SCHEDULE OF LOADS

CIRCUIT LIGHTING CONV.


PB PB VOLTS WATTS TOTAL AMPERE AT SIZE OF HOMERUN
1 NO. OUTLETS OUTLETS WATTS
3
1 10 230 100 1000 4.34 20 A 2-3.5mm THHN - 1/2" DIA. PVC

2 2 5 230 150 750 3.26 30 A 2-2.0mm THHN - 1/2" DIA. PVC

3 REF 230 1500 1500 6.52 30 A 2-2.0mm THHN - 1/2" DIA. PVC

4 SPARE 30 A 2-2.0mm THHN - 1/2" DIA. PVC

TOTAL 3,250 14.12

COMPUTATION OF LOAD FOR SUBFEEDER


I = 4,125 VA
LP-1

230
LIGHTING LAYOUT POWER LAYOUT APPLYING DEMAND FACTOR:
10 L.O. @ 100WATTS @ 60% D.F. = 600 VA
WIRE SIZE:
I = 17.93 AMP
LP-1

5 C.O. @ 150WATTS @ 70% D.F. = 525 VA 2-14mm THHN IN 1" DIA. PVC /
SCALE 1:100 M. SCALE 1:100 M.
1-5.5mm TW (ground wire) IN 32mm DIA. RSC
OTHER LOAD(S)
1 REF. @ 100% D.F. = 1500 VA
1500 VA PROTECTION:
1 SPARE @ 100% D.F. =
60AT,100AF,2P,ACB
NET COMPUTED LOAD = 4,I25 VA

SINGLE LINE
LEGEND
RISER DIAGRAM GENERAL NOTE & SPECIFICATION
2-14mm THHN IN 1" DIA. PVC / 1. ALL ELECTRICAL MATERIALS, EQUIPMENT AND METHODS OF WIRING SHALL BE DONE IN ACCORDANCE WITH THE
LIGHTING OUTLET 1-5.5mm TW (ground wire) IN 25mm
PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE REQUIREMENTS OF THE LOCAL
DIA. RSC
FLOURESCENT LIGHT
GOVERNMENT UNIT CONCERNED AND THE ELECTRIC UTILITY COMPANY.

CO DUPLEX CONVENIENCE OUTLET


2. ELECTRICAL MATERIALS SHALL BE NEW AND OF THE MAKE, TYPE AND DESCRIPTION SPECIFIED IN THE PLAN OR
WATER PROOF CONVENIENCE OUTLET GIVEN BY THE SUPERVISING ELECTRICAL ENGINEER. ALL ELECTRICAL INSTALLATIONS SHALL BE IN PROPER
W 60AMP
20 AT 30 AT OPERATING CONDITION BEFORE THE WORK IS DEEMED COMPLETED.
PB PANEL BOARD

CIRCUIT HOMERUN 1 30 AT 30 AT
2 3. CHARACTER OF SERVICE SHALL BE 230 VOLTS, 60 HZ, SINGLE PHASE, LINE TO GROUND.
1
S1 SINGLE POLE SWITCH
3 4 SPARE 4. BRANCH CIRCUITS SHALL BE 20 AMPERES FOR THE GENERAL PURPOSE RECEPTACLE OUTLETS AND 15 AMPERES
S2 TWO GANG SWICTH FOR LIGHTING OUTLETS. OTHER BRANCH CIRCUITS SUPPLYING SPECIFIC EQUIPMENTS SHALL BE PROTECTED AS
THREE GANG SWICTH SPECIFIED IN THE LOAD SCHEDULE.
S3
ELECTRICAL SERVICE ENTRANCE
5. THE MINIMUM SIZE OF WIRE TO BE USED SHALL BE 2.00 MM SQ THW WITH APPROPRIATE ISO CERTIFICATION.
15AT CIRCUIT BREAKER
6. CONDUITS SMALLER THAN 20 MM DIAMETER TRADE SIZE ARE NOT TO BE INSTALLED IN THE BUILDING
M ELECTRICAL METER PURPOSELY FOR ELECTRICAL USED. NON-METAL CONDUITS SHALL BE USED TO ENCASED WIRES FOR BRANCH
GROUND BUS CIRCUITS INCLUDING SWITCH LINE ENCASEMENT. SERVICE ENTRANCE CONDUCTOR SHALL BE PROTECTED AND
LIGHTING LINE, CONCEALED ON CEILING
ENCASED IN APPROPRIATE SIZE CONDUIT FROM SERVICE TAKE-OFF TO BREAKER PANEL.
GROUND
CONDUCTORS USED FOR SERVICE ENTRANCE SHALL BE THW OR THWN ENCASED IN CONDUIT.
POWER LINE, CONCEALED ON FLOOR
7. ALL CONDUCTORS USED WITHIN THE BUILDING THAT ARE LARGER THAN 3.50 MM SQ SHALL BE STRANDED.
MOUNTING HEIGHT OF CONVENIENCE OUTLETS SHALL BE 300 MM, SWITCHES AT 1300 MM AND CENTER OF PANEL
BOARD AT 1300 MM ALL REFERRED TO THE FINISHED FLOOR LEVEL UNLESS OTHERWISE SPECIFIED IN THE
DRAWINGS. COUNTER TOP RECEPTACLES SHALL BE MOUNTED AT 300 MM ABOVE FINISHED COUNTER TOP.

DESIGNED: PROJECT: OWNER: SHEET CONTENTS: REVISIONS: SHEET NO.

AS BUILT PLAN OF GROCERY STORE WITH GARAGE


EVANGELINE D. DANNUG AS SHOWN E-1
ADDRESS
BARANGAY LINGLINGAY ,GAMU, ISABELA