 -
그림 104 - (마지막)
- 50 -
취부용 러그의 치수는 그림 101 참조.
단위 : ㎜
다른 치수는 그림 101 참조
P* R ** 대(bar)
mΩ
크기 I
W 갯수 직경
0
00 30.5 12 0.47 1 7
-3
14) 0
0 46 25 0.97 1 6
-4
0
1 46 32 0.51 1 8
-4
0
2 46 45 0.281 2 8
-4
0
3 46 60 0.151 3 9
-4
0
4 54 90 0.09 3 12
-6
0
4a 54 110 0.07 4 12
-6
*
크기에 상응하는 최대 정격전류에서
**
취부용 러그에서 측정한; ±2 %의 허용오차로 조정된
- 51 -
그림 106 - K 60269-1의 8.3.4, 퓨즈 시스템 A의 8.3.4.1,
8.3.4.2와 8.10.2에서의 측정 지점
참 조: 이 그림은 이전에 K 60269-2-1, Ⅰ절의 그림 6 (Ⅰ)와 같다.
- 52 -
그림 108 - 8.9.1과 8.11.1.2에 따른 인출력을 측정하기 위한 측정 장치의 예
참 조: 이 그림은 이전에 K 60269-2-1, Ⅰ절의 그림 8 (Ⅰ)와 같다.
- 53 -
그림 109 - 취부용 러그의 기계적 강도를 검증하기 위한 설비
(8.11.1.8 참조)
참 조: 이 그림은 이전에 K 60269-2-1, Ⅰ절의 그림 9 (Ⅰ)와 같다.
- 54 -
단위: ㎜
기호
1 도체
2 클램프
3 퓨즈-베이스
4 더미 퓨즈-링크
그림 110 - 8.10.2에 따른 시험 지점
참 조: 이 그림은 이전에 K 60269-2-1, Ⅰ절의 그림 10 (Ⅰ)와 같다.
- 55 -
그림 111 - 기준 퓨즈-베이스
참 조: 이 그림은 이전에 K 60269-2-1, Ⅰ절의 그림 11 (Ⅰ)와 같다.
- 56 -
그림 112 - 이격 취부용 러그의 기호
참 조: 이 그림은 이전에 K 60269-2-1, Ⅰ절의 그림 12 (Ⅰ)와 같다.
- 57 -
부속서 A
(참고)
케이블 과부하 보호를 위한 특수 시험
(퓨즈 시스템 A의 8.4.3.5 비고 참조)
A.1 퓨즈의 배치
- 58 -
퓨즈 시스템 B -
블레이드 접촉형 스트라이커 퓨즈-링크로 된 퓨즈
(NH 퓨즈 시스템)
참 조: 이전에 이 시스템은 K 60269-2-1의 ⅠA절에서 기술되었다.
1 일반사항
1.1 적용범위
• 최소 정격 차단 용량
• 시간-전류 특성
• I 2t 특성
• 구조의 표준조건
• 전력 손실과 허용 전력 손실
2 용어와 정의
K 60269-1을 적용한다.
3 사용조건
K 60269-1을 적용한다.
4 분류
K 60269-1을 적용한다.
5 퓨즈의 특성
- 59 -
K 60269-1과 다음의 추가 요구 사항을 적용한다.
5.2 정격전압
5.7.2 정격 차단 용량
6 표시사항
퓨즈 시스템 A의 6을 참조한다.
7 구조의 표준조건
7.1 기계적 설계
- 60 -
퓨즈-링크와 퓨즈-베이스의 치수는 그림 201과 202에서 제공한다.
7.1.3 퓨즈-접촉부
7.1.7 퓨즈-링크의 구조
7.7 I 2 t 특성
8 시험
- 61 -
8.1.6 퓨즈-홀더의 시험
기준 A 기준 B
크기
0에서 4 1에서 4a 00
S0max ㎜ 1 1 1
S1 ㎜ 13에서 20 최소 10 최소 5.5
0과 1 위치 간의 F min N 8 1 1
1 위치에서 F max N 20 20 20
8.9 열에 대한 내성의 검증
- 62 -
8.9.1 퓨즈-베이스
8.9.1.1 시험 배치
8.9.1.2 시험방법
8.9.1.3 시험결과의 판정
8.9.2.1 시험 배치
8.9.2.2 시험방법
8.9.2.3 시험결과의 판정
- 63 -
한다. 표면을 크롬으로 도금한 연마된 강철 퓨즈-링크를 퓨즈-베이스에 3회 삽입한다. 퓨즈
-링크의 블레이드 접촉부의 치수는 그림 201의 치수와 동일하게 한다.
적절한 시험 설비로 천천히 인출할 때, 측정된 인출력 F (그림 108 참조)는 퓨즈 시스템 A
의 표 118에 규정된 제한값 이내이어야 한다.
8.11.2.4.1 시험방법
- 64 -
단위 : ㎜
그림에서 나타낸 비고와 치수를 제외하고 그림에 의해서 퓨즈-링크의 설계가 제한되지는 않는다.
- 65 -
단위 : ㎜
정격 전력 손실 P n의 최대값
gG gM
그림 201 - (계속)
- 66 -
기준 A
크기 a1 a2 a’2 a3 a4 b c1 c2 d e1 e2 e3 e4 f k l m
최소 ±0.8 최대 최대 ±0.2 최대
1) 2) 1) 1) 12) 5) 6) 6)
+0 +3 +1.5 +1.5
0 125 ± 2.5 68 - 8 73 62 68 15 35 11 - 2 2 48 45 20 ± 5 6 15 14.5 14 25 ± 0.5
-1.5 -1.5 -3 -0.5
+0 +1.5 +5
1 135 ± 2.5 75 - 10 79 62 ± 2.5 68 ± 2.5 20 40 11 - 2 2.5 53 52 20 6 15 16 14.5 25.5 ± 0.5
-1.5 -0.5 -2
+0 +1.5 +5
2 150 ± 2.5 75 - 10 79 62 ± 2.5 68 ± 2.5 25 48 11 - 2 2.5 61 60 20 6 15 19 14.5 25.5 ± 0.5
-1.5 -0.5 -2
+0 +1.5 +5
3 150 ± 2.5 75 - 10 79 62 ± 2.5 68 ± 2.5 32 60 11 - 2 2.5 76 75 20 6 18 24 14.5 25.5 ± 0.5
-1.5 -0.5 -2
+1.5 +5
4 200 ± 3 최대 90 62 ± 2.5 68 ± 2.5 49 87 11 - 2 2.5 110 105 20 8 25 27.5 14.5 -
-0.5 -2
기준 B
크기 a1 a2 a3 a4 b c1 c2 d e1 e2 e3 e4 f k l m
최소 ±0.8 최대 최대 ±0.2 최대
1) 2) 1) 1) 12) 5) 6) 6)
+1.5
00 78.5 ± 2.5 54 - 6 45 ± 1.5 49 ± 1.5 15 35 10 - 1 2 48 30 20 ± 5 6 15 0 21.5 16.6 ± 0.5
-0.5
+1.5 +5
1 135 ± 2.5 75 - 10 62 ± 2.5 68 ± 2.5 20 40 11 - 2 2.5 53 52 20 6 15 13.7 20.5 23.5 ± 0.5
-0.5 -2
+1.5 +5
2 150 ± 2.5 75 - 10 62 ± 2.5 68 ± 2.5 25 48 11 - 2 2.5 61 60 20 6 15 16.2 27.3 23.5 ± 0.5
-0.5 -2
+1.5 +5
3 150 ± 2.5 75 - 10 62 ± 2.5 68 ± 2.5 32 60 11 - 2 2.5 76 75 20 6 18 17.0 35.6 23.5 ± 0.5
-0.5 -2
+1.5
4a11) 200 ± 3 최대 100 84 ± 3 90 ± 3 49 85 ± 2 11 - 2 2.5 110 102 30 ± 10 6 30 24.0 49.0 -
-0.5
- 67 -
1)
치수 a1, a3와 a4의 중심은 a2의 중심으로부터 1.5 ㎜ 이상 벗어나지 않아야 한다.
2)
치수 a2는 블레이드의 하단에서부터 블레이드 양쪽에 대하여 최소 4 ㎜ 이상의 폭으로 전체 면적(b 최소/2)에 대하여 측정해야 한다. 이 면적 밖은 a2의 값보다 적어도 좋다.
3)
절연물.
4)
접촉부 표면은 평면이거나 빗살모양이어도 좋다.
5)
교체 핸들을 위한 부착물(상세도 X).
6)
퓨즈-링크 외함의 최대 치수, 이 제한값 내에서 퓨즈-링크는 예를 들면 정사각형, 직사각형, 원형, 타원형, 다각형 등 어떠한 형태이어도 좋다.
7)
크기 4인 퓨즈-링크에 대하여 슬롯(slot)은 의무사항이다.
8)
스트라이커.
9)
통전부, 취부용 러그는 절연할 수도 있다.
10)
교체 핸들(상세도 X)을 위한 부착물 외에 절연부로부터 돌출되는 것은 허용되지 않는다.
11)
인터록(interlock) 장치가 있는 회전 설비(swivel unit)에만 사용됨.
12)
크기 0, 1, 2와 3 내에서 정격 전류가 중복되는 부분이 존재한다. 더 작은 크기의 치수가 허용된다.
13)
블레이드 접촉부의 모서리는 둥글거나 다른 어떤 적절한 모양으로 될 수도 있다.
그림 201 - (마지막)
- 68 -
단위 : ㎜
그림에서 나타낸 비고와 치수를 제외하고 그림에 의해서 퓨즈-베이스의 설계가 제한되지는 않는다.
- 69 -
기준 A
크기 h n1 n2 p1 p2 r s t v w1 w2 x y z
±1.5 최대 최대 최대 ±1.5 최소 최대 최소 최소 ±0.5 최대
7) 7) 7) 7) 7)
기준 B
크기 h n1 n2 p1 p2 r s t v v’ w1 w2 x y z
±1.5 최대 최대 최대 ±1.5 최소 최대 최소 최소 ±0.5 최대
7) 7) 7) 7) 7)
크기 정격전류 정격 허용 전력 손실
A W
00 160 12
0 160 25
1 250 32
2 400 45
3 630 60
4 1 000 90
4a 1 250 110
그림 202 - (계속)
- 70 -
1)
이 부분은 통전부로 간주한다.
2)
치수 v의 최대값은 접촉 지점을 정의하기 위한 것이다. 퓨즈-링크의 블레이드 접촉부 하단에서부터 b 최소
/2의 범위 내에서 하나의 퓨즈-링크 접촉 지점이 있어야 한다. 블레이드 접촉부의 상단에서 v값을 측정할
필요는 없다.
3)
접촉면의 높이. 또한 비록 접촉면이 평탄하지 않고 홈이 있거나 분리되어 있더라도 그림 201에 따른 블레이
드 접촉형 퓨즈-링크의 삽입이 가능해야 한다.
4)
크기 4에 대한 치수. 크기 4에 대하여 고정 나사는 의무사항이다; M12 나사산일 때.
5)
크기 4를 제외하고 탄성 있는 접촉면. 보조 수단에 의한 접촉력.
6)
스트라이커에 의해 동작되는 장치를 위한 공간. 스트라이커를 수신하기 위한 장치가 장착된 퓨즈-베이스는
n2보다 더 큰 치수를 가져도 좋다.
7)
이와 같은 값들은 퓨즈-베이스의 호환성이 요구되는 경우에만 의무사항이다.
8)
단극 퓨즈-베이스를 조합하여 다극으로 구성할 때, 안전상 n1에 규정된 최대 치수에서 함께 사용할 수 있는
절연 배리어(예를 들면, 격벽)를 설치할 필요가 있다.
9)
인터록(interlock) 장치가 있는 회전 설비(swivel unit)에만 사용됨.
10)
v'는 세로 방향의 끝 부분 사이를 측정한 값이다.
기준 A
크기 j1 j2 j3 j4
최소 최대 최소 최대 최소 최대
0 66 10.5 27 30 - -
1 75.5 12 27 30 - -
2 79.5 15 27 30 - -
3 87.5 20 27 30 - -
4 - 23.5 - - 6.5 9
기준 B
j1' j2 j3'
크기
최소 최대 최소 최대
00 21.5 0 17.5 19.5
1 30.5 13.7 24.5 26.5
2 27.3 16.2 24.5 26.5
3 35.3 17.0 24.5 26.5
4a - 24.0 - -
그림 202 - (마지막)
- 71 -
퓨즈 시스템 C -
퓨즈-레일
(NH 퓨즈 시스템)
참 조: 이전에 이 시스템은 K 60269-2-1의 ⅠB절에서 기술되었다.
1 일반사항
1.1 적용범위
2 용어와 정의
2.1.301 퓨즈-레일(fuse-rails)
참 조: 이전에 K 60269-2-1의 ⅠB절 2.1.13
3 사용조건
K 60269-1을 적용한다.
4 분류
K 60269-1을 적용한다.
5 퓨즈의 특성
5.2 정격전압
- 72 -
퓨즈 시스템 A의 5.2를 적용한다.
5.3.2 정격전류
5.5.1 정격 허용 전력
6 표시사항
퓨즈 시스템 A의 6을 참조한다.
7 구조의 표준조건
7.1 기계적 설계
단면적의 범위
퓨즈-레일의 정격전류 mm2
크기
A
동 알루미늄
3 630 적용값 없음
- 73 -
7.2 절연 특성
8 시험
8.1.6 퓨즈-홀더의 시험
- 74 -
표 302 - 퓨즈-레일의 시험 항목과 시료수 대조표
참 조: 이 표는 K 60269-1의 표 14와 관련 있으며, 이전에 K 60269-2-1의 ⅠB절, 표 Ⅷ과 같다.
퓨즈-레일의 시료수
시험 항목
1 1 1 2
8.1.4 치수 ×
8.2 절연 특성 ×
8.3 온도상승과 전력 손실 ×
8.3 온도상승과 전력 손실 ×
8.10.1.1 접촉부의 성능 ×
8.11.2.3 녹에 대한 내성 ×
1)
8.11.1.2에 따른 인출력을 만족한다면 필요 없음
2)
L1(첫 번째 상)의 더미가 보장된다.
8.3.1 퓨즈의 배치
- 75 -
험결과의 판정을 위하여 퓨즈 시스템 A의 8.10.3.1을 적용한다.
8.5.5.1.1 퓨즈의 배치
8.5.5.1.2 시험방법
8.10.1 퓨즈의 배치
8.10.1.2 단자 클램프
- 76 -
8.11.2.4.1 시험방법
- 77 -
그림에서 나타낸 비고와 치수를 제외하고 그림에 의해서 퓨즈-레일의 설계가 제한되지는 않는다.
- 78 -
설계 크기 동대계통 c d1 d2 h1 h2 2) m 1 1) m 2 m3 m4 m5 n2 r s t v z
중심거리 최대 ±0.5 최소 최소 최대 +20 ±2.5 최대 ±10 +15 최대 최소 최대 최소 최대
-5
00 100 40 9 16 90 155 100 165 70 17 21 15 56.5 3
00 185 175 285 185 280 ±1.5
기준
1 60 14 22 35 100 17 38 21 80 5
A
2 185 175 285 185 280 46 27 ±3
3 65 110 20 58 33
00 100 9 16 10 90 155 100 165 30 60 17 21 15 56.5 3
00 185 175 285 185 280 ±1.5
기준
1 14 22 40 175 285 185 280 50 100 17 38 21 80 5
B
2 185 46 27 ±3
3 20 58 33
00 100 9 16 25 90 155 100 165 30 25 60 17 21 15 56.5 3
00 185 175 285 185 280 ±1.5
기준
1 14 22 40 175 285 185 280 40 55 80 17 38 21 80 5
C
2 185 46 27 ±3
3 20 58 33
1)
다른 치수도 허용된다. 다른 치수는 형식시험성적서와 제조자의 기술문서에 기록되어야 한다.
2)
최대 천체 치수
크기 정격전류 정격 허용 전력 손실
A W
00 160 12
1 250 32
2 400 45
3 630 60
그림 301 - (마지막)
- 79 -
설계 기준 A
그림에서 나타낸 비고와 치수를 제외하고 그림에 의해서 퓨즈-레일의 설계가 제한되지는 않는다.
- 80 -
설계 기준 B와 C
그림 302 - (마지막)
- 81 -
퓨즈 시스템 D -
동대 고정용 퓨즈-베이스 (40 mm 계통)
(NH 퓨즈 시스템)
참 조: 이전에 이 시스템은 K 60269-2-1의 ⅠC절에서 기술되었다.
1 일반사항
1.1 적용범위
• 구조의 표준조건
• 허용 전력 손실
2 용어와 정의
3 사용조건
K 60269-1을 적용한다.
4 분류
- 82 -
K 60269-1을 적용한다.
5 퓨즈의 특성
5.2 정격전압
5.3.2 정격전류
5.5.2 일렬 퓨즈-베이스의 정격 허용 전력 손실
6 표시사항
퓨즈 시스템 A의 6을 참조한다.
7 구조의 표준조건
7.1 기계적 설계
- 83 -
크기가 00인 63 A 일렬 퓨즈-베이스의 단자는 표 401에서 제공한 범위의 도체가 접속이 가
능해야 한다.
단면적의 범위
퓨즈-베이스의 정격전류 mm2
크기
A
동 알루미늄
00 63 2.5에서 25 -
- 84 -
다. 접촉력은 스프링을 장착한 부품 또는 다른 적절한 방법으로 보증되어야 한다.
8 시험
8.3.1 퓨즈의 배치
In 토크
크기
A Nm
2 × 63 00 6
8.5.5.1.1 퓨즈의 배치
- 85 -
표 403 - 시험 전류
참 조: 이 표는 이전에 K 60269-2-1, ⅠC절의 표 HH와 같다.
크기 컷-오프 전류
kA
1)
00 4...5
8.9.1 퓨즈-베이스
8.9.1.1 시험 배치
8.9.1.3 시험결과의 판정
8.10.1 퓨즈의 배치
8.10.2 시험방법
- 86 -
중심 간의 거리가 40 ㎜인 동대를 사용한 계통을 위한 퓨즈-베이스 각각의 접촉부 부품이
먼 경우에 저항 측정 지점은 접촉면과 가능한 가깝게 해야 한다.
인출력
크기 정격전류 F min F max
N N
1)
00 63 80 200
8.11.2.4.1 시험방법
- 87 -
단위 : ㎜
상단 결선을 위한 O형(version) 하단 결선을 위한 U형
기호
A 연결 스트립(connection strip)
B 격벽(partition wall)
C 통전부와 그 밖의 부품의 면적
2)
D 접촉부, 각주 참조
E 차페물(protection shield)
크기 a v r g h3) k e 14) l 4)
±1 최소 ±1 +2 ±2.5
-4
1)
동대의 상단면과 삽입된 퓨즈-링크의 베이링 숄더(bearing shoulder) 간의 치수는
(그림 101의 치수
c1과 e 3 참조).
2)
동대 고정 베이스는 동대 위에 두어도 좋다.
3)
계기판에서 사용하기 위한 권장값.
4)
평각 결선(flat connections)에 대해서만.
- 88 -
단위 : ㎜
상단 결선을 위한 O형(version) 하단 결선을 위한 U형
기호
A 연결 스트립
B 격벽
C 통전부와 그 밖의 부품의 면적
2)
D 접촉부, 각주 참조
E 차페물
크기 a v r g h3) k e 14) l 4)
±1 최소 ±1 +2 ±2.5
-4
- 89 -
단위 : ㎜
상단 및 하단 결선을 위한 O형과 U형
기호
A 외부 격벽
B 연결 스트립
C 격벽
D 통전부와 그 밖의 부품의 면적
2)
E 접촉부, 각주 참조
F 보호 커버
크기 a v r g h3) e 1 4) l 4)
±1 ±1.5 최소 ±1 +2
-4
00 33 56.5 ± 1.5 17 47 50 10 18
- 90 -
단위 : ㎜
기호
1 단극(3극은 유닛의 형태이어도 좋다)
2 결선
3 케이블, 각 케이블의 길이는 1 m
- 91 -
단위 : ㎜
기호
1 일렬 배치된 두 단극 퓨즈-베이스
(단극 6개 = 2 × 3 극이 유닛이어도 좋다)
2 결선
3 케이블, 각 케이블의 길이는 1 m
- 92 -
단위 : ㎜
기호
1 단극 시료(또는 다극 시료의 한 극)
2 지지대
3 클램프 단자의 경우 어댑터(adaptor)를 권장한다.
4 전원
- 93 -
단위 : ㎜
기호
1 용접
2 CuMn12Ni
3 은도금된 구리 합금
In I P 1) R 2) 대(bar)
mΩ
크기
A W 갯수 직경
+0
00 63 30.5 7.5 1.88 1 3.5
-3
1)
두 번째 열에서 제시한 I n에서
2)
취부용 러그에서 측정한; ±2 %의 허용오차로 조정된
그림 407 - 더미 퓨즈-링크
참 조: 이 그림은 이전에 K 60269-2-1, ⅠC절의 그림 6 (ⅠC)와 같다.
- 94 -
퓨즈 시스템 E -
볼트 결합형 퓨즈-링크로 된 퓨즈
(BS 볼트로 된 퓨즈 시스템)
참 조: 이전에 이 시스템은 K 60269-2-1의 Ⅱ절에서 기술되었다.
1 일반사항
1.1 적용범위
• 최소 정격 차단 용량
• 시간-전류 특성
• I 2t 특성
• 구조의 표준조건
• 전력 손실과 허용 전력 손실
2 용어와 정의
K 60269-1을 적용한다.
3 사용조건
K 60269-1을 적용한다.
4 분류
K 60269-1을 적용한다.
5 퓨즈의 특성
- 95 -
최대 권장 정격전류는 그림 501과 502에서 제공한다.
5.6.3 게이트
- 96 -
표 502 - “gG” 퓨즈-링크의 규정 용단시간에 대한 게이트
참 조: 이 표는 K 60269-1의 표 3과 관련 있으며, 이전에 K 60269-2-1의 Ⅱ절, 표 Ⅲ과 같다.
5.7.2 정격 차단 용량
6 표시사항
• 크기
• 크기 또는 기준
• 정격 차단 용량
7 구조의 표준조건
7.1 기계적 설계
- 97 -
7.1.2 단자를 포함한 접속부
고려중.
8 시험
8.3.1 퓨즈의 배치
8.4 동작의 검증
8.4.1 퓨즈의 배치
8.5 차단 용량의 검증
8.5.1 퓨즈의 배치
8.5.8 시험결과의 판정
- 98 -
8.9 열에 대한 내성의 검증
본체나 필터에 유기물을 포함한 퓨즈-링크는 위에서 기술한 것과 동일한 시험을 해야 한다.
이와 같은 퓨즈-링크는 I 1과 I 5의 시험전류를 차단해야 한다.
8.10.1 퓨즈의 배치
8.10.2 시험방법
시험전류: 협약 불용단 전류 I nf
부하 주기: 협약시간의 25 %
무부하 주기: 협약시간의 10 %
8.10.3 시험결과의 판정
- 99 -
를 초과하지 않아야 한다.
- 100 -
크기 A 퓨즈-링크 크기 C 퓨즈-링크
크기 B 퓨즈-링크 크기 D 퓨즈-링크
그림에서 나타낸 비고와 치수를 제외하고 그림에 의해서 퓨즈-링크의 설계가 제한되지는 않는다.
- 101 -
크기 최대 최대 a b d e f g h j k l m
정격 전력 (최대) (최대) (최대) (최대) (최대) (공칭) (공칭) (최소) (최대) (공칭) (최대)
전류 손실 1) 2) 3) 3) 2) 4)
A1 20 2.7 36.5 14.5 56 11.2 0.8 1.5 44.5 4.2 5.5 14.5 - 36.5
A2 32 4.4 57 24 86 9.2 0.8 1.5 73 5.5 7 25.5 - 60
A3 63 6.9 58 27 91 13 1.2 1.6 73 5.5 7 28 - 61
A4 100 9.1 70 37 111 20 2.4 3.2 94 8.7 9.5 38.5 - 74
B1 100 9.1 70 37 138 20 3.2 4 111 8.7 11 - - 82
B2 200 17 77 42 138 20 3.2 4 111 8.7 11 - - 82
B3 315 32 77 61 138 26 3.2 4.8 111 8.7 11 - - 82
B4 400 40 83 66 138 26 4.8 6.6 111 8.7 11 - - 89
C1 400 40 83 66 212 26 4.8 6.6 133 10.3 11 - 25.4 95
C2 630 55 85 77 212 26 6.3 7.8 133 10.3 11 - 25.4 95
C3 800 70 89 84 212 39 9.5 11.1 133 10.3 12.5 - 25.4 101
D1 1 250 100 89 102 200 64 9.5 12.7 149 14.3 16.5 - 31.8 95
1)
모든 크기에서, 치수 a와 m 사이의 태그(tag) 구조를 제외한 리벳 머리와 같은 모든 돌출부를 포함하는 치수
a는 접촉면에 대하여 45°의 직선내로 제한된다.
2)
j로 표시한 모든 고정 구멍은 치수 a에 대한 제조 허용 오차를 고려하기 위해 연장된다.
3)
치수 e 와 f는 재료의 공칭 크기이며 원재료에 대한 관련 기준으로 규정된 제조 허용 오차를 적용한다.
4)
크기 A1에서 A4 퓨즈-링크의 경우에 고정 슬롯(slot)은 축방향 또는 측면 방향으로 변경이 가능한 슬롯 형
태로 되어도 좋다.
그림 501 - (마지막)
표준 “gM” 퓨즈-링크
크기 표준 정격 전류 정격 특성 정격
A A
A1 20M25 20 25
A1 20M32 20 32
A2 32M40 32 40
A2 32M50 32 50
A2 32M63 32 63
A3 63M80 63 80
A3 63M100 63 100
A4 와 B1 100M125 100 125
A4
A4
} 와 B1
와 B1
100M160
100M200
100
100
160
200
B2 200M250 200 250
B2 200M315 200 315
- 102 -
단위 : ㎜
비 고 퓨즈-캐리어는 중심 태그형 또는 오프셋(offset) 태그형 퓨즈-링크의 삽입이 가능해도 좋다.
- 103 -
단위 : ㎜
비 고 접촉부 덮개의 틈은 IP2X의 보호 등급을 제공(IEC 60529)
이 그림은 설명을 위한 예이며, 위에 열거한 치수를 만족하는 다른 형태나 모양을 사용하지 못하는 것은 아니
다.
그림 503 - (마지막)
- 104 -
그림 504 - “gG” 퓨즈-링크의 시간 전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅱ절의 그림 3 (Ⅱ)와 같다.
- 105 -
그림 505 - “gG” 퓨즈-링크의 시간 전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅱ절의 그림 4 (Ⅱ)와 같다.
- 106 -
단위 : ㎜
치수의 근사값이 허용된다.
퓨즈-링크 치수 전류 정격
크기 a b c d m t A 이하
A1 10 12.5 16 50 38 0.5 20
A2 10 12.5 16 50 61 0.5 32
A3 16 12.5 16 50 62 1.0 63
A4 20 25 25 70 75 1.6 100
B1 20 25 25 70 83 1.6 100
B2 20 25 25 70 83 5 200
B3 25 38 25 80 83 8 315
B4 25 38 25 80 90 10 400
C1 25 38 25 80 96 10 400
C2 32 38 25 80 96 12 630
C3 40 45 32 100 101 12 800
D1 80 60 45 160 96 10 1 250
그림 506 - 전력 손실 시험 리그(rig)
참 조: 이 그림은 이전에 K 60269-2-1, Ⅱ절의 그림 5 (Ⅱ)와 같다.
- 107 -
단위 : ㎜
치수
퓨즈-링크 전류 정격
크기 A 이하 a b c d e f g h j
A1에서 A4
B1에서 B4 400 187 127 25 36.5 38 12 114 M12 111
C1에서 C3 800 248 140 38 51 50 20 114 M20 159
D1 1 250 305 152 63 83 57 20 114 M24 159
- 108 -
1)
적절한 강도가 보증되는 두께의 그물망, 연강판(mild steel sheet) 또는 타공(perforated) 연강판으로 제작된
분리 가능한 덮개. 그물망이나 타공 강판의 각 구멍의 면적은 8.5 ㎟를 초과하지 않아야 한다. 덮개와 통전
부 간의 공간거리가 19 ㎜를 초과하지 않는다면, 그림에서 나타낸 덮개의 단면과 달라도 좋다.
2)
고-도전성(high-conductivity) 동으로 된 연결 스터드(studs).
3)
고정 중심; A1에서 A3의 퓨즈-링크인 경우에 단면이 최소 25 ㎜ × 6.3 ㎜인 적절한 어댑터(adapter)를 사용
해야 한다.
4)
캡(cap)의 끝이 접촉 블록(block)에 접촉하지 않는 것을 보증하기 위해, 이 지점에서 눈으로 볼 수 있는 틈
이 있어야 한다.
5)
시험 리그 외부의 시험 결선에 대한 배치는 규정되지 않는다(K 60269-1의 8.5.1의 두 번째 문단을 적용하지
않는다).
6)
베이스는 페놀 수지 판을 겹쳐서 접착시킨 파괴강도(cross-breaking strength)가 85 Mpa 이상인 판으로 되
어야 한다.
7)
동 스트립(strip).
8)
가느다란 선으로 된 퓨즈를 위한 단자. 지름이 약 0.1 ㎜인 가느다란 선으로 된 동 퓨즈는 이 단자와 시험
전원의 한 극 간에 50 ㎜ 이상의 길이로 연결.
9)
모서리는 깎아냄.
10)
예상 전류 교정을 위해 필요한 회로 단락 장치. 제거하기 쉽게 슬롯으로 되어도 좋다.
그림 507 - (마지막)
- 109 -
퓨즈 시스템 F -
실린더 접촉 캡형 퓨즈-링크로 된 퓨즈
(NF 실린더 퓨즈 시스템)
참 조: 이전에 이 시스템은 K 60269-2-1의 Ⅲ절에서 기술되었다.
1 일반사항
1.1 적용범위
• 최소 정격 차단 용량
• 시간-전류 특성
• I 2t 특성
• 구조의 표준조건
• 전력 손실과 허용 전력 손실
2 용어와 정의
K 60269-1을 적용한다.
3 사용조건
K 60269-1을 적용한다.
4 분류
K 60269-1을 적용한다.
5 퓨즈의 특성
5.2 정격전압
- 110 -
교류인 경우에 정격전압의 표준값은 400 V, 500 V와 690 V이다. 직류인 경우에 정격전압은
250 V와 440 V이다. 직류 정격전압의 표준값은 교류 정격전압의 표준값과는 관계가 없다.
예를 들면, 다음 표준값의 조합이 가능하다: 교류 500 V - 직류 250 V, 교류 500 V - 직류
440 V, 교류 500 V, 기타.
교류 500 V 교류 690 V
gG aM gG aM
크기
In In In In
A A A A
10 × 38 25 16 10 -
14 × 51 50 40 25 25
22 × 58 100 100 50 50
교류 400 V
gG aM
크기
In In
A A
8 × 32 16 10
- 111 -
표 602 - 퓨즈-홀더의 최대 정격전류
참 조: 이 표는 이전에 K 60269-2-1, Ⅲ절의 표 L과 같다.
In
크기
A
8 × 32 16
10 × 38 25
14 × 51 50
22 × 58 100
크기 8 × 32 10 × 38 14 × 51 22 × 58
gG 2.5 W 3 W 5 W 9.5 W
aM 0.9 W 1.2 W 3 W 7 W
표 604 - 퓨즈-홀더의 정격 허용 전력 손실
참 조: 이 표는 이전에 K 60269-2-1, Ⅲ절의 표 N과 같다.
크기 8 × 32 10 × 38 14 × 51 22 × 58
정격 허용 전력 손실 2.5 W 3 W 5 W 9.5 W
- 112 -
표 605 - 정격전류가 16 A 미만인 “gG” 퓨즈-링크에 대한 협약시간과 협약전류
참 조: 이 표는 K 60269-1의 표 2와 관련 있으며, 이전에 K 60269-2-1의 Ⅲ절, 표 Ⅱ와 같다.
5.6.3 게이트
5.7.2 정격 차단 용량
표 607 - 최소 정격 차단 용량
참 조: 이 표는 이전에 K 60269-2, 2판의 표 B와 같다.
정격전압 최소 정격 차단 용량
≤ 교류 690 V 50 kA
≤ 직류 750 V 25 kA
6 표시사항
- 113 -
6.1 퓨즈-홀더의 표시사항
• 크기
• 크기 또는 기준
• 정격 차단 용량
표 608 - 표시사항의 색
참 조: 이 표는 K 60269-1의 표 4와 관련 있으며, 이전에 K 60269-2-1의 Ⅲ절, 표 CC와 같다.
특성 gG aM
표시사항의 색상 흑색 녹색
음각 인쇄된 음각 인쇄된
인쇄 종류 일반 인쇄 일반 인쇄
스트립 스트립
전압
V
400 V × ×
500 V × ×
690 V × ×
7 구조의 표준조건
7.1 기계적 설계
- 114 -
표 609 - 단단한 동 도체에 대한 단면적의 최소 범위
참 조: 이 표는 이전에 K 60269-2-1, Ⅲ절의 표 P 와 같다.
크기 8 × 32 10 × 38 14 × 51 22 × 58
단면적
1.5에서 4 1.5에서 6 2.5에서 16 4에서 50
㎟
7.7 I 2 t 특성
In 용단 I 2 t min 동작 I 2t max
A A2s A2s
2 1 23
4 6 90
6 24 225
8 49 420
10 100 576
12 160 750
정격전압 U n I 2 t max
V A2s
Un ≤ 400 18 I n2
400 < Un ≤ 500 24 I n2
500 < Un ≤ 690 35 I n2
- 115 -
정격전류의 비가 1 : 1.6이며 정격전류가 16 A 이상인 퓨즈-링크는 8.7.4에서 규정한 값까지
판별해야 한다.
8 시험
8.1.6 퓨즈-홀더의 시험
8.3.1 퓨즈의 배치
토크 (Nm)
Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ
나사산의 공칭 지름
㎜
- 116 -
Ⅰ열은 나사를 조일 때, 구멍으로부터 나사가 튀어나오는 머리가 없는 나사와 나사의 지름
보다 큰 드라이버로 조일 수 없는 나사에 적용한다.
8.3.4.2 퓨즈-링크의 전력 손실
- 117 -
8.5.5.1.1 퓨즈의 배치
8.5.5.1.2 시험방법
표 613 - 시험 전류
참 조: 이 표는 이전에 K 60269-2-1, Ⅲ절의 표 G와 같다.
크기 컷-오프 전류
kA
8 × 32 3... 4
10 × 38 5... 6
14 × 51 13...16
22 × 58 17...21
8.5.5.1.3 시험결과의 판정
- 118 -
n
690 V 퓨즈에 대하여 시험전압은 × 이다.
n
다른 모든 퓨즈에 대하여 시험전압은 × 이다.
최소 용단 I 2t 최대 동작 I 2 t
In 예상 I 예상 I
I 2t I 2t 판별비
A r.m.s r.m.s
A2s A2s
kA kA
2 0.013 0.67 0.064 16
4 0.035 4 0.130 67
6 0.064 16 0.220 193
계산할 수 없음
8 0.100 40 0.310 390
10 0.130 67 0.400 640
12 0.180 130 0.450 820
16 0.270 291 0.550 1 210
20 0.400 640 0.790 2 500
25 0.550 1 210 1.000 4 000
32 0.790 2 500 1.200 5 750
40 1.000 4 000 1.500 9 000
1 : 1.6
50 1.200 5 750 1.850 13 700
63 1.500 9 000 2.300 21 200
80 1.850 13 700 3.000 36 000
100 2.300 21 200 4.000 64 000
125 3.000 36 000 5.100 104 000
8.9 열에 대한 내성의 검증
본체나 필터에 유기물을 포함한 퓨즈-링크는 위에서 기술한 것과 동일한 시험을 해야 한다.
이와 같은 퓨즈-링크는 I 1과 I 5의 시험전류를 차단해야 한다.
- 119 -
8.10.1 퓨즈의 배치
8.10.2 시험방법
시험전류: 협약 불용단 전류 I nf
부하 주기: 협약시간의 25 %
무부하 주기: 협약시간의 10 %
8.10.3 시험결과의 판정
- 120 -
8.3.4.2에 따른 측정 지점 S
그림에서 나타낸 비고와 치수를 제외하고 그림에 의해서 퓨즈-링크의 설계가 제한되지는 않는다.
비 고
크기 정격 전력 손실의 a b c d r
최대값 최대 최소
W
8 × 32 2.5 31.5 ± 0.5 6.7 8.5 ± 0.1 4 1 ± 0.5
10 × 38 3 38 ± 0.6 10.5 10.3 ± 0.1 6 1.5 ± 0.5
+0.6
14 × 51 5 51 13.8 14.3 ± 0.1 7.5 2±1
-1
+0.1
22 × 58 9.5 58 16.2 22.2 ± 0.1 11 2±1
-2
단위 : ㎜
- 121 -
단위 : ㎜
그림에서 나타낸 비고와 치수를 제외하고 그림에 의해서 퓨즈-링크의 설계가 제한되지는 않는다.
- 122 -
베이스 A 두 개의 실린더 캡으로 접촉
단위 : ㎜
크기 In G1 H1 L +0.8
A 최대 최소 0
8 × 32 16 11.5 14 16
10 × 38 25 13 15.5 19.3
14 × 51 50 18 20.5 25.8
22 × 58 100 18 25 29
- 123 -
베이스 C 한 쪽은 실린더 면으로 접촉, 다른 쪽은 끝면으로 접촉
단위 : ㎜
크기 In G2 H2
A 최대 최소
8 × 32 16 26.5 29.5
10 × 38 25 31.5 34.5
14 × 51 50 43 47
22 × 58 100 46 52
그림에서 나타낸 비고와 치수를 제외하고 그림에 의해서 퓨즈-링크의 설계가 제한되지는 않는다.
그림에 대한 비고
2) 축방향 멈춤장치, 고정용 부품과 접촉 부품은 지시 장치나 스트라이커의 동작을 방해하지 않는 구조이어야 한
다. 이와 같은 구조라면 퓨즈-링크와 결합되어도 좋다.
3) 최소한 접촉 부품의 하나(크기 14 × 51와 22 × 58의 경우, 외부 스프링으로), 또는 베이스 C의 경우에 고정용
부품은 그림에서 화살표 방향으로 퓨즈-링크의 축방향 치수 허용 오차를 고려하여 충분한 탄성을 가져야 한
다.
표 603 -(마지막)
- 124 -
퓨즈 시스템 G -
오프셋 블레이드 접촉형 퓨즈-링크로 된 퓨즈
(BS 클립 퓨즈 시스템)
참 조: 이전에 이 시스템은 K 60269-2-1의 Ⅳ절에서 기술되었다.
1 일반사항
1.1 적용범위
• 최소 정격 차단 용량
• 시간-전류 특성
• I 2t 특성
• 구조의 표준조건
• 전력 손실과 허용 전력 손실
2 용어와 정의
K 60269-1을 적용한다.
3 사용조건
K 60269-1을 적용한다.
4 분류
K 60269-1을 적용한다.
5 퓨즈의 특성
- 125 -
K 60269-1과 다음의 추가 요구 사항을 적용한다.
5.2 정격전압
E1 크기 퓨즈-링크 교류 230 V
F1, F2, F3 크기 퓨즈-링크 교류 400 V
(1.1의 비고 적용)
- 126 -
표 701 - “gG” 퓨즈-링크에 대한 협약시간과 협약전류
참 조: 이 표는 K 60269-1의 표 2와 관련 있으며, 이전에 K 60269-2-1의 Ⅳ절, 표 Ⅱ와 같다.
In ≤ 4 1 1.25 I n 2.1 I n
5.6.3 게이트
5.7.2 정격 차단 용량
a) E1 크기의 퓨즈-링크는 50 ㎄
b) F1, F2, F3 크기의 퓨즈-링크는 80 ㎄
6 표시사항
• 크기
- 127 -
• 크기 또는 기준
• 정격 차단 용량
7 구조의 표준조건
7.1 기계적 설계
표 703 - 동도체의 크기
참 조: 이 표는 이전에 K 60269-2-1, Ⅳ절의 표 U와 같다.
20 4 E1
32 10 F1
63 25 F2
125 70 F3
7.7 I 2 t 특성
In I 2t min I 2t max
2
A As A2s
2 0.30 2.5
4 2.0 15
6 5 45
10 25 200
- 128 -
7.9 전기적 충격에 대한 보호
8 시험
8.4.1 퓨즈의 배치
8.5.1 퓨즈의 배치
- 129 -
8.9 열에 대한 내성의 검증
본체나 필터에 유기물을 포함한 퓨즈-링크는 위에서 기술한 것과 동일한 시험을 해야 한다.
이와 같은 퓨즈-링크는 I 1과 I 5의 시험전류를 차단해야 한다.
8.10.1 퓨즈의 배치
8.10.2 시험방법
시험전류: 협약 불용단 전류 I nf
부하 주기: 협약시간의 25 %
무부하 주기: 협약시간의 10 %
8.10.3 시험결과의 판정
- 130 -
필요한 경우, 750 주기 후에 측정한 온도상승값이 이 시험을 시작하기 전에 측정한 온도상
승값보다 20 K를 초과하지 않아야 한다.
- 131 -
단위 : ㎜
최대 최대 a 1) b
정격 전력 d e f n
크기
전류 손실
A W 최대 최대 최대 최소 최대 최소 최대 최소 최대 최소
- 132 -
단위 : ㎜
퓨즈-링크의 최대 정격 허용 A B C
크기 정격전류 전력 손실
A W 최대 최대 최대
E1 20 2 26 71 59
F1 32 3.5 26 81 59
F2 63 5 32 96 68
F3 125 7.5 40.5 110 81
비 고 위에서 열거한 치수를 만족하는 위의 그림과 다른 형태나 모양을 사용하지 못하는 것은 아니다.
- 133 -
그림 703 - “gG” 퓨즈-링크의 시간-전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅳ절의 그림 3 (Ⅳ)와 같다.
- 134 -
그림 704 - “gG” 퓨즈-링크의 시간-전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅳ절의 그림 4 (Ⅳ)와 같다.
- 135 -
X-X는 전력 손실 측정을 위한 전압 측정 지점을 나타낸다.
크기 a b c d e f g h j m t 정격전류
A 이하
E1 10 12.5 16 50 12.5 40 28 1.6 M4 30 0.5 20
F1 10 12.5 16 50 12.5 40 28 1.6 M4 30 0.5 32
F2 16 12.5 16 50 15 45 28 1.6 M5 45 1.0 63
F3 20 25 25 50 15 50 35 2 M5 45 1.6 125
단위 : ㎜
그림 705 - 전력 손실 시험 리그
참 조: 이 그림은 이전에 K 60269-2-1, Ⅳ절의 그림 5 (Ⅳ)와 같다.
- 136 -
퓨즈 시스템 H -
“gD”와 “gN” 특성의 퓨즈-링크로 된 퓨즈
( J 등급과 L 등급 시간 지연형 퓨즈와 비시간 지연형 퓨즈)
참 조: 이전에 이 시스템은 K 60269-2-1의 Ⅴ절에서 기술되었다.
1 일반사항
1.1 적용범위
다음의 추가 요구 사항을 그림 801, 802, 803과 804에서 규정한 치수를 따르는 “gD”와 “gN”
퓨즈에 적용한다. 이와 같은 퓨즈의 정격전류는 실린더 접촉식인의 경우에는 60 A, 블레이
드/볼트 접속식인 경우에는 600 A, 그리고 볼드 접속식인 경우에는 6 000 A 이하이다. 정격
전압은 600 V이고 차단 정격은 200 ㎄이다.
• 최소 정격 차단 용량
• 시간-전류 특성
• I 2t 특성
• 구조의 표준조건
• 전력 손실과 허용 전력 손실
2 용어와 정의
K 60269-1을 적용한다.
3 사용조건
K 60269-1을 적용한다.
4 분류
K 60269-1을 적용한다.
- 137 -
5 퓨즈의 특성
5.2 정격전압
K 60269-1에서 규정한 정격 외에, R40 시리즈에서 적절한 정격을 선택해도 좋다. 또한, 다
음 정격도 허용된다: 5 - 17, 5 - 35 - 70 - 175 - 350 - 700 - 1 200 - 3 500.
- 138 -
표 801 - “gD”와 “gN” 퓨즈-링크에 대한 협약시간과 협약전류
참 조: 이 표는 K 60269-1의 표 2와 관련 있으며, 이전에 K 60269-2-1의 Ⅴ절, 표 II와 같다.
5.6.3 게이트
5.7.2 정격 차단 용량
6 표시사항
• 크기
- 139 -
• 크기 또는 기준
• 정격 차단 용량
7 구조의 표준조건
7.1 기계적 설계
7.6 컷-오프 전류 특성
7.7 I 2 t 특성
최대 동작 I 2t 값은 표 806에서 제공한다.
- 140 -
표 803 - “gD”와 “gN” 퓨즈-링크에 대한 0.01 s에서 용단 I 2t 값
참 조: 이 표는 K 60269-1의 표 7과 관련 있으며,
이전에 K 60269-2-1의 Ⅴ절, 표 Ⅵ와 같다.
In I 2t min I 2t max
3 2
A 10 × A s 103 × A2s
10 0.08 0.23
15 0.17 0.49
17.5 0.24 0.70
20 0.31 0.93
25 0.50 1.4
30 0.70 2.1
35 1.2 3.5
40 1.6 4.7
50 2.4 7.1
60 3.5 10
70 5.5 17
80 7.5 23
100 11 33
125 17 49
150 24 70
175 33 98
200 49 130
250 70 200
300 98 290
350 130 390
400 200 580
500 300 890
600 410 1 200
700 730 2 000
800 900 2 700
1 000 1 300 3 800
1 200 2 100 6 000
1 400 2 800 8 400
1 600 3 800 11 000
2 000 6 000 17 000
2 500 9 000 26 000
3 000 13 000 38 000
3 500 17 000 50 000
4 000 26 000 74 000
5 000 38 000 110 000
6 000 50 000 150 000
8 시험
- 141 -
8.3 온도상승과 전력 손실의 검증
8.3.1 퓨즈의 배치
퓨즈를 수평으로 고정해야 한다. 정격전류가 600 A 이상인 퓨즈-링크의 경우에 각 단자는
퓨즈-링크와의 접촉부가 은도금된 동대로 접속해야 한다.
8.3.4.2 퓨즈-링크의 전력 손실
8.4 동작의 검증
8.4.1 퓨즈의 배치
- 142 -
8.4.3.3.2 게이트의 검증
In Ic In Ic
A ㎄ A ㎄
10 4.1 300 33
15 5.0 350 36
17.5 5.7 400 38
20 6.2 500 52
25 7.5 600 55
30 9.5 700 73
35 9.5 800 80
40 10 1 000 89
50 11.3 1 200 100
60 12.5 1 400 115
70 14.4 1 600 125
80 15.7 2 000 150
100 17.5 2 500 180
125 19.6 3 000 200
150 21.2 3 500 229
175 23 4 000 250
200 25 5 000 300
250 30 6 000 350
- 143 -
최대 동작 I 2t 값은 표 806에서 제시한 제한값을 초과하지 않아야 한다. 시료는 8.5와 K
60269-1의 표 20에 따른 차단 용량 시험과 동일하게 배치한다.
In I 2 t min In I 2 t min
A 103 × A2s A 103 × A2s
8.9 열에 대한 내성의 검증
본체나 필터에 유기물을 포함한 퓨즈-링크는 위에서 기술한 것과 동일한 시험을 해야 한다.
이와 같은 퓨즈-링크는 I 1과 I 5의 시험전류를 차단해야 한다.
8.10.1 퓨즈의 배치
- 144 -
한 치수와 최대 전력 손실 P n(W)을 가져야 한다.
8.10.2 시험방법
시험전류: 협약 불용단 전류 I nf
부하 주기: 협약시간의 25 %
무부하 주기: 협약시간의 10 %
8.10.3 시험결과의 판정
8.11.2 기타 시험
- 145 -
8.11.2.2 비정상적인 열과 화재에 대한 내성의 검증
고려중이다.
- 146 -
그림 교류 600 V 치수
㎜
1) 2)
a b c d e f g h
I n (A) P n (W)
±0.08 ±0.9 min. ±1.6 ±1.5 ±0.13
1 - 30 8 57.1 20.6 - - 12.7 - - -
A
35 - 60 12 60.3 27.0 - - 15.9 - - -
70 - 100 18 118 28.6 3.18 19.1 24.6 92.1 9.52 7.14
125 - 200 34 146 41.3 4.78 28.6 34.1 111 9.52 7.14
B
250 - 400 64 181 54.0 6.35 41.3 46.8 133 13.5 10.3
500 - 600 92 203 66.7 9.52 50.8 53.2 152 17.5 13.5
1)
1 - 60 A: ±0.8
70 - 600 A: ±2.4
2)
1 - 60 A: ±0.20
70 - 600 A: 최대
- 147 -
그림 교류 600 V 치수
㎜
a b c d
I n (A) P n (W)
±2.4 최대 ±0.8 ±1.6
700 63 219 64.3 9.5 50.8
C
800 72 219 64.3 9.5 50.8
1 000 90 273 70.6 9.5 50.8
1 200 108 273 70.6 9.5 50.8
D 1 400 126 273 77.0 11.1 60.3
1 600 144 273 77.0 11.1 60.3
2 000 180 273 89.7 12.7 69.8
2 500 213 273 128 19.0 88.9
E
3 000 255 273 130 19.0 102
3 500 300 273 147 19.0 121
F
4 000 340 273 147 19.0 121
5 000 425 273 182 25.4 133
G
6 000 510 273 182 25.4 146
- 148 -
A - 실린더형 접촉부용 베이스 B - 블레이드형 접촉부용 베이스
치수
㎜
In a b c d e f g h i -
그림 최대 접촉 접촉 양쪽 끝 퓨즈-링크 퓨즈-링크 최소 최대 구멍 구멍의 스터드의
A 클립의 클립 간 간의 접촉부의 블레이드의 공간 간의 지름 지름
최소폭 거리 최소 공칭 지름 최소 두께 거리 공간
거리 거리
30 12.7 31.8 57.9 20.6 - - - - - -
A
60 15.9 28.6 61.1 27.0 - - - - - -
100 22.2 69.9 120 - 3.18 120 9.53 92.1 7.14 6.35
B
200 31.8 79.4 148 - 4.76 148 14.3 111 7.14 6.35
와
400 44.5 88.9 183 - 6.35 183 20.2 133 10.3 9.53
C
600 50.8 98.4 206 - 9.53 206 25.0 152 13.5 12.7
- 149 -
치수 ㎜
퓨즈-링크의 정격전류
그림 a b c
A
접촉부의 폭 최소
D 700 - 800 51 220 -
1 000 - 1 200 51 280 -
E 1 400 - 1 600 60 280 -
2 000 70 280 -
2 500 89 280 41
F 3 000 100 280 41
3 500 - 4 000 120 280 83
5 000 130 280 41
G
6 000 150 280 41
- 150 -
기호
A - 저항 측정 지점
그림 805 - 더미 퓨즈-링크
참 조: 이 그림은 이전에 K 60269-2-1, Ⅴ절의 그림 3 (Ⅴ)와 같다.
- 151 -
기호
A - 온도상승 측정 지점
B - 전력 손실 측정 지점
그림 806 - 시험 배치
참 조: 이 그림은 이전에 K 60269-2-1, Ⅴ절의 그림 4 (Ⅴ)와 같다.
- 152 -
그림 807 - “gN” 퓨즈-링크의 시간-전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅴ절의 그림 5a (Ⅴ)와 같다.
- 153 -
그림 808 - “gN” 퓨즈-링크의 시간-전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅴ절의 그림 5b (Ⅴ)와 같다.
- 154 -
그림 809 - “gN” 퓨즈-링크의 시간-전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅴ절의 그림 5c (Ⅴ)와 같다.
- 155 -
그림 810 - “gD” 퓨즈-링크의 시간-전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅴ절의 그림 6a (Ⅴ)와 같다.
- 156 -
그림 811 - “gD” 퓨즈-링크의 시간-전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅴ절의 그림 6b (Ⅴ)와 같다.
- 157 -
그림 812 - “gD” 퓨즈-링크의 시간-전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅴ절의 그림 6c (Ⅴ)와 같다.
- 158 -
퓨즈 시스템 I -
웨지(wedge) 접촉형 gU 퓨즈-링크
1 일반사항
1.1 적용범위
비 고 3 통전부와의 우연한 접촉에 대한 비호환성과 보호를 구조적인 방법으로 보증할 필요는 없다.
• 최소 정격 차단 용량
• 시간-전류 특성
• I 2t 특성
• 구조의 표준조건
• 전력 손실과 허용 전력 손실
- 159 -
2 용어와 정의
K 60269-1을 적용한다.
3 사용조건
3.9 퓨즈-링크의 판별
4 분류
K 60269-1을 적용한다.
5 퓨즈의 특성
5.2 정격전압
5.5 퓨즈-링크의 정격 전력 손실
- 160 -
그림 906에서 규정된 표준 전력 손실 시험 리그로 8.3.1에 따라 시험하였을 때, 퓨즈-링크에
허용되는 전력 손실의 최대값은 표 901에서 규정된다.
표 901 - 최대 전력 손실값
참 조: 이 표는 이전에 K 60269-2-1, Ⅵ절의 표 LL과 같다.
정격전류 (A) 100 160 200 250 315 355 400 500 630
전력 손실 (W) 10 14 18 22 29 29 33 38 46
5.6.3 게이트
5.7.2 정격 차단 용량
표 902 - 최소 정격 차단 용량
참 조: 이 표는 이전에 K 60269-2, 2판의 표 B와 같다.
정격전압 최소 정격 차단 용량
≤ 교류 690 V 50 kA
≤ 직류 750 V 25 kA
- 161 -
K 60269-1의 5.8을 적용한다; I 2t 특성은 정격전류에 대한 용단값과 전체 동작값을 함수의
형태로 나타낸 그래프이어도 좋다.
6 표시사항
• 크기
• 크기 또는 기준
• 정격 차단 용량
7 구조의 표준조건
7.1 기계적 설계
7.5 차단 용량
7.7 I 2 t 특성
- 162 -
표 903 - gU 퓨즈-링크에 대한 0.01 s에서 용단 I 2 t 값
참 조: 이 표는 이전에 K 60269-2-1의 Ⅵ절, 표 MM과 같다.
In I 2t min I 2t max
A 103 × A2s 103 × A2s
8 시험
8.1.1 시험의 종류
8.3.1 퓨즈의 배치
- 163 -
표 904 - 전력 손실 시험과 온도상승 시험을 위한 도체의 단면적
참 조: 이 표는 이전에 K 60269-2-1의 Ⅵ절, 표 NN과 같다.
퓨즈-링크의 정격 도체의 단면적 1)
A ㎜
100 20 × 1.6
160 20 × 2.5
200 20 × 3.15
250 20 × 5
315 25 × 5
355 25 × 6
400 25 × 8
500 40 × 6
630 40 × 10
1)
이와 같은 도체와 크기가 비슷한 도체도 허용된다.
8.4.1 퓨즈의 배치
8.4.3.3.2 게이트의 검증
8.5.1 퓨즈의 배치
8.5.2 시험 회로의 특성
8.5.5 시험방법
- 164 -
직류에 대한 시험을 생략하는 것을 제외하고 K 60269-1의 8.5.2를 적용한다.
8.5.8 시험결과의 판정
8.9 열에 대한 내성의 검증
본체나 필터에 유기물을 포함한 퓨즈-링크는 위에서 기술한 것과 동일한 시험을 해야 한다.
이와 같은 퓨즈-링크는 I 1과 I 5의 시험전류를 차단해야 한다.
- 165 -
그림 901 - 100 A, 200 A, 355 A와 630 A 전류 정격에 대한
시간-전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅵ절의 그림 1a (Ⅵ)과 같다.
- 166 -
그림 902 - 160 A와 315 A 전류 정격에 대한 시간-전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅵ절의 그림 1b (Ⅵ)과 같다.
- 167 -
그림 903 - 250 A와 500 A 전류 정격에 대한 시간-전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅵ절의 그림 1c (Ⅵ)과 같다.
- 168 -
그림 904 - 200 A와 400 A 전류 정격에 대한 시간-전류 영역
참 조: 이 그림은 이전에 K 60269-2-1, Ⅵ절의 그림 1d (Ⅵ)과 같다.
- 169 -
L형 태그를 가진 퓨즈-링크 태그 구조의 대표적인 형태
비 고 1 M 은 캡의 끝 면으로부터 7 ㎜
단위 : ㎜
최대 고정 중심 간의 간격 82 ㎜
전류
A B C D E F 1) G H J K L M 2) N P O
정격
최대 공칭 최대 최대 최대 최대 공칭 공칭 공칭 최대 공칭 공칭 공칭 공칭
A
400 112 82 61 25 36 48 19 17 14 35 2.4 6.53 13 10 3
6.45
1)
F 는 리벳 머리를 포함하는 본체 유효 길이의 최대 치수를 나타낸다.
2)
M 은 최대 치수와 최소 치수를 나타낸다.
단위 : ㎜
최대 고정 중심 간의 간격 92 ㎜
전류
A B C D E F 1) G H J K L M 2) N P O
정격
최대 공칭 최대 최대 최대 최대 공칭 공칭 공칭 최대 공칭 공칭 공칭 공칭
A
630 132 92 75 25 50 48 24 20 17 42 3.2 8.13 16 11 3
8.05
1)
F 는 리벳 머리를 포함하는 본체 유효 길이의 최대 치수를 나타낸다.
2)
M 은 최대 치수와 최소 치수를 나타낸다.
- 170 -
기호
1 A (고정 중심 간의 간격)
2 전압 강하 측정 지점
3 주석도금한 동
4 절연판
비 고 1 외부 도체를 위한 고정 나사.
비 고 2 퓨즈-캐리어는 생략.
단위 : ㎜
최대 전류 정격 A B C D E F G H
A
400 80.0 31.5 6.3 35.0 24.0 76.2 16.0 13.5
630 92.0 40.0 8.0 41.3 28.6 76.2 22.3 17.5
그림 906 - 전력 손실 시험 리그
참 조: 이 그림은 이전에 K 60269-2-1, Ⅵ절의 그림 3 (Ⅵ)과 같다.
- 171 -
1)
적절한 강도가 보증되는 두께의 그물망, 연강판(mild steel sheet) 또는 타공(perforated) 연강판으로 제작된
분리 가능한 덮개. 그물망이나 타공 강판의 각 구멍의 면적은 8.5 ㎟를 초과하지 않아야 한다. 덮개와 통전
부 간의 공간거리가 19 ㎜를 초과하지 않는다면, 그림에서 나타낸 덮개의 단면과 달라도 좋다.
2)
캡(cap)의 끝이 시험 리그의 접촉부와 접촉하지 않는 것을 보증하기 위해, 이 지점에서 눈으로 볼 수 있는
틈이 있어야 한다.
3)
동 도체의 크기는 차단 용량에 따라 시험소(testing laboratory)에 의해서 선택되어야 한다.
4)
베이스와 베이스에 연결되는 접촉부의 고정 장치는 퓨즈-링크에 외부 부하를 인가하지 않았을 때 발생하는
힘을 견디기에 충분한 강도를 가져야 한다. 페놀 수지 판을 겹쳐서 접착시킨 판이 베이스의 재료로 적절하
다.
5)
동 스트립(strip).
- 172 -
6)
가느다란 선으로 된 퓨즈를 위한 단자. 지름이 약 0.1 ㎜인 가느다란 선으로 된 동 퓨즈는 이 단자와 시험
전원의 한 극 간에 75 ㎜ 이상의 길이로 연결.
7)
예상 전류 교정을 위해 필요한 회로 단락 장치. 제거하기 쉽게 슬롯으로 되어도 좋다.
8)
절연된 바닥판.
9)
연강(mild steel) 모서리 브래킷(bracket) 32 × 32 × 5.
단위 : ㎜
최대 전류 정격 A B C D E F G H X Y 퓨즈-링크
A 고정 나사
400 82.0 31.5 6.3 35.0 24.0 76.2 16.0 13.5 152 124 M12
630 92.0 40.0 8.0 41.3 28.6 76.2 22.3 17.5 170 138 M16
그림 907 - (마지막)
- 173 -
인용문헌
- 174 -