HVAC default
for typical BMS applications
SCR | Signal cable shield (screen)
Al1_| External reference 4: 0(2)...10 Vor 0(4)...20 mA
4.10 ohm fy]
eT}
AGND| Analogue input circuit common
10V | Reference voltage +10 V DC
AGND| Anaiogue input circuit common
401 | Output frequency: 0(4)...20 ma
402 | Output current: 0(4)...20 ma
1
2
3
a
I | | aiz_| actual signat 4: 0(2)...10 Vor 0(4)...20 ma?
6
7
8
Q
AGND| Analogue output cireuit common
. 10|24v | auxiliary vohage output +24 v BC
77[ GND | Commen for DI return signals
12[DCOM| Digital input common for all
[13] It _| start/stop: Activation starts the drive
74[ Diz _| Not used
si 15|_D13_| Constant speed 4 (par. 1202) '
16| Di4_| Start enable 1: Deactivation stops the drive?
a7 Dis_| Notusea
16[ DI6 | Notused
19| ROIC Relay output 4 (par. 1401)
20[ ROTA Default operation
w pe
21[RO1B} Ready => 19 connected to21
22] RO2C Relay ouput 2 (par. 1402)
23[ RO2A |_| Default operation
24[ RO2B|+ Running => 22 connected to 24
25| RO3C Relay output 3 (par. 1403)
26[ RO3A Ly | Default operation
27[ RO38 + Fault (-1) => 25 connected to 27
| Not available if PID is activated
2 Disable/enable with parameter 1608
The sensor for Al2is powered externally (not shown in the figure). See the manufacturer's.
instructions. To use sensors supplied by the drive auxiliary voltage output, see page 124.
Note: The drive starts only if possible protectin functions (Run enable or Start enable 1 and
2) are activated from If or disabled with parameters.