INSTALLATION INSTRUCTIONS
WARNING
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly could result in serious injury or property damage.
• Installation and service must be performed by a qualified installer, service agency or the gas
supplier.
• Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or
any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbors phone. Follow the gas suppliers instructions.
• If you cannot reach your gas supplier, call the fire department.
DO NOT DESTROY. PLEASE READ CAREFULLY & KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION..........................3 ELECTRICAL WIRING...................................................17
Line Voltage Wiring....................................................17
REQUIREMENTS & CODES..........................................3
Grounding...................................................................17
Combustion Air Quality...............................................4
Thermostat / Low Voltage Connections......................17
Clearances to Combustible Materials.........................4
Heat Anticipator..........................................................17
Heating Load..............................................................4
Twinning.....................................................................17
Installation in a Garage...............................................5
One stage heating......................................................18
Operation of Furnace During Construction.................5
Two stage heating......................................................19
COMBUSTION AIR & VENTING REQUIREMENTS......5
START-UP & ADJUSTMENTS.......................................19
Installation In A Confined Space................................6
Pre-Start Check List...................................................19
Air From Inside.........................................................6
Start-up Procedures...................................................19
Outdoor Air from a Crawl Space or Vented Attic......6
Verifying & Adjusting Input Rate.................................19
Outdoor Air Using Vertical Ducts..............................6
Verifying & Adjusting Temperature Rise.....................20
Outdoor Air Using Horizontal Ducts..........................6 Verifying Burner Operation.........................................20
Air Directly Through An Exterior Wall.......................7 Verify Operation of the Supply Air Limit Switch..........20
Alternate Method of Providing Air from Outside:......8
OPERATING SEQUENCE..............................................21
Installation In An Unconfined Space...........................8
Heating Cycle.............................................................21
Category I Venting......................................................8
Cooling Cycle.............................................................21
Horizontal Venting......................................................9
Fan Mode...................................................................21
Flexible Vent Systems................................................9
MAINTENANCE..............................................................21
CIRCULATING AIR REQUIREMENTS...........................9
Plenums & Air Ducts...................................................9 FIGURES & TABLES......................................................23
Return Air Connections..............................................10 Figure 18. Furnace Dimensions................................23
Upflow & Horizontal Furnaces..................................10 Airflow Data................................................................24
Downflow Furnaces..................................................10 Table 3. *SA Upflow / Horizontal Blower Data..........24
Supply Air Connections..............................................10 Table 4. *SK Downflow Blower Data........................26
Acoustical Treatments................................................10 Electrical Information..................................................27
FURNACE INSTALLATION............................................11 Figure 19. Wiring Diagram........................................27
About The Furnace.....................................................11 Gas Information..........................................................28
Before You Install the Furnace...................................11 Table 5. Gas Flow Rates..........................................28
Locating the Furnace..................................................11 Table 6. Gas Pipe Capacities...................................28
Upflow Furnaces.........................................................11 Table 7. High Altitude Deration Chart for Propane
Horizontal Furnaces...................................................11 Gas.............................................................29
Downflow Installation..................................................12 Table 8. Natural Gas Heating Values.......................29
Installation on a Concrete Slab.................................12 Table 9. High Altitude Deration Chart for Natural
Pressure Switch Tubing..............................................13 Gas - High Heating Value...........................30
Bottom Panel Removal...............................................13 Table 10. High Altitude Deration Chart for Natural
Alternate Bottom Panel Removal..............................13 Gas - Low Heating Value..........................30
GAS SUPPLY & PIPING.................................................14 TROUBLESHOOTING....................................................31
Leak Check.................................................................14 Table 11. Control Board Fault Conditions.................31
High Altitude Application.............................................14
Conversion to LP / Propane.......................................16 FURNACE COMPONENTS............................................31
Figure 20. Component Locations..............................32
INSTALLATION CHECKLIST.........................................36
2
IMPORTANT SAFETY INFORMATION understand the instructions provided with the equipment
prior to performing the installation and operational checkout
INSTALLER: Please read all instructions before servicing
of the equipment.
this equipment. Pay attention to all safety warnings and any
• Use caution when handling this appliance or removing
other special notes highlighted in the manual. Safety markings
components. Personal injury can occur from sharp metal
are used frequently throughout this manual to designate a
edges present in all sheet metal constructed equipment.
degree or level of seriousness and should not be ignored.
• Do not store any of the following on, or in contact with, the
WARNING - indicates a potentially hazardous situation that unit: Rags, brooms, vacuum cleaners, or other cleaning
if not avoided, could result in personal injury or death. tools, spray or aerosol cans, soap powders, bleaches,
CAUTION - indicates a potentially hazardous situation that waxes, cleaning compounds, plastics or plastic containers,
if not avoided, may result in minor or moderate injury or paper bags or other paper products, gasoline, kerosene,
property damage. cigarette lighter fluid, dry cleaning fluids, paint thinners,
or other volatile fluids.
• The installer should become familiar with the units wiring
WARNING: diagram before making any electrical connections to the
unit. See Figure 19, (page 27) or the unit wiring label.
The safety information listed in this manual must • Always reinstall the doors on the furnace after servicing.
be followed during the installation, service, and Do not operate the furnace without all doors and covers
in place.
operation of this unit. Unqualified individuals
should not attempt to interpret these instructions REQUIREMENTS & CODES
or install this equipment. Failure to follow safety • This furnace must be installed in accordance with these
recommendations could result in possible instructions, all applicable local building codes and the
damage to the equipment, serious personal current revision of the National Fuel Gas Code (NFPA54/
injury or death. ANSI Z223.1) or the Natural Gas and Propane Installation
Code, CAN/CSA B149.1.
• Use only with type of gas approved for this furnace. Refer
to the furnace rating plate.
WARNING: • Install this furnace only in a location and position as
specified on page 5.
Improper installation, service, adjustment, or • Provide adequate combustion and ventilation air to the
maintenance may cause explosion, fire, electrical furnace space as specified on page 5, page 6,
shock or other hazardous conditions which may page 7, & page 8.
result in personal injury or property damage. • Combustion products must be discharged outdoors.
Unless otherwise noted in these instructions, Connect this furnace to an approved vent system only,
only factory authorized kits or accessories may as specified on page 8 & page 9.
be used with this product. • Never test for gas leaks with an open flame. Use
a commercially available soap solution to check all
connections. See page 14.
• This furnace is designed to operate with a maximum external
WARNING: pressure rise of 0.5 inches of water column. Consult Table
3, (page 24) & Table 4, (page 26), and the rating plate
Unless otherwise noted in these instructions, for the proper circulating air flow and temperature rise. It
only factory authorized kits or accessories may is important that the duct system be designed to handle
be used with or when modifying this product. the desired flow rate and temperature rise. An improperly
designed duct system can result in nuisance shutdowns,
and comfort or noise issues.
WARNING: • When supply ducts carry air circulated by the furnace to
areas outside the space containing the furnace, the return
Do not install this furnace if any part has been air shall also be handled by duct(s) sealed to the furnace
submerged under water. A flood damaged furnace casing and terminating outside the space containing the
furnace. See page 9 & page 10.
is extremely dangerous. Attempts to use the • A gas-fired furnace for installation in a residential garage
furnace may result in fire or explosion. A qualified must be installed as specified on page 5.
service agency should be contacted to inspect the • This furnace is not approved for installation in mobile homes.
furnace and to replace any electrical or control Installing this furnace in a mobile home could cause fire,
system parts that have been wet or under water. property damage, and/or personal injury.
3
The information listed below is for reference purposes only • Installations in these locations may require outdoor air for
and does not necessarily have jurisdiction over local or state combustion, due to chemical exposures:
codes. Always consult with local authorities before installing Commercial buildings
any gas appliance. Buildings with indoor pools
Combustion & Ventilation Air Furnaces installed in laundry rooms
• US: National Fuel Gas Code (NFGC), Air for Combustion and Furnaces installed in hobby or craft rooms
Ventilation Furnaces installed near chemical storage areas
• CANADA: Natural Gas and Propane Installation Codes • Exposure to the following substances in the combustion
(NSCNGPIC), Venting Systems and Air Supply for Appliances air supply may require outdoor air for combustion:
Duct Systems Permanent wave solutions
• US and CANADA: Air Conditioning Contractors Association Chlorinated waxes and cleaners
(ACCA) Manual D, Sheet Metal and Air Conditioning Chlorine based swimming pool chemicals
Contractors National Association (SMACNA), or American Water softening chemicals
Society of Heating, Refrigeration, and Air Conditioning De-icing salts or chemicals
Engineers (ASHRAE) Fundamentals Handbook
Carbon Tetrachloride
Electrical Connections Halogen type refrigerants
• US: National Electrical Code (NEC) ANSI/NFPA 70 Cleaning solvents (perchloroethylene)
• CANADA: Canadian Electrical Code CSA C22.1 Printing inks, paint removers, varnishes, etc.
Gas Piping & Gas Pipe Pressure Testing Hydrochloric Acid
• US: NFGC and National Plumbing Codes Cements and glues
• CANADA: NSCNGPIC Antistatic fabric softeners
General Installation Masonry acid washing materials
• US: Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association Inc., Clearances to Combustible Materials
Batterymarch Park, Quincy, MA 02269; or American Gas This furnace is Design Certified in the U.S. and Canada by
Association, 400 N. Capitol, N.W., Washington DC 20001 or CSA International for the minimum clearances to combustible
www.NFPA.org materials. NOTE: The furnace is listed for installation on
• CANADA: NSCNGPIC. For a copy, contact Standard Sales, combustible or non-combustible flooring. However, wood
CSA International, 178 Rexdale Boulevard, Etobicoke is the only combustible flooring allowed for installation.
(Toronto), Ontario, M9W 1R3 Canada Downflow models must use the appropriate subase kit when
installing over a wood floor. To obtain model number and
Safety
specific clearance information, refer to the furnace rating
• US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the Installation
plate, located inside of the furnace cabinet.
Standards, Warm Air Heating and Air Conditioning Systems
ANSI/NFPA 90B. Access for positioning and servicing the unit must be
• CANADA: CAN/CSA-B149.1 and .2–M00 National Standard considered when locating unit. The need to provide clearance
of Canada. (NSCNGPIC) for access to panels or doors may require clearance distances
over and above the requirements. Allow 24 inches minimum
Combustion Air Quality clearance from the front of the unit. However 36 inches
is strongly recommended. See Figure 1, (page 5) for
CAUTION: minimum clearance requirements.
4
CLEARANCES TO COMBUSTIBLE MATERIALS* COMBUSTION AIR & VENTING
REQUIREMENTS
UPFLOW & DOWNFLOW
APPLICATIONS
BACK WARNING:
HORIZONTAL
APPLICATIONS CARBON MONOXIDE POISONING HAZARD
RIGHT SIDE Failure to follow the steps outlined below
LEFT SIDE
BOTTOM
FRONT result in carbon monoxide poisoning or death.
The following steps shall be followed with
VENT
VENT
5
IMPORTANT INFORMATION: Air From Inside
• Provisions must be made during the installation of If combustion air is taken from the heated space, the two
this furnace that provide an adequate supply of air openings must each have a free area of at least 1 in2 per
for combustion. Furnace installation using methods 1,000 Btuh of total input of all appliances in the confined
other than those described in the following sections space, but not less than 100 in2 of free area. See Figure
must comply with the National Fuel Gas Code (NFGC) 2 and the Example below.
and all applicable local codes.
• Instructions for determining the adequacy of EXAMPLE
combustion air for an installation can be found in the If the combined input rate of all appliances is less than or
current revision of the NFGC (ANSI Z223.1 / NFPA54). equal to 100,000 Btuh, each opening must have a free
Consult local codes for special requirements. These area of at least 100 in2. If the combined input rate of all
requirements are for US installations as found in the appliances is 120,000 Btuh, each opening must have a
NFGC. free area of at least 120 in2.
• The requirements in Canada (B149.1) are structured
differently. Consult with B149.1 and local code officials
for Canadian installations.
Vent or
CAUTION: Chimney
Air openings on top of the furnace and openings in closet 40,000 100 in2 12 inches
doors or walls must never be restricted. If the furnace is 60,000 100 in2 12 inches
operated without adequate air for combustion, the flame roll- 80,000 100 in2 12 inches
out switch will open, turning off the gas supply to the burners. 100,000 100 in2 12 inches
IMPORTANT NOTE 120,000 120 in2 13 inches
This safety device is a manually reset switch. DO NOT 140,000 140 in2 14 inches
install jumper wires across these switches to defeat 160,000 160 in2 15 inches
their function or reset a switch without identifying
and correcting the fault condition. If a switch must be Figure 2. Combustion Air Drawn from Inside
replaced, use only the correct sized part specified in the
Replacement Parts List provided online.
Outdoor Air from a Crawl Space or Vented Attic
Installation In A Confined Space When the openings can freely exchange air with the outdoors,
A confined space is an area with volume less than 50 each opening shall have a minimum free area of 1 in2 per
cubic feet per 1,000 Btuh of the combined input rates of all 4,000 Btuh of total appliance input. The openings shall
appliances drawing combustion air from that space. Furnace exchange directly, or by ducts, with the outdoor spaces
closets, small equipment rooms and garages are confined (crawl or attic) that freely exchange with the outdoors. See
spaces. Furnaces installed in a confined space which supply Figure 3, (page 7).
heated air to areas outside the space must draw return air
from outside the space and must have the return air ducts Outdoor Air Using Vertical Ducts
tightly sealed to the furnace. If combustion air is taken from outdoors through vertical
ducts, the openings and ducts must have a minimum free
The required sizing of these openings is determined by
area of 1in2 per 4,000 Btuh of total appliance input. In
whether inside or outside air is used to support combustion,
installations drawing combustion air from a ventilated attic,
the method by which the air is brought to the space, and by
both air ducts must extend above the attic insulation. See
the total input rate of all appliances in the space. In all cases,
Figure 4, (page 7).
the minimum dimension of any combustion air opening is
3 inches. Outdoor Air Using Horizontal Ducts
If combustion air is taken from outdoors through horizontal
ducts, the openings and ducts must have a minimum free
area of 1in2 per 2,000 Btuh of total appliance input. See
Figure 5, (page 7).
6
Ventilation louvers
Vent or at each end of attic
Chimney Vent or
Chimney
Attic Outlet air duct must be
Insulation at least 1 sq. in. per 12" Max
4,000 Btuh of total
input rating. Must -- --
NOTE: Each
--
-- --
Air Duct --
- - -
extend above attic opening to
Water insulation Furnace
Heater Furnace outside must
See
be at least 1
Inlet air duct must be at Note
sq. in. per 2,000
least 1 sq. in. per 4,000
Btuh of total input rating. Btuh of total
-- --- --
--
-
-- Air Duct --
- input rating.
7
Alternate Method of Providing Air from Outside:
If acceptable under local Codes, it is permitted to provide
outside air using one opening (See NFGC). Generally,
WARNING:
confined spaces must have 2 openings in the space for Venting into an unlined masonry chimney or
combustion air. One opening must be within 12 inches of concrete chimney is prohibited. This may result in
the ceiling, and the other must be within 12 inches of the improper draft and excess condensation forming
floor. However, an alternative method recently adopted by in the chimney.
the NFGC uses one opening within 12 inches of the top of
the space. This method may be used if it is acceptable to • This furnace must be vented in compliance with
the local codes. the current revision of the National Fuel Gas Code
THE FOLLOWING CONDITIONS MUST BE MET: (ANSI-Z223.1/NFPA54) and the instructions provided
1. The opening must start within 12” of the top of the structure below. Refer to the NFGC for approved vent tables.
and connect with the out of doors through vertical or Consult local codes for special requirements.
horizontal ducts or be ducted to a crawl or attic space that • In Canada, venting shall conform to the requirements
connects with the out of doors. of the current (CAN/CSA B149.1) installation codes.
2. The opening must have a minimum free area of 1 in2. per Consult local codes for special requirements.
3,000 Btu per hour of the total input rating of all equipment • Category I furnace installations must be connected
located in the enclosure. to a factory built chimney or vent complying with a
3. The free area must not be less than the sum of all the recognized standard, or a masonry or concrete chimney
areas of the vent connectors in the enclosure. lined with a lining material acceptable to the authority
having jurisdiction.
Installation In An Unconfined Space • In the U.S., this furnace must never be vented to a
An unconfined space is an area including all rooms not chimney or flue that services a fireplace or other
separated by doors with a volume greater than 50 cubic feet appliance designed to burn solid fuel. If the furnace
per 1,000 Btuh of the combined input rates of all appliances vent is to be connected to a chimney serving a fireplace,
which draw combustion air from that space. the fireplace must be sealed off from the chimney. In
Canada, common venting with a fireplace is permitted.
In general, a furnace installed in an unconfined space will not
Consult B149.1 and your local code authority.
require outside air for combustion. However, in homes built for
• This furnace may be vented with a dedicated venting system
energy efficiency (low air change rates), it may be necessary
or common vented with other Category I appliances. The
to provide outside air to ensure adequate combustion and
vent system dimensions and material must conform to the
venting, even though the furnace is located in an unconfined
NFGC or local Codes. Generally, this means using Type
space. See Example
B vent pipe or a lined masonry chimney. When consulting
the vent sizing tables in the NFGC, the MAX capacity of
EXAMPLE the vent must be greater than the furnaces high fire rate.
A space with a water heater rated at 45,000 Btuh input The MIN capacity must be lower than the low fire rate. If
and a furnace rated at 75,000 Btuh requires a volume of the venting system is inappropriate for the furnace, the
6,000 cubic feet [50 x (45 + 75) = 6,000] to be considered venting system will need to be modified to comply with
unconfined. If the space has an 8 foot ceiling, the floor NFGC or local codes.The minimum diameter of any
area of the space must be 750 sq. ft. (6,000 / 8 = 750). vent pipe is 4 inches.
• The venting system should be designed to have the
Category I Venting minimum number of elbows or turns. All horizontal runs
This furnace is listed as a Category I vented appliance. shall slope upwards from the furnace at ¼ inch per running
Category I furnaces generally operate with a slight negative foot of vent. Supports for the vent pipe must be installed
pressure (draft) and must be vented vertically or near vertical. a minimum of every five feet along the vent run to ensure
Additionally it is important to guard against excessive no displacement after installation. Under no circumstances
condensation. shall any portion of the vent system extend into or pass
through any return air duct, supply air duct, or plenum.
• Single wall vent connectors may be used under the
WARNING: limited capacity ranges found in the vent sizing tables. It
is recommended that Type B double wall vent be used for
Upon completion of the furnace installation, the connector whenever possible. An existing masonry
carefully inspect the entire flue system both chimney should be inspected and relined if necessary.
inside and outside the furnace to assure it is • Single wall metal vertical vents shall not be used for
properly sealed. Leaks in the flue system can Category I venting. The furnace vent, if metal, may
be insulated if local codes allow. Any part of the vent
result in serious personal injury or death due system, metal vent only, not exposed to weather,
to exposure of flue products, including carbon but which are exposed to temperatures below 35° F
monoxide. (1° C) must be insulated to prevent condensation. All
vent insulation shall be foil backed fiberglass of one inch
minimum thickness.
• Sheet metal fasteners should be used to secure the vent
pipe to the furnace flue. However, the NFGC states that
alternative vent products may be attached according to
the vent manufacturers instructions.
8
• When an existing furnace is removed from a vent system CIRCULATING AIR REQUIREMENTS
serving other appliances, the existing vent system may no
longer be sized to properly vent the remaining appliances.
An improperly sized venting system can result in the WARNING:
formation of condensate, leakage, or spillage. The existing
vent system should also be checked to make sure it remains Do not allow combustion products to enter the
in compliance with NFGC. If it isn’t, the vent system must circulating air supply. Failure to prevent the
be brought into compliance before installing the furnace. circulation of combustion products into the
living space can create potentially hazardous
Horizontal Venting conditions including carbon monoxide poisoning
• Horizontal vent systems must be sealed with a high
temperature sealant that can withstand temperatures of
that could result in personal injury or death.
450° F. Recommended sealants: Dow Corning Sealant All return ductwork must be secured to the
736 RTV; GE 106 RTV; High Tech Ind., High TEMP RED. furnace with sheet metal screws. For installations
• This furnace is not approved for horizontal venting without in confined spaces, all return ductwork must be
the use of an add-on power venter. Power venters establish adequately sealed. When return air is provided
negative pressure in the vent piping and the furnace through the bottom of the furnace, the joint
operates as if connected to a Category I vertical vent. The between the furnace and the return air plenum
power venter is only for use when exhausting through an must be air tight.
exterior wall. The surface that the furnace is mounted on must
• The power venter must be installed according to the
provide sound physical support of the furnace
instructions provided by the power venter manufacturer
with no gaps, cracks or sagging between the
and applicable requirements of local codes. For Canadian
installations please refer to the Canadian Installation Code
furnace and the floor or platform.
(CAN/CSA-B149.1 or 2) and/or local codes. Return air and circulating air ductwork must
• The outlet of the vent must be at least 12 inches above not be connected to any other heat producing
the highest expected snow accumulation. device such as a fireplace insert, stove, etc. This
may result in fire, explosion, carbon monoxide
Flexible Vent Systems
Flexible venting systems are approved for use providing poisoning, personal injury, or property damage.
they are listed for the application and meet all local Code
requirements. These systems are primarily used to line Plenums & Air Ducts
existing masonry chimneys. They must be sized to the • Plenums and air ducts must be installed in accordance with
application according to the sizing tables in the National the Standard for the Installation of Air Conditioning and
Fuel Gas Code, including the required 20% reduction in Ventilating Systems (NFPA No. 90A) or the Standard for
maximum capacity. the Installation of Warm Air Heating and Air Conditioning
Systems (NFPA No. 90B).
Flexible venting systems are permitted to be used as the • Table 3, (page 24) & Table 4, (page 26) contain
vent connector. However, great care must be taken to ensure the maximum airflow and temperature rise data for each
that there are no sags in the venting system which could furnace input rate. If the maximum airflow is 1,600 CFM
accumulate condensate. The flexible vent system must be or more, it is recommended that two openings be used
supported at no more than 5 foot intervals and maintain a for return air on upflow furnaces. Downflow furnaces can
minimum slope of ¼ inch per foot of horizontal run. only use one return opening.
• It is recommended that the outlet duct contain a removable
access panel. The opening should be accessible when the
furnace is installed in service and shall be of a size that
smoke or reflected light may be observed inside the casing
to indicate the presence of leaks in the heat exchanger.
The cover for the opening shall be attached in such a
manner as to prevent leaks.
• If outside air is used as return air to the furnace for
ventilation or to improve indoor air quality, the system must
be designed so that the return air is not less than 60° F
(15° C) during operation. If a combination of indoor and
outdoor air is used, the ducts and damper system must
be designed so that the return air supply to the furnace is
equal to the return air supply under normal, indoor return
air applications.
• When a cooling system is installed which uses the furnace
blower to provide airflow over the indoor coil, the coil must
be installed downstream (on the outlet side) of the furnace
or in parallel with the furnace.
9
• If a cooling system is installed in parallel with the furnace, a Downflow Furnaces
damper must be installed to prevent chilled air from entering • To attach the return air duct to the downflow furnace, bend
the furnace and condensing on the heat exchanger. If a the flanges on the furnace upward 90° with wide duct pliers.
manually operated damper is installed, it must be designed See Figure 18, (page 23) for furnace flange locations.
so that operation of the furnace is prevented when the NOTE: If system installation includes AC coil casing, bend
damper is in the cooling position and operation of the the flanges on the coil casing upward 90° before attaching
cooling system is prevented when the damper is in the the return air duct.
heating position. • Secure the return air ductwork to the furnace or coil casing
• Seal all connections and joints with industrial grade sealing (if installed) with sheet metal screws. Make sure the screws
tape or liquid sealant. Requirements for sealing ductwork penetrate the sheet metal casing and flanges.
vary from region to region. Consult with local codes for
requirements specific to your area. Supply Air Connections
• The supply air must be delivered to the heated space by
Return Air Connections duct(s) secured to the furnace or coil box casing, running
• In applications where the supply ducts carry heated air to full size and without interruption.
areas outside the space where the furnace is installed, • To attach the supply air duct to upflow & horizontal furnaces,
the return air must be delivered to the furnace by duct(s) bend the flanges on the furnace upward 90° with wide
secured to the furnace casing, running full size and without duct pliers. See Figure 18, (page 23) for furnace flange
interruption. Do not use the back of the furnace for locations. NOTE: If system installation includes AC coil
return air. casing, bend the flanges on the coil casing upward 90°
• Position the furnace with the return air ductwork ensuring before attaching the supply air duct.
even alignment of furnace (or coil casing) air opening and • Position the supply air ductwork onto the furnace ensuring
return air duct. NOTE: The ductwork must have an opening even alignment of furnace air opening and supply air duct.
equal to that of the return air opening of the furnace (or coil NOTE: The ductwork must have an opening equal to that
casing). See Figure 18, (page 23) for return air opening of the supply air opening of the furnace. See Figure 18 for
size. supply air opening size.
10
FURNACE INSTALLATION surface that the furnace is mounted on must provide sound
These Installation procedures are suggested for typical physical support of the unit. Secure the furnace to the floor.
furnace installations. Since each installation is different, • The furnace should be installed as close to the center of
the sequence of instructions may differ from the actual the air distribution system as possible and attached to a
installation. Only qualified HVAC technicians should properly installed duct system. Do not use the back of
install this furnace. the furnace for return air. See page 9 & page 10
for circulating requirements.
The installer must be familiar with and comply with all codes • The furnace must be installed so that all electrical
and regulations applicable to the installation of these heating components are protected from water.
appliances and related equipment. In the absence of local • The plenum attached to the A/C coil box and ductwork
codes, the installation must be in accordance with the current within 3 ft. of the furnace must be installed so that surfaces
provisions of one or more of the following standards. are at least 1” from combustible construction.
• American National Standard (ANSI-Z223.1/NFPA-54) and/ • When installed in a residential garage, the furnace must
or CAN/CSA B149 for all gas-fired furnace models. be positioned so the burners and the source of the ignition
• American National Standard (ANSI-C1/NFPA-70) and/or are located no less than 18 inches above the floor and
CSA 22.1 Canadian Electric Code Part 1 for all electrical protected from physical damage by vehicles.
field wiring. • The furnace must be installed upstream from a refrigeration
system.
About The Furnace • The furnace requires special venting materials and
The *SA / *SK series furnace is designed only for indoor installation procedures. See page 8 & page 9 for
installations and can be readily connected to the high venting guidelines and specifications.
static duct system of a home. *SA series gas furnaces are
shipped ready for installation in the upflow or horizontal Upflow Furnaces
right or left positions. *SK series gas furnace may only be
used for downflow operation. Units are approved for single
/ multistory residential structures in freestanding /closet / WARNING:
alcove configurations. The furnace must not be installed directly on
This appliance will provide many years of safe and dependable carpeting, tile, or any combustible material other
comfort, providing it is properly installed and maintained. than wood flooring. Failure to comply may result
Abuse, improper use, and/or improper maintenance can in fire, property damage or personal injury.
shorten the life of the appliance and create unsafe hazards.
Please read all instructions before installing the unit. *SA series gas furnaces are shipped with the bottom panel
Approved installation, operation, and maintenance of this installed as shown in Figure 18, (page 23). If the furnace
appliance must be in accordance with the listed specifications is installed with only side return air, the bottom panel must
contained in these instructions and other documents supplied not be removed. If the furnace is installed with bottom return
with the furnace and/or optional air conditioning equipment. air, the bottom panel must be removed. See Bottom Panel
Unless it is noted differently in this manual, only use factory Removal on page 13.
authorized kits and accessories on this appliance. Refer to
local authorities having jurisdiction for further information.
Horizontal Furnaces
11
threaded rod. Fasten the frame together with nuts, washers, Downflow Installation
and lockwashers. Secure the support frame to the rafters
with lag bolts. The furnace can also be suspended using The furnace must not be installed directly on carpeting,
steel straps around each end of the furnace. The straps tile, or any combustible material other than wood flooring.
should be attached to the furnace with sheet metal screws To install the furnace on combustible flooring, a special
and to the rafters with bolts. sub-base is required.
• It is recommended for further reduction of fire hazard
that cement board or sheet metal be placed between the
furnace and the combustible floor and extend 12 inches WARNING:
beyond the front of the door and top of the furnace.
Failure to install the downflow sub-base kit may
result in fire, property damage or personal injury.
Electrical Supply
Connection
WARNING:
Gas Inlet The downflow sub-base kit must not be installed
Type “B” Vent directly on carpeting, tile, or any combustible
material other than wood flooring. Failure to
Wood or
non-combustible comply may result in fire, property damage or
Platform personal injury.
Downflow sub-base kits are factory supplied accessories
Coil Plenum and are listed according to the cabinet letter of the furnace.
For ‘A’ size cabinets use Sub-Base kit #902974 only. For ‘B’,
‘C’, and ‘D’ size cabinets use Kit #904911. Please follow
Figure 7. *SA Horizontal Installed on a Platform the instructions provided with the kit.
A downflow sub-base kit is not necessary if the furnace is
installed on a factory or site-built cased air conditioning coil.
However, the plenum attached to the coil casing must be
installed so that its surfaces are at least 1” from combustible
construction.
12
Pressure Switch Tubing Alternate Bottom Panel Removal
If the bottom panel cannot be removed using the previous
Figure 10 displays the proper routing of pressure switch instructions, the steps below are an alternate method for
tubing for *SA & *SK furnaces. On both furnaces, the removing the bottom panel. See Figure 12.
tubing connects at one end of the pressure switch and is 1. Remove the door (1) from the blower compartment .
routed directly onto the static tap of the inducer assembly. 2. Remove all screws securing the bottom panel (2) to the
front brace (3).
3. Remove two screws (4) securing the furnace cabinet to
the blower deck (5).
4. Remove all screws (6) securing the furnace cabinet to the
bottom panel (2).
5. Remove the screw (7) securing the bottom corner of the
furnace cabinet to the front brace (3).
6. Carefully spread the bottom corner of the furnace cabinet
outwards while sliding the bottom panel (2) out through
the front of the furnace.
7. Reassemble the furnace in reverse order.
1 5
1 3
2
5
4
6
7
13
GAS SUPPLY & PIPING The furnace may be installed for either left or right side gas
entry. When connecting the gas supply, provide clearance
between the gas supply line and the entry hole in the furnace
WARNING: casing to avoid unwanted noise and/or damage to the furnace.
Typical gas hookups are shown in Figure 13.
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly could Leak Check
result in serious injury or property damage.
• Installation and service must be performed WARNING:
by a qualified installer, service agency or the
gas supplier. FIRE OR EXPLOSION HAZARD
• Do not store or use gasoline or other Failure to follow safety warnings exactly could
flammable vapors and liquids in the vicinity result in serious injury or property damage.
of this or any other appliance.
Never test for gas leaks with an open flame. Use
WHAT TO DO IF YOU SMELL GAS a commercially available soap solution made
• Do not try to light any appliance.
specifically for the detection of leaks to check
• Do not touch any electrical switch; do not
use any phone in your building. all connections. A fire or explosion may result
• Leave the building immediately. causing property damage, personal injury or
• Immediately call your gas supplier from a loss of life.
neighbor’s phone. Follow the gas supplier’s
instructions. After the gas piping to the furnace is complete, all connections
• If you cannot reach your gas supplier, call must be tested for gas leaks. This includes pipe connections
the fire department. at the main gas valve, emergency shutoff valve and flexible
gas connectors (if applicable). The soap and water solution
can be applied on each joint or union using a small paintbrush.
• All gas piping must be installed in compliance with If any bubbling is observed, the connection is not sealed
local codes and utility regulations. In the absence of adequately and must be retightened. Repeat the tightening
local codes the gas line installation must comply with and soap check process until bubbling ceases.
the latest edition of the National Fuel Gas Code (ANSI
Z223.1) or (CAN/CSA B149.1) Installation Codes. IMPORTANT NOTE:
• Some local regulations require the installation of a When pressure testing gas supply lines at pressures
manual main shut-off valve and ground joint union greater than 1/2 psig (14 inch W.C.), the gas supply
external to the furnace as shown in Figure 13, (page piping system must be disconnected from the furnace
15). The shut-off valve should be readily accessible to prevent damage to the gas control valve. If the test
for service and/or emergency use. Consult the local pressure is less than or equal to 1/2 psig (14 inch W.C.),
utility or gas supplier for additional requirements close the manual shut-off valve.
regarding placement of the manual main gas shut-off.
• Per ANSI 21.47, A 1/8-inch NPT plugged tapping, High Altitude Application
accessible for test gauge connection, must be installed High altitude conversion with this furnace depends on
immediately upstream of the gas supply connection to the installation altitude and the heating value of the gas.
the furnace external to the cabinet. If local codes allow Installation of this furnace at altitudes above 2,000 feet
the use of a flexible gas appliance connector, always shall be in accordance with local codes, or in the absence
use a new listed connector. Do not use a connector of local codes, the National Fuel Gas Code, ANSI Z223.1/
that has previously serviced another gas appliance. NFPA 54 or National Standard of Canada, Natural Gas &
• Gas piping must never run in or through air ducts, Propane Installation Code CSA B149.1. Please consult your
chimneys, gas vents, or elevator shafts. local code authority.
• Compounds used on threaded joints of gas piping
must be resistant to the actions of LP propane gas.
• The main gas valve and main power disconnect to WARNING:
the furnace must be properly labeled by the installer The reduction of input rating necessary for high
in case emergency shutdown is required.
• Flexible gas connectors are not recommended for this altitude installation may only be accomplished
type of furnace but may be used if allowed by local with factory supplied orifices. Do not attempt to
jurisdiction. Only new flexible connectors may be drill out orifices in the field. Improperly drilled
used. Do not use a connector which has previously orifices may cause fire, explosion, carbon
serviced another gas appliance. monoxide poisoning, personal injury or death.
• A drip leg should be installed in the vertical pipe run
to the unit (Figure 13). The furnaces are shipped from the factory with orifices and
Table 6, (page 28) lists gas pipe capacities for standard gas regulator settings for natural gas operation at sea level
pipe sizes as a function of length in typical applications based altitudes. At 2,000 feet, the NFGC requires that this appliance
on nominal pressure drop in the line. be derated 4% for each 1,000 feet of altitude. For example,
at 2,000 feet the input needs to be reduced 8%, at 3,000
14
UPFLOW MODELS
1 1
See See
R C Y G W
R C Y G W
STATUS STATUS
Note
24V
24V
FAN
FAN
COOL
COOL
HEAT
HEAT
Note
FLAME FLAME
8
6 3 6 3
L1A
L1A
8
5 2 5 2
4 1 4 1
NEUTRALS
NEUTRALS
XFMR
XFMR
HIGH
HIGH
HUM
LOW
HUM
LOW
EAC
EAC
MH
MH
ML
ML
L1
L1
3 3
7
5
5
2 6 2 6
DOWNFLOW MODELS
R C Y G W
R C Y G W
STATUS STATUS
24V
24V
FAN
FAN
COOL
HEAT
COOL
HEAT
FLAME FLAME
6 3 6 3
L1A
L1A
5 2 5 2
4 1 4 1
NEUTRALS
NEUTRALS
XFMR
XFMR
HIGH
HIGH
HUM
LOW
HUM
LOW
EAC
EAC
MH
ML
MH
ML
L1
L1
See 7 See
Note 1 1 Note
8 8
4
3 3
5
5
2 6 2 6
COMPONENTS:
(1) Automatic Gas Valve
(2) Burner Assembly (3) Dripleg (4) Elbow
(w/ manual shut-off)
(5) Ground Joint Union (6) Manifold (7) Plug (8) Shut - Off Valve
NOTE: Some utilities require Shut- Off Valve to be 4 - 5 feet above floor.
15
feet (12%), etc. This deration is in reference to the input rate IMPORTANT NOTE:
and gas heating value at sea level. Observe the action of the burners to make sure there is
To derate the furnace requires knowing the heating value of no yellowing, lifting or flashback of the flame.
the gas at the installation site. Heating values at particular For US installations only: To avoid nuisance tripping
job sites vary for two reasons: at altitudes from 7500 to 10,000 feet, a pressure switch
1. The chemical mixture of the gas varies across regions conversion may be required. Consult the tables in the LP
and is expressed as the “sea level heating value”. and High altitude and LP gas conversion kit for installations
2. The heating value varies by altitude. For this reason, in the US.
especially in high altitude areas, the local gas utility
specifies the heating value at the residence’s gas meter Conversion to LP / Propane
as the “local value”.
For added flexibility, two tables have been provided for
natural gas installations with HIGH or LOW heating values
WARNING:
at sea level. Table 9 & Table 10, (page 30) contain the The furnace was shipped from the factory
orifice sizes and manifold pressure to use at various altitudes. equipped to operate on natural gas. Conversion
Table 9 (High) is for natural gas installations with a heating to LP / Propane gas must be performed by
value of more than 1,000 Btu per cubic foot and Table 10 qualified service personnel using a factory
(Low) is for less than 1,000 Btu per cubic foot. To determine
which table to use: supplied conversion kit. Failure to use the proper
conversion kit can cause fire, explosion, property
1. Consult the local utility for the local heating value at your damage, carbon monoxide poisoning, personal
installation site.
2. From Table 8, (page 29), find your local heating value as
injury, or death.
supplied by the utility company. Follow down the column
Conversion to LP / Propane is detailed in the installation
and stop at your altitude level.
instructions provided with the conversion kit. Generally, this
3. If your sea level heating value is HIGH, use Table 9 or if
will require the replacement of the burner orifices and the
it’s LOW, use Table 10.
spring found under the cap screw on the pressure regulator.
In the U.S. if installation is above 2,000 ft., refer to Table 7,
EXAMPLE (page 29) to determine the correct orifice size and manifold
Elevation:.......................................................5,000 feet pressure. See example below.
Type of Gas:............................................... Natural Gas
Local Heating Value of Gas:................................... 750 EXAMPLE
Elevation:.......................................................5,000 feet
From Table 8, find 750 and follow down the column, stop Type of Gas:............................................. Propane Gas
at the 5,000 feet row. The heating value listed is LOW. Input BTUH of Furnace:.....................................72,000
Table 10 will be used to determine orifice size and manifold
pressure
From Table 7, find 5,000 and follow across the row, stop
at the 72,000 BTU column. The manifold pressure listed
After changing the regulator pressure or the orifices, it is is 10.0 and the orifice size is 57.
required that you measure the gas input rate. This may be
accomplished in the usual way, by clocking the gas meter When conversion is complete, verify the manifold pressure
and using the local gas heating value. See Verifying and and input rate are correct as listed in the Tables. Approved
Adjusting the Input Rate section (page 19). conversion kits are listed below:
• The United States LP / Propane Gas Sea Level and High
Altitude Conversion Kit (P/N 905028) is for LP / Propane
conversion in the United States at altitudes between
zero and 10,000 ft. above sea level. Please follow the
instructions provided with the kit.
• The Canadian LP / Propane Gas Sea Level and High
Altitude Conversion Kit (P/N 905029) is for LP / Propane
conversions in Canada at altitudes between zero and
4,500 ft. above sea level. Please follow the instructions
provided with the kit.
16
ELECTRICAL WIRING Thermostat / Low Voltage Connections
• The furnace is designed to be controlled by a 24 VAC
WARNING: thermostat. The thermostat’s wiring must comply with the
current provisions of the NEC (ANSI/NFPA 70) and with
applicable local codes having jurisdiction.
ELECTRICAL SHOCK, FIRE OR • The thermostat must be installed according to the
EXPLOSION HAZARD instructions supplied by the thermostat manufacturer.
Failure to follow safety warnings exactly could Low voltage connections (24 VAC) from the thermostat
result in serious injury or property damage. are wired to the terminal strip on the integrated control in
the furnace. Figure 15 contains the proper connections
Improper servicing could result in dangerous for heating only (two-wire) and heating/cooling (four-wire)
operation, serious injury, death or property applications. Recommended minimum wire gauge for
damage. thermostat wiring is shown in Table 2, (page 18).
• The thermostat should be mounted about 5 feet above the
• Before servicing, disconnect all electrical floor on an inside wall. DO NOT install the thermostat on
power to furnace. an outside wall or any other location where its operation
• When servicing controls, label all wires prior may be adversely affected by radiant heat from fireplaces,
to disconnecting. Reconnect wires correctly. sunlight, or lighting fixtures, and convective heat from
• Verify proper operation after servicing.” warm air registers or electrical appliances. Refer to the
thermostat manufacturer’s instruction sheet for detailed
• Electrical connections must be in compliance with all mounting information.
applicable local codes and the current revision of the • The six pin terminal marked “Expansion Port” (Figure
National Electric Code (ANSI/NFPA 70). 15) is not used in the single stage furnace as shipped
• For Canadian installations the electrical connections and from the factory. It is used for the furnace control board
grounding shall comply with the current Canadian Electrical to communicate to a fixed speed or variable speed high
Code (CSA C22.1 and/or local codes). efficiency motor that may be optionally installed. Please
contact your distributor for the proper upgrade motor kit.
Line Voltage Wiring
It is recommended that the line voltage (115 VAC) to the Heat Anticipator
furnace be supplied from a dedicated branch circuit containing Set the heat anticipator according to the instructions supplied
the correct fuse or circuit breaker for the furnace. See Table 2. by the thermostat manufacturer. To determine the heat
anticipator setting:
IMPORTANT NOTES: 1. Add the current draw of the system components; or
• An electrical disconnect must be installed readily 2. Measure the current flow on the thermostat R-W circuit
accessible from and located within sight of the furnace. after the circulating blower motor has started.
See Figure 14 or the wiring diagram label inside of
the control door. Any other wiring methods must be Twinning
acceptable to authority having jurisdiction. Single stage furnaces are not supplied with a built-in twinning
• Proper line voltage polarity must be maintained in order capability. Other valuable features and enhancements were
for the control system to operate correctly. Verify the made to the new control that made it necessary to remove
incoming neutral line is connected to the white wire the twinning capability. For twinning of single stage furnaces
and the incoming “hot” line is connected to the black with PSC motors, a twinning kit (1010035) is available for
wire. The furnace will not operate unless the polarity purchase. Please follow the instructions provided with
and ground are properly connected as shown in Figure the kit.
14. If both single stage furnaces are upgraded to the fixed speed
• If replacing any of the original wires supplied with the iSEER™ blower, the twin terminal on both blower control
furnace, the replacement wire must be copper wiring boards (Figure 16, (page 19)) may be used to twin the
and have a temperature rating of at least 105° F (40° single stage furnaces. The twinning system requires a relay
C). For electrical specifications, refer to the furnace (P/N 624843) in the secondary furnace for proper twinning.
nameplate or Table 2.
For proper twinning of fixed speed furnaces the following
Grounding criteria must be met:
• Both furnaces and motors must be the same size.
WARNING: • Both motors must be on the same speed for cooling and
heating.
To minimize personal injury, the furnace cabinet • Both furnaces must have a common return duct and
common supply plenum.
must have an uninterrupted or unbroken electrical • Both furnaces must be the same phase and on the same
ground. The controls used in this furnace require leg of power.
an earth ground to operate properly. Acceptable
Furnaces equipped with variable speed iSEER™ motors
methods include electrical wire or conduit may not be twinned under any circumstances.
approved for ground service. Do not use gas
piping as an electrical ground!
17
FURNACE FURNACE CABINET NOMINAL MAXIMUM MINIMUM MAXIMUM MINIMUM MAXIMUM
MODEL INPUT WIDTH ELECTRICAL OPERATING OPERATING FURNACE WIRE FUSE OR CIRCUIT
*SA/*SK (BTUH) (IN.) SUPPLY VOLTAGE VOLTAGE AMPERES GAUGE BREAKER AMPS*
24 55 ft. 25 ft.
22 90 ft. 45 ft.
20 140 ft. 70 ft.
18 225 ft. 110 ft.
Junction Box (may be int. or ext. to the furnace). These connections can be made in the field supplied disconnect at the furnace.
NOTE: Connections made within the furnace burner compartment do not require a junction box.
A/C
CONDENSING UNIT
CONTROL BOX
MH
H WARNING:
CONDENSING
UNIT
L
ML When servicing either twinned furnace, power
must be turned off on both furnaces. Failure to
SPEED
JUMPER PIN comply may result in improper operation leading
to damage to the furnaces or personal injury!
3 AMP SETUP
COM
C STATUS
R &W
FAN
24V
Only G GREEN
W FLAME YELLOW
control boards. Use field supplied wire and 3/16” wire
9 6 3 180
NOTE: The “Y” terminal 8 5 2
BLOWER
OFF 120
90
terminals.
on the control board 7 4 1 DELAY 60
must be connected to
the thermostat for
6 3
NOTE: One furnace can be used for one stage of heating
proper cooling mode
operation. 5 2 and the other furnace can be used for the second stage of
4 1
heating. The installer also has the choice of running one
NEUTRALS
FIELD WIRING
furnace only or both furnaces. In both cases the blowers will
XFMR
HIGH
LOW
HUM
LOW VOLTAGE
EAC
MH
ML
L1
CONNECTION
run at the same time and at the same speeds:
MOTOR SPEED TAPS
NEUTRAL LEADS (NOT USED)
18
• Connect W from the primary furnace to the coil side of the • Connect R from the secondary furnace control board to
relay (using field supplied wire and 3/16” terminals). the COM side of the relay (use included red wire).
• Connect C from the primary furnace to the coil side of the • Connect W from the secondary furnace control board to
relay (using field supplied wire and 3/16” terminals). NO side of the relay. (Use included white wire).
NOTE: Make sure connections are made on opposite sides
of the coil. START-UP & ADJUSTMENTS
• Connect R from the secondary furnace control board to Pre-Start Check List
the COM side of the relay (use included red wire). √ Verify the polarity of the connections are correct, the line
• Connect W from the secondary furnace control board to voltage power leads are securely connected and the furnace
NO side of the relay (use included white wire). is properly grounded.
√ Verify the thermostat wires (R, W, Y, & G) are securely
Two stage heating connected to the correct leads on the terminal strip of the
• Connect the thermostat wires to the furnace control circuit board.
board (except W2). Mount the relay on the bracket on the √ Verify the jumper setting (for fan speed) on the control
secondary furnace. board. See Figure 15, (page 18).
• Connect W1 from the thermostat control to W of the primary √ Verify the gas line service pressure does not exceed 10.0
furnace. inches of W.C., and is not less than 4.5 inches W.C. for
• Connect W2 from the thermostat to the coil side of the natural gas. For LP gas the line service pressure must not
relay (using field supplied wire and 3/16” terminals). exceed 14 in. W.C., and must not be less than 11.0 in.
• Connect C from the primary furnace to the coil side of the W.C.
relay (using field supplied wire and 3/16” terminals). √ Verify the roll-out and manual reset switch is closed. If
NOTE: Make sure connections are made on opposite sides necessary, press the red button to reset a switch. DO NOT
of the coil. install a jumper wire across a switch to defeat its function.
If a switch reopens on startup, DO NOT reset the switch
SINGLE STAGE HEATING (WITH TWINNING) without identifying and correcting the fault condition.
√ Verify the blower door is in place, closing the door switch
AC
UNIT THERMOSTAT in the line voltage circuit.
Y R G W1 C W2
RELAY
√ Verify the gas line has been purged and all connections
COM
NO
are leak free.
Start-up Procedures
WHITE
RED
Expansion
Port
FURNACE FURNACE
BOARD BOARD
Expansion
BLOWER BLOWER
CONTROL CONTROL 4. Set the thermostat above room temperature and verify the
Port
Port
BOARD BOARD
Operating Sequence (page 21).
TWIN TERMINAL TWIN TERMINAL 5. After 5 minutes of operation, set the thermostat below
room temperature and verify steps 9 - 10 of the Operating
PRIMARY FURNACE SECONDARY FURNACE Sequence.
TWO STAGE HEATING (WITH TWINNING)
Verifying & Adjusting Input Rate
AC
UNIT THERMOSTAT
The input rate must be verified for each installation to prevent
Y R G W1 C W2
RELAY over-firing of the furnace. NOTE: The input rate must not
COM
NO
exceed the rate shown on the furnace rating plate. At altitudes
WHITE
above 2,000 feet, it must not exceed that on the rating plate
less 4% for each 1,000 feet. To determine the exact input
RED
Expansion
FURNACE FURNACE
2. Start the furnace and run it for at least 3 minutes.
Port
Port
BOARD BOARD
3. Measure the time (in seconds) required for the gas meter
6-Pin Wiring
Harness
6-Pin Wiring
Harness to complete one revolution.
4. Convert the time per revolution to cubic feet of gas per
Expansion
Expansion
BLOWER BLOWER
CONTROL CONTROL hour using Table 5, (page 28).
Port
Port
BOARD BOARD
5. Multiply the gas flow rate in cubic ft per hr by the heating
TWIN TERMINAL TWIN TERMINAL value of the gas in Btu per cubic ft to obtain the input rate
in Btuh. See Example.
PRIMARY FURNACE SECONDARY FURNACE
19
For typical duct systems, the temperature rise will fall within the
EXAMPLE limits specified on the rating plate with the blower speed at the
• Time for 1 revolution of a gas meter with a 1 cubic ft factory recommended setting. If the measured temperature
dial = 40 seconds. rise is outside the specified limits, it may be necessary to
• From Table 5 read 90 cubic ft gas per hr. change the speed of the blower. NOTE: Lowering the blower
• Local heating value of the gas (obtained from gas speed will increase the temperature rise and a higher blower
supplier) = 1,040 Btu per cubic ft. speed will decrease the temperature rise.
• Input rate = 1,040 x 90 = 93,600 Btuh.
The furnace is equipped with a multi-speed motor. Heating,
cooling, and fan speed selection is made by moving the switch
on the integrated control located in the furnace.
WARNING: Verifying Burner Operation
Do not attempt to drill the gas orifices. Use only
factory supplied orifices. Improperly drilled
orifices may cause fire, explosion, carbon CAUTION:
monoxide poisoning, personal injury or death. The door over the burners may only be open
for inspection purposes only. The door must be
6. Obtain the manifold pressure setting required for this installed during unattended operation.
installation by referring to Table 7, (page 29) for Propane
or Table 9 or Table 10, (page 30) for Natural Gas. 1. Remove the burner compartment door.
The manifold pressure must be set to the appropriate 2. Set the thermostat above room temperature and observe
value for each installation by a qualified installer, the ignition sequence. NOTE: The burner flame should
service agency or the gas supplier. carry over immediately between all burners without lifting
off, curling, or floating. The flames should be blue, without
7. Remove the regulator capscrew from the INLET side of yellow tips.
the regulator. See (Figure 17, (page 20). 3. After validating the flame, change the thermostat setting
8. Slowly turn the adjustment screw inside the regulator to to below room temperature.
obtain the appropriate manifold pressure. 4. Verify the burner flame is completely extinguished.
NOTE: Turning the screw clockwise increases the pressure 5. Replace the burner compartment door.
and turning the screw counter-clockwise decreases the
pressure. To prevent backing the screw all the way out Verify Operation of the Supply Air Limit
from the valve, turn the screw slowly. Switch
A properly functioning limit switch should turn off the gas
9. Replace and tighten the regulator capscrew over the
valve when the return is blocked (time depends on how well
adjustment screw.
the return air is blocked). The circulating air and combustion
Verifying & Adjusting Temperature Rise blowers should continue to run when the limit switch opens.
After installation of the furnace, confirm the temperature rise 1. Verify the blower door is securely mounted in place and
of the furnace is within the limits specified on the rating plate. that there is power to the furnace.
Any temperature rise outside the specified limits could result 2. Block the return airflow to the furnace by installing a close-
in premature failure of the heat exchanger. off plate in place of or upstream of the filter(s).
3. Set the thermostat above room temperature and observe
1. Place thermometers in the return and supply air stream the Operating Sequence.
as close to the furnace as possible. The thermometer on 4. Remove the close-off immediately after the limit switch
the supply air side must be shielded from direct radiation opens. If the furnace continues to operate with no return
from the heat exchanger to avoid false readings. air, set the thermostat below room temperature, shut off
2. Adjust all registers and duct dampers to the desired position power to the furnace, and replace the limit switch.
and run the furnace for 10 to 15 minutes before taking
any temperature readings. The temperature rise is the
difference between the supply and return air temperatures.
Capscrew
20
OPERATING SEQUENCE MAINTENANCE
The operating sequences for the heating, cooling, and fan
modes are described below. Refer to the field and furnace
wiring diagrams:Figure 14, (page 18), Figure 15, (page
WARNING:
18) and Figure 19, (page 27). ELECTRICAL SHOCK, FIRE OR
Heating Cycle EXPLOSION HAZARD
1. The thermostat calls for heat by energizing the W terminal Failure to follow safety warnings exactly could
with 24VAC. result in serious injury or property damage.
2. The control verifies the pressure switch is open.
3. If the pressure switch is open, the control energizes the Improper servicing could result in dangerous
inducer and waits for the pressure switch to close. The operation, serious injury, death or property
pressure switch must close within 10 seconds. damage.
4. The control runs the inducer for a 30 second pre-purge.
5. The control energizes the igniter output for the appropriate • Before servicing, disconnect all electrical
warm-up time limit. power to furnace.
6. The control energizes the main gas valve for 3 seconds. • When servicing controls, label all wires prior
7. If the flame proved and ignites the gas, the control de- to disconnecting. Reconnect wires correctly.
energizes the igniter. The gas valve and inducer remains • Verify proper operation after servicing.”
energized. The control goes to blower on delay.
8. If flame is present, the control energizes the blower on Proper maintenance is most important to achieve the best
the selected HEAT speed 30 seconds after the gas valve performance from a furnace. Follow these instructions for
opened. The gas valve and inducer remain energized. years of safe, trouble free operation.
9. When the thermostat demand for heat is satisfied, the
control de-energizes the gas valve. The inducer output • These maintenance instructions are primarily intended
remains on for a 30 second post-purge period. to assist qualified technicians experienced in the proper
10. Blower off timing begins when the thermostat is satisfied. maintenance and operation of this appliance.
The control will operate at the selected HEAT speed of 60, • Always reinstall the doors on the furnace after servicing or
90, 120, or 180 seconds. If the blower off delay jumper is cleaning/changing the filters. Do not operate the furnace
not present, the fan should still operate for 120 seconds without all doors and covers in place.
at the selected HEAT speed. The Indoor blower motor • Verify the thermostat is properly installed and is not being
is de-energized after a blower off delay as selected by affected by drafts or heat from lamps or other appliances.
the movable jumper. • To achieve the best performance and minimize equipment
Cooling Cycle failure it is recommended that a yearly maintenance
1. The thermostat calls for cooling by energizing the Y terminal checkup be performed. At a minimum, this check should
with 24VAC. include the following items:
2. The control energizes the blower in the cooling speed and Air Filter - An air filter is not supplied with the furnace as
sends 24VAC to the contactor in the condensing unit. shipped from the factory. The installer must provide a high
3. When the thermostat removes the call for cooling, the velocity filter that is appropriately sized to the return air duct
contactor in the outdoor condensing unit is de-energized opening or external filter rack.
and the control continues to run the fan for a period of 60
seconds.
Fan Mode WARNING:
• When the thermostat energizes the G terminal for Never operate the furnace without a filter in place.
continuous fan (without calling for heat or cooling), the Dust and lint can build up on internal components,
indoor fan is energized on the selected FAN speed. See resulting in loss of efficiency, equipment damage,
Figure 15, (page 18).
• If a call for cooling occurs during continuous fan, the blower
and possible fire.
will switch over to the selected COOL speed. It is recommended that filter(s) be 1” or 2” thick and be cleaned
• If the W terminal receives a call for heat during continuous or replaced monthly. New or newly renovated homes may
fan, the blower will de energize. require more frequent changing until the construction dust
• A call for fan is ignored while in lockout. has minimized.
• The blower will operate at 50% of the selected high cooling
speed for continuous fan operation. Filters designed to remove smaller particles such as pollen,
may require additional maintenance. Filters for side return
and bottom return applications are available from most local
distributors.
Blower Compartment - Dirt and lint can create excessive
loads on the motor resulting in higher than normal operating
temperatures and shortened service life. It is recommended
that the blower compartment be cleaned of dirt or lint that
may have accumulated in the compartment or on the blower
and motor as part of the annual inspection.
21
Cleaning of Burners - If the burners must be cleaned, follow 12. Remove all screws securing the inducer assembly to the
steps 1 - 12. See Figure 20, (page 32) for component collector pan.
location. 13. *SA models - Carefully remove the inducer assembly
1. Shut off gas supply to the furnace at the meter or at a from the furnace.
manual valve in the supply piping. *SK models - Carefully remove the inducer assembly
2. Turn off all power to the furnace and set the thermostat and combustion tube assembly from the furnace. DO
to its lowest setting. NOT BREAK THE SEALS AT EACH END OF THE
3. Remove the burner door from the furnace. COMBUSTION AIR TUBE.
4. Turn the gas control switch to the OFF position. 14. Remove all screws securing the collector pan to the
5. Disconnect the wires from the gas valve, igniter, flame furnace.
sensor, and flame rollout switch. 15. Remove the collector pan and gasket from the furnace.
16. Attach a round wire brush to a length of high grade stainless
CAUTION: steel cable. Attach the other end of the cable to a variable
speed reversible drill. Slowly insert and rotate the cable
To prevent damage to the unit or internal into the top portion of the heat exchanger. Operate the
drill alternating between forward and reverse, working
components, it is recommended that two the cable in and out several times to obtain sufficient
wrenches be used when loosening or tightening cleaning. Repeat this sequence for each heat exchanger
nuts. Do not over tighten! tube.
17. Remove all loosened debris from the heat exchanger
6. Using two wrenches, separate the ground-joint union in tubes using a vacuum cleaner.
the gas supply piping at the furnace. 18. Using a bright light, check the condition of the upper and
7. Remove the piping between the gas valve and the ground- lower sections of the heat exchanger tubes.
joint union. (If applicable). 19. Inspect the burners for accumulated dust or debris. If
8. Remove all screws securing the burner assembly to the burners must be cleaned, see page 22.
furnace. 20. Replace all the parts in reverse order that they were
9. Carefully remove the burner assembly from the furnace. removed.
DO NOT DAMAGE THE IGNITER WHILE REMOVING 21. Check gaskets for damage and replace if needed.
THE BURNER ASSEMBLY. 22. Follow the lighting instructions found on the furnace door
10. Inspect the burners for accumulated dust or debris. If to return the furnace to operation. Verify proper operation
necessary carefully clean them with a soft wire brush and after servicing.
a vacuum cleaner. DO NOT DAMAGE THE IGNITER
WHILE CLEANING THE BURNER. Vent System - Check the vent pipe and/or chimney for
11. Replace all the parts in reverse order that they were corrosion or debris. Any corroded section of vent pipe must be
removed. replaced, and any obstruction or blockage must be removed
12. Follow the lighting instructions found on the furnace door prior to operating the furnace.
to return the furnace to operation. Verify proper operation
after servicing.
WARNING:
Cleaning of Flue Passages - If the flue passages must be
cleaned, follow the steps below. See Figure 20, (page 32) Holes in the vent pipe or heat exchanger can
for component location. cause combustion products to enter the home.
1. Shut off the gas supply to the furnace at the meter or at Replace the vent pipe or heat exchanger if leaks
the manual valve in the gas supply piping. are found. Failure to prevent the circulation of
2. Turn off all power to the furnace and set the thermostat combustion products into the living space can
to the lowest temperature setting. create potentially hazardous conditions including
3. Remove the blower door from the furnace.
4. Turn the gas control switch to the OFF position.
carbon monoxide poisoning that could result in
5. Disconnect the wires from the gas valve, flame sensor, personal injury or death.
inducer, flame roll-out switch, limit switch, pressure switch
and igniter. Heat Exchanger & Burner Maintenance - The furnace
6. Remove the silicone rubber tube from the inducer. should operate for many years without soot buildup in the
7. Using two wrenches, separate the ground-joint union in flue passageways, however, the flue, vent system, and
the gas supply piping at the furnace. burners should be inspected and cleaned (if required) by a
8. Remove the piping between the gas valve and the ground- qualified service technician annually to ensure continued safe
joint union. (If applicable). operation. Pay attention to any deterioration from corrosion
9. Remove all screws securing the burner assembly to the or other sources.
furnace. Lubrication - The bearings in the blower motor and inducer
10. Carefully remove the burner assembly from the furnace. blower used in these furnaces are pre-lubricated and sealed
DO NOT DAMAGE THE IGNITER WHILE REMOVING by the manufacturer. No further oiling of the bearings is
THE BURNER ASSEMBLY. required for the life of the motor.
11. *SA models - Remove all screws securing the inducer
assembly to the vent pipe running out of the furnace
*SK models - Remove all screws securing the combustion
air tube assembly to the vent pipe running out of the
furnace.
22
FIGURES & TABLES
23 1/2
072C-24B Panel
17 1/2 11 3/4 15 7/8 16 1/8
090C-24B
072C-35C
090C-35C 21 14 19 3/8 19 7/8
B
108C-35C
126C-45D 24 1/2 15 1/4 22 7/8 23 1/8 Accepts 4” Type B Vent Pipe
34 1/2
°)
45
29 1/2
X
3 as
2
G
22 1/2
1/
22 3/4
23
X
8
15
5/
(1
1 1/4
23
1 28
LEFT SIDE FRONT VIEW RIGHT SIDE
T-stat
A (Ø 7/8)
22 1/4
Electric
Electric (Ø 7/8)
(Ø 7/8)
25
34 1/2
29 1/2
Gas Gas
22 1/2
22 1/2
7 7
25 3/8
28
23
Airflow Data
MAXIMUM AIRFLOW & TEMPERATURE RISES (° F)
*SA - UPFLOW / HORIZONTAL FURNACES - 80+ AFUE
MODEL NUMBER EXTERNAL STATIC PRESSURE (INCHES WATER COLUMN)
& MOTOR
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
HEATING INPUT SPEED
(BTUH) CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
24
MAXIMUM AIRFLOW & TEMPERATURE RISES (° F)
*SA - UPFLOW / HORIZONTAL FURNACES - 80+ AFUE
EXTERNAL STATIC PRESSURE (INCHES WATER COLUMN)
HEATING
MODEL MOTOR
INPUT 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
NUMBER SPEED
(BTUH)
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
NOTES:
* Factory Set Cooling Speed
** Factory Set Heating Speed
1. Two openings are recommended for airflows above 1,600 CFM if filter(s) is(are) adjacent to furnace
2. Temperature rises in the table are approximate. Actual temperature rises may vary.
3. Temperature rises shaded in gray are for reference only. These conditions are not recommended.
Table 3. Continued
25
MAXIMUM AIRFLOW & TEMPERATURE RISES (° F)
*SK - DOWNFLOW FURNACES - 80+ AFUE
MODEL NUMBER EXTERNAL STATIC PRESSURE (INCHES WATER COLUMN)
& MOTOR
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
HEATING INPUT SPEED
(BTUH) CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
SK054C-23A Med-High 1,155 35 1,130 35 1,110 36 1,085 37 1,055 38 1,015 39 975 41 910 44
(54,000) Med-Low** 790 51 775 52 765 52 750 53 730 55 700 57 665 60 610 66
Low 650 62 640 63 630 63 610 66 590 68 565 71 530 75 480 83
High* 1,675 32 1655 32 1640 33 1620 33 1590 34 1560 35 1520 35 1475 36
SK072C-24B Med-High 1,330 40 1315 41 1300 41 1280 42 1255 42 1230 44 1200 44 1150 46
(72,000) Med-Low** 1,180 45 1165 46 1150 46 1135 47 1115 48 1090 50 1060 50 1010 53
Low 940 57 925 58 900 59 880 61 850 63 825 65 795 67 760 70
High* 1,610 41 1590 42 1575 42 1560 43 1540 43 1495 46 1460 46 1415 47
SK090C-24B Med-High 1,295 51 1275 52 1260 53 1250 53 1220 55 1195 57 1170 57 1120 60
(90,000) Med-Low** 1,155 58 1235 54 1115 60 1095 61 1065 63 1040 66 1015 66 980 68
Low 910 73 885 75 860 78 835 80 810 82 785 85 765 87 735 91
High* 2,395 33 2,335 34 2,285 35 2,230 36 2,200 36 2,140 37 2,080 38 2,000 40
SK108C-35C Med-High 2,190 37 2,135 37 2,115 38 2,080 38 2,030 39 1,975 41 1,915 42 1,810 44
(108,000) Med-Low** 1,785 45 1,770 45 1,740 46 1,725 46 1,685 47 1,645 49 1,615 50 1,565 51
Low 1,145 70 1,110 72 1,070 75 1,035 77 1,000 80 950 84 905 88 835 96
High* 2,445 38 2,395 39 2,385 39 2,330 40 2,275 41 2,225 42 2,130 44 2,015 46
SK126C-45D Med-High 2,195 43 2,170 43 2,140 44 2,120 44 2,090 45 2,030 46 1,975 47 1,855 50
(126,000) Med-Low** 1,795 52 1,780 52 1,770 53 1,760 53 1,725 54 1,690 55 1,655 56 1,610 58
Low 1,480 63 1,475 63 1,450 64 1,440 65 1,440 65 1,415 66 1,405 66 1,375 68
NOTES:
* Factory Set Cooling Speed
** Factory Set Heating Speed
1. Temperature rises in the table are approximate. Actual temperature rises may vary.
2. Temperature rises shaded gray are for reference only. These conditions are not recommended.
26
WIRING DIAGRAM
SUPPLY FLAME VENT LIMIT
For 80+ and 90+ AIR LIMIT ROLLOUT SWITCH
BLUE BLUE
Refer to the Installation Instructions
provided with the furnace for the ORANGE ORANGE
proper heating and cooling speeds BLOWER
PRESSURE SWITCH PRESSURE LIMIT
for your application. (ON SELECT MODELS) SWITCH
ORANGE
SINGLE STAGE
THERMOSTAT
24 V 120 V
24V
COM
FAULT CONDITIONS
Diagnostic Description Green LED Red LED
GREEN RED BLOWER
Control Fault (No Power) Off Off
LIMIT
R C Y G W
L1 / Neutral Polarity Fault Flash Flash YELLOW
1 Hour Lockout Alternating Flash
Normal Operation On On GREEN 9 6 3
Pressure Switch Closed Fault On Flash 8 5 2 4 SPEED MOTOR
Pressure Switch Open Fault Flash On FLAME SENSOR
RED 7 4 1
Open Limit Switch Fault Flash Off GAS YELLOW
VALVE YELLOW
C
Electrical Information
Flame Present On
4 1 L ML
IGNITOR
EAC
LOW
HUM
HIGH
XFMR
WHITE
RED 1 1 RED
Use copper conductors only. R C BLACK ORANGE 2 2 ORANGE
BLUE 3 3 BLUE
1 1 BLACK BLACK 4 4 BLACK
INDUCER
2 2 WHITE 5 5
BLACK
6 6
7 7 BLUE
WHITE
8 8 BLUE
9 9
LEGEND: BLACK BLACK
27
Gas Information
TIME FOR CUBIC FEET PER TIME FOR CUBIC FEET PER
ONE REVOLUTION REVOLUTION OF GAS METER ONE REVOLUTION REVOLUTION OF GAS METER
(SECONDS) 1 5 10 (SECONDS) 1 5 10
10 360 1,800 3,600 66 55 273 545
12 300 1,500 3,000 68 53 265 529
14 257 1,286 2,571 70 51 257 514
16 225 1,125 2,250 72 50 250 500
18 200 1,000 2,000 74 49 243 486
20 180 900 1,800 76 47 237 474
22 164 818 1,636 78 46 231 462
24 150 750 1,500 80 45 225 450
26 138 692 1,385 82 44 220 439
28 129 643 1,286 84 43 214 429
30 120 600 1,200 86 42 209 419
32 113 563 1,125 88 41 205 409
34 106 529 1,059 90 40 200 400
36 100 500 1,000 92 39 196 391
38 95 474 947 94 38 191 383
40 90 450 900 96 38 188 375
42 86 429 857 98 37 184 367
44 82 409 818 100 36 180 360
46 78 391 783 102 35 176 353
48 75 375 750 104 35 173 346
50 72 360 720 106 34 170 340
52 69 346 692 108 33 167 333
54 67 333 667 110 33 164 327
56 64 321 643 112 32 161 321
58 62 310 621 114 32 158 316
60 60 300 600 116 31 155 310
62 58 290 581 118 31 153 305
64 56 281 563 120 30 150 300
NOTE:
The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas flow required by the furnace.
To determine the cubic feet per hour of gas flow required by the furnace, divide the input rate of the furnace by the heating value
(from gas supplier) of the gas.
28
PROPANE DERATION CHART
ALTITUDE ABOVE INPUT (BTU)
SEA LEVEL 45,000 54,000 72,000 90,000 108,000 126,000
57 56 56 56 56 56 ORIFICE SIZE
0 to 1,999 FT
10.0 10.0 10.0 10.0 10.0 10.0 MANIFOLD PRESSURE
57 56 56 56 56 56 ORIFICE SIZE
2,000 to 2,999 FT
9.0 9.0 9.0 9.0 9.0 9.0 MANIFOLD PRESSURE
57 56 56 56 56 56 ORIFICE SIZE
3,000 to 4,999 FT
8.5 8.5 8.5 8.5 8.5 8.5 MANIFOLD PRESSURE
59 57 57 57 57 57 ORIFICE SIZE
5,000 to 5,999 FT
10.0 10.0 10.0 10.0 10.0 10.0 MANIFOLD PRESSURE
59 57 57 57 57 57 ORIFICE SIZE
6,000 to 7,999 FT
9.0 9.0 9.0 9.0 9.0 9.0 MANIFOLD PRESSURE
59 57 57 57 57 57 ORIFICE SIZE
8,000 to 10,000 FT
8.5 8.5 8.5 8.5 8.5 8.5 MANIFOLD PRESSURE
29
NATURAL GAS W/ HIGH HEATING VALUE
ALTITUDE ABOVE INPUT (BTU)
SEA LEVEL 45,000 54,000 72,000 90,000 108,000 126,000
49 47 47 47 47 47 ORIFICE SIZE
0 to 1,999 FT
3.5 3.5 3.5 3.5 3.5 3.5 MANIFOLD PRESSURE
49 47 47 47 47 47 ORIFICE SIZE
2,000 to 2,999 FT
2.9 3.2 3.2 3.2 3.2 3.2 MANIFOLD PRESSURE
49 47 47 47 47 47 ORIFICE SIZE
3,000 to 3,999 FT
2.8 3.0 3.0 3.0 3.0 3.0 MANIFOLD PRESSURE
49 47 47 47 47 47 ORIFICE SIZE
4,000 to 4,999 FT
2.6 2.8 2.8 2.8 2.8 2.8 MANIFOLD PRESSURE
49 47 47 47 47 47 ORIFICE SIZE
5,000 to 5,999 FT
2.5 2.7 2.7 2.7 2.7 2.7 MANIFOLD PRESSURE
51 49 49 49 49 49 ORIFICE SIZE
6,000 to 6,999 FT
3.3 3.5 3.5 3.5 3.5 3.5 MANIFOLD PRESSURE
51 49 49 49 49 49 ORIFICE SIZE
7,000 to 7,999 FT
3.0 3.3 3.3 3.3 3.3 3.3 MANIFOLD PRESSURE
51 49 49 49 49 49 ORIFICE SIZE
8,000 to 8,999 FT
2.8 3.0 3.0 3.0 3.0 3.0 MANIFOLD PRESSURE
51 49 49 49 49 49 ORIFICE SIZE
9,000 to 9,999 FT
2.6 2.8 2.8 2.8 2.8 2.8 MANIFOLD PRESSURE
Table 9. High Altitude Deration Chart for Natural Gas - High Heating Value
Table 10. High Altitude Deration Chart for Natural Gas - Low Heating Value
30
TROUBLESHOOTING FURNACE COMPONENTS
If the furnace fails to operate check the following: The descriptions below are various functional components
• Is the thermostat operating properly? that affect the operation and shutting down of this furnace.
• Are the blower compartment door(s) in place? Some of these components and their locations are shown
• Is the furnace disconnect closed? in Figure 20, (page 32). If any component of the furnace
• Has the circuit breaker tripped or the control board fuse must be replaced, use only factory authorized replacement
burned open? parts specified in the Replacement Parts List provided online.
• Is the gas turned on?
Blower Limit Switch - Prevents operation when blower is
• Are any manual reset switches open?
not operational.
• Is the filter dirty or plugged?
• Is the flame sensor coated? (Remove and clean with steel Flame Sensor - Verifies when a flame has carried over from
wool). the igniter to the opposite end burner. If no flame is detected,
• Are all the LED’s on the furnace control board constantly the furnace will shut down within 4 seconds.
ON? If not, refer to Table 11 or the wiring diagram (Figure Flame Roll-Out Switch - Verifies that the burner flames are
19, (page 27)) to determine fault condition. drawn into the heat exchanger tubes. If the burner flames are
IMPORTANT NOTE: The furnace will lock out after 5 failed not properly drawn into the heat exchanger, the flame roll-out
attempts for ignition and will try again every hour if the switch will close the gas valve and initiate the shutdown cycle.
call for heat remains. Gas Valve - Controls the flow of gas to the burners. When the
gas valve is energized it automatically opens and regulates
• If the inducer blower is operating and items above have
the gas pressure in the manifold.
been verified, check the blower limit switch and reset if
necessary. See Figure 20, (page 32) for component Inducer Assembly - Vents products of combustion to the
location. outside.
• If the furnace operates when the blower limit switch is reset,
Pressure Switch - Verifies that the inducer is drawing
contact a qualified service technician to identify and repair
the combustion gases through the heat exchanger. The
the problem.
pressure switch prevents furnace operation with excessive
• If the furnace still doesn’t operate, check the flame roll-out
flue blockage or improper inducer operation.
switch and reset if necessary. See Figure 20 for component
location. Supply Air Limit Switch - Prevents the air temperature
• If the furnace operates when the flame rollout switch is leaving the furnace from exceeding the maximum allowable
reset, contact a qualified service technician to identify and outlet air temperature.
repair the problem.
31
UPFLOW / HORIZONTAL FURNACE (*SA SERIES)
Main Air
Limit Switch
Blower
Assembly
Blower Assembly
Combustion Tube
Inducer Assembly
Gas Valve
Main Air Limit Switch
Gas Manifold
Igniter
32
33
34
35
INSTALLATION CHECKLIST
INSTALLATION ADDRESS:
Supply Voltage:................................................................ VOLTS
CITY: STATE: Has the thermostat been calibrated? YES NO
Is the thermostat level? YES NO
UNIT MODEL #
Is the heat anticipator setting correct? YES NO
UNIT SERIAL #
GAS SYSTEM
Minimum clearances as showni n
YES NO Natural
Figure 1, (page 5)? Gas Type: (circle one) Propane
Gas
Has the owner’s information been
YES NO Gas pipe connections leak tested? YES NO
reviewed with the home-owner?
Has the literature package been
YES NO Gas Line Pressure:........................................................... (in - W.C.)
left near the furnace?
Installation Altitude:............................................................(FT.)
PROPOSITION 65 WARNING:
Deration Percentage:..........................................................(%)
WARNING:This product contains chemicals known
Furnace Input:....................................................................(Btuh)
to the state of California to cause cancer.
Specifications & illustrations subject to change without notice or incurring obligations (08/18). 709044E
O’Fallon, MO, © Nortek Global HVAC LLC 2018. All Rights Reserved. (Replaces 709044D)