Professional Documents
Culture Documents
What Is Generator Synchronization1
What Is Generator Synchronization1
● Reliability: With multiple alternators, parallel operation is much more reliable than single-unit
generators. In a single-unit system, the whole setup will shut down if the alternator fails. In
parallel systems, one alternator can fail and the other units will keep the system active.
● Continuity: If a unit needs maintenance, the other systems can stay up and running to prevent
your entire operation from stopping.
● Load: Your load requirements may vary throughout the day. Adjust your parallel system to
accommodate higher and lower loads with more or fewer active systems.
● Efficiency: Generators run at the highest efficiency when they operate at their load rating. By
adapting to load changes, your system can remain efficient at all times.
● Capacity: Bigger operations require more power. With more generators, systems have more
alternators for increased capacity.
Phase Angle
The voltage produced by the generator and grid must be zero. The phase angle can be
determined by comparing the frequent occurrence of the peaks or zero crossing of the
sinusoidal waveforms.
If the breaker is closed when both their values are same, the connection will be seamless and
reliable. Only then the pointer will indicate 12:00 o’clock (Figure 4 below)
If the generator is exactly out-of phase (180°), the ponter will indicate 6:00 o’clock.
Incase the generator is slower than the grid, the synchroscope would rotate rapidly anti-
clockwise.
If the breaker was closed, the generator would be out of step and act like a motor. The grid
would try to increase its speed. The motor and stator will be slipping poles and can damage the
generator. This same problem si to occur id the generator was fasgter than the grid. The grid
would try to decrease its speed, resulting in the slipping of poles.
Voltage Magnitude
The magnitude of voltage produced by the generator and the grid must be equal.
Incase of the conditions being met by the voltages differing (Voltage Differential), closing the AC
generator output breaker will cause a large MVAR flow.
As we now know that when a generaator is synchronized to the grid, the internal voltage and the
terminal voltage of the generator are equal.
If the generator voltage is higher than the grid voltage: the internal voltage is higher than the
grid voltage, it will put out MVAR
If the generator voltage is less than the grid voltage: the internal voltage is lower than the grid
voltage, it will absorb MVAR
Phase sequence :
The phase sequence of the three phases of the generator must be the same as the three phases of the
electrical system or grid. The sequence of the power leads can be changed during maintenance.
For a better understanding, if a generator is producing an ABC sequence and the bus is operating a
different sequence like CDE will create a magnetic field disturbing the rotation of the machine. With this
opposition, high pulsating torques are created, which can in some cases damage the machine.
We need a method to identify if the poles of the three-phase switch have zero voltage. This can be solved
with the help of manual techniques although many automatic electronic devices allow safe and reliable
paralleling of synchronous generators.
FIGURE 1: The problem of synchronizing a generator with the power system.
However, only one phase can be in phase at any given time if the phase sequences are
different, as shown in Figure 2(c). As a result, each light would go out sequentially. Keep in
mind that when the voltage is too low to light the bulbs but not zero, they will remain dark for
some time.
FIGURE 2: Three-bulb method for synchronizing a generator to an infinite bus.
Schematic.
Phasor diagrams of generator and bus voltages with the same phase sequences.
Phasor diagrams of generator and bus voltages with opposite phase sequences.
To properly parallel a generator using the three-bulb method, the generator should be brought up to a few
RPM over synchronous speed and the excitation should be adjusted so that the voltages on the two sides
of the switch are approximately equal.
If the phase sequences are correct, then the bulbs should be glowing and be darkening together. With the
generator running only a few RPM above synchronous speed, the cycle time for the bulbs to lighten and
darken should be five to ten seconds. If that is the case, then the switch can be closed during the middle of
the dark cycle and the generator will pull into synchronism with the infinite bus.
If the phase sequence is incorrect, then the bulbs will go dark one at a time. In that case, the generator
should be shut down and two of its connections to the switch should be reversed. Then the process can be
repeated.
“Note that it is important that the generator is operating slightly above synchronous speed. That way,
when the switch is closed, the generator must slow down slightly, which means it will deliver power to
the bus. If the machine was running below synchronous speed, it would have to speed up when the switch
was closed, which would require that it draws power from the bus, making it a motor.”
The light bulbs must have a voltage rating of twice the phase voltage since the voltages can be 180° out of
phase. Obviously, on higher voltage systems, that can be a problem. To solve that, transformers can be
used.
● Schematic.
● Open-delta connection.
Two-Light-and-One-Dark-Method
Two-Light and One-Dark Method A three-bulb method variation that provides
frequency data is depicted in Figure 4.
Here, the two external stages are cross-associated. The middle bulb is dark and the
outside ones are bright when the system and generator are phased correctly. The
bulbs will flash sequentially if the frequencies differ, and the direction of the
flashing indicates whether the generator speed is high or low.
The ability to close the switch when the two outside lights are at their maximum
(at equal brightness) is another benefit of this method. The operator can close the
switch when the system and generator are more closely aligned because it is easier
to determine the maximum brightness than the middle of the dark period. Using a
synchroscope is another method for determining the relative frequency or phase
angle.