CMC4+ Only Commisioning
CMC4+ Only Commisioning
COMMISIONING
• For doing so, X84 in UBA2 must be disconnected and lift in normal from the control cabinet.
4.0.2. Cabin roof “in level” with door sill in lift with encoder positioning:
If we want to do like this, we must activate/deactivate 3 times landing door lock (at any floor except bottom one) and press
landing call After acting about landing door lock, LOP will make bip signal in that moment we must press that landing call,
and the lift will move down in slow speed and leave the car roof “in level” with that door sill. If after 20 seconds we did not
change to Insepction, lift will return to nomral mode.
POME/DiagPC/DiagPDA Write in address position AE39=A5, controller will change to 00 or 01 depending on the new
direction; if the process is faulty it will show FF. Activate recall for saving changes.
CMB/CMS
FI
4.1.1. Electrical/mechanical components revision: Checking the installation without power supply
• Right functioning of electrical/mechanical components all of them are making right contact.
4.1.2. Insolation of the shaft installation ohm resistance between UBA2 0V and installation earth is zero ohms; J50 must
be placed
4.1.3. Phases Voltages L1, L2 and L3 are according to the specifications with +10% and -15%
• Voltage in board input voltage: it must be taken with the connector unplugged from the board; it must follow the order
of the next table 1.
output voltage: it must be taken with the connector plugged to the board; it must follow the order of
the next table 2.
Table 1 Table 2
TENSIÓN in Connector Board TENSIÓN in Connector Board
230 Vac X133.3 (PE), X133.2 (N), X133.1 (L1) UBA2 230Vac X130.1 y X816.1 (N), X130.2 y X816.3 (L1), X816.2 (PE) UBA2
24 Vdc X302.1(+), X302.2(-) UCC2 24 Vdc X604.1 o X604T.1(+), X604.2 o X604T.2(-) UCP+
24 Vdc X602.1(+), X602.2(-) UCP+ X813, X814 (Brake power supply) UBV
4.1.6. Automatic rescue for lack of power supply: UPS parameter 32E4 must be
01. Only in HD lifts must be 03
4.1.7. Brake tests: Lift must be in normal, top/bottom level and Static & dinamic
must be done in sequence.
• Static turning –S72 right or left (I or II position) and keeping so for more
than 4 seconds, one brake (I or II) will be opened; we can see it by LEDs SF1
and SF2, Off=open and On= close. Repeat the same for the other brake.
• Dinamic After making both static tests; turning –S72 (I or II position) and
giving order to move from the UBA2 board; then lift will start to move and when
it reachs nominal speed it will activate one break and lift will be stopped; then
send the lift to the floor where it started (by pressing up/down push button in
the UBA2 or by –S154.1. Repeat the test for the other brake,
Always to disconnect the power supply and check jumpers in the new board are in the same place.
Leave the controller in rappel or switch lift off. Then we can start to upgrade the FW into CMC4+ boards.
The only FW which is uploaded through the big red connector is the UCM2 (USB2CMC4 or TKE-USB).
The rest of the CMC4+ board should be upgraded through the small red connector of TKE-USB or the
group USB2CMC4+special adapter.
Before reaching job site: LCA1 must be activated and take it with you for commisioning +
POME/BOMO/DiagPC/DiagPDA/LD2T,
At job site:
• Shaft teaching
• Load weight device tare
Shaft teaching: if lift has encoder positioning. LIFT IN NORMAL in bottom floor (FI on and CMB OFF).
When the lift has made a complete travel of the shaft: AE53 or F4 will show «00»: Teach-in correctly
done or «FF» fault during the process.
If we want to know the % of load inside the car controller must be in rappel; then activate and deactivate
SW3 in the UCM2 and car display will show % of cabin nominal load,
With one load weight cell in traction ropes Tare must be carried out in 2 steps. First tare at the bottom flor
and second one at the top floor.
For working with this option, calibration with two point of load is needed. And activate P8,18 in Vacon VVVF.
Lift in recall
*3 to 00; in this moment controller is waiting for ‘0’ car call, so we must activate ‘0’ cabin push button;
then display will change to 01 and we’ll press ‘1’ cabin push button;
…
if display shows 40, we’ll press open push button in COP. Ckeck table 3
Whenever we have finished with push buttons, we’ll press the last one pressed as many time as
needed to get *3 on the display again.
42 Ccanelling calls
43 cabin priority
44 authorized persons
45 firemen indicator
46 overload
47 buzzer
48 VIP/Shabbat/Attika indicator
49 lift man
56 firemen key
Elevator Manufacturing Spain
57 fan key
58 Shabbat key
59 light key
71 keypad 2
72 keypad 3
73 keypad 4
CMC4+ new generation. DIAGNOSTIC TOOLS
May 2013
88
Opening door in operation
29 1Dh No APER_PTARUN_200 No
<200ms
30 1Eh No Free No
31 1Fh No Free No
Overload sensor activation
32 20h No EXCESO_CARGA No
detected
Differential load sensor activation
33 21h No EXCESO_CARGA_DIF No
detected
Communication failure of the
34 22h No FALLO_MPLEX No
multiplex lift group
Rotational emergency power
35 23h No CORRIENTE_EMERGENCI No
function activated
Elevator Manufacturing Spain
May 2013
55 37h YES PMS_SIN_PANT *8
activated without vane(1V)
89
Stop travel when downwards
56 38h YES PMB_SIN_PANT *8
activated without vane(1V)
57 39h YES APER_SERIE_SEG *9 Safeties series opening
58 3Ah YES APER_S40_MARCHA *4 Presence series opening
59 3Bh YES APER_S41_MARCHA *4 Interlock series opening
60 3Ch YES INCONGRUENCIA *9 Incorrect variables detected
Slowdown when upwards
61 3Dh YES CMS_ERROR *6
incorrect activation B323
Slowdown when downwards
62 3Eh YES CMB_ERROR *6
incorrect activation B322
Opening with slowdown when
63 3Fh YES APER_SEG_CMS *9
upwards B323
Elevator Manufacturing Spain
May 2013
30 seconds
90
Back safety edge activated for 30
84 54h YES BORT_ACT_30S *0
seconds
Teach-in failure, rear landing
85 55h YES NO_UCPS_TRASERO *A board not detected, level shown
in POME
Teach-in failure, front landing
86 56h YES NO_UCPS_FRONTAL *B board not detected, level shown
in POME
Teach-in failure, more landing
87 57h YES MAS_UCPS_FRONTAL *A boards than programmed are
detected (front)
Teach-in failure, more landing
Elevator Manufacturing Spain
May 2013
(CPI-CAN)
91
Brake switch surveillance,
105 69h YES NO_CAE_BRK1 *1 contact does not switch off BRK1
(CPI-CAN)
Brake switch surveillance,
106 6Ah YES NO_ENTRA_BRK2 *1 contact does not switch on BRK2
(CPI-CAN)
Brake switch surveillance,
107 6Bh YES NO_CAE_BRK2 *1 contact does not switch off
BRK2(CPI-CAN)
108 6Ch YES FALLO_INITCPI *1 Initialisation failure CPI CAN
109 6Dh NO SHAFT_FUME_SENSOR_ON NO Smoke detector in shaft activated
Fault of unintended movement
110 6Eh YES FALLO_CMI_A3 *3
Elevator Manufacturing Spain
control system
111 6Fh YES INCOHERENCIA_CONTAJE *8 Fault end section bi-stable
112 70h NO INUNDACION_SENSOR_ON no Buoy flooding sensor activated
113 71h YES ERROR_PARAM_CMI_A3 *3 Error in parameter ControlMI_A3 ThyssenKrupp
It has been detected that a
114 72h YES NIVEL_BAJO_ACEITE *0 hydraulic elevator has low oil
level
115 73h NO LUZ_CABINA_SENSOR_ON NO Car light fault detected
Command to stop received from
116 74h YES PARADA_TELESERVICIO *0
remote service
After an automatic fire service
evacuation as per
May 2013
switch off
92
Upwards trip contactor does not
135 87h YES NO_ENTRA_UCONT *1
switch on
Upwards trip contactor does not
136 88h YES NO_CAE_UCONT *1
switch off
Downwards trip contactor does
137 89h YES NO_ENTRA_DCONT *1
not switch on
Downwards trip contactor does
138 8Ah YES NO_CAE_DCONT *1
not switch off
Downwards trip contactor does
139 8Bh YES NO_CAE_UDCONT *1
not switch off
140 8Ch YES NO_PROX_PAR *8 Next stop not defined
141 8Dh YES NO_MOTORCODE *9 Traction type not defined
Elevator Manufacturing Spain
in POME
Maximum time delay after
158 9Eh YES NO_RET_RBB *9
electrocam de-energisation
159 9Fh YES NO_PREFER_SUB *9 Preferential upper level number
160 A0h YES NO_PREFER_INF *9 Preferential lower level number
161 A1h YES NO_LOBBY_1 *9 Main level 1 number
162 A2h YES NO_LOBBY_2 *9 Main level 2 number
163 A3h YES NO_PLANTA_BOMBEROS *9 Fire service floor not defined
Delta contactor does not switch
164 A4h YES NO_ENTRA_DRDCONT *1
on
Delta contactor does not switch
165 A5h YES NO_CAE_DRDCONT *1
off
May 2013
168 A8h NO CODE_FOT_F1 *8
pulse fault (additional info )
93
Photo switch position sensor
169 A9h NO CODE_FOT_F2 *8
pulse fault (additional info )
Photo switch position sensor
170 AAh NO CODE_FOT_F3 *8
pulse fault (additional info )
Starting command without
171 ABh NO START_SIN_DIRECCION *8
setting the direction of travel
A required MP1_TKE module
172 ACh YES FALLO_EQUIPO_MP1_TKE *3
does not work
173 ADh YES SITUAC_RESCATE *3 DEA rescue device activated
174 AEh YES RESCATE_OK *3 DEA rescue finished
175 AFh YES RESCATE_ERROR *3 Error in the DEA rescue control
General fault in intermediate
Elevator Manufacturing Spain
May 2013
193 C1h YES FALLO_SCNC_BRAKE_VACONCAN *1
the series normally closed
94
At start-up the series which are
normally open and the series
194 C2h YES FALLO_SCNCNA0_VACON_CAN *1
normally closed are not in their
initial status
At start-up the series which are
195 C3h YES FALLO_SCNCNA_VACON_CAN *1
normally closed fail to open
At start-up the Inverter does not
FALLO_SECUANCIA_ESP_VACONC
196 C4h YES *1 authorise the activation of the
AN
motor contactor
FALLO_SECUANCIA_EBS_VACON At start-up the Inverter does not
197 C5h YES *1
CAN authorise brake release
At start-up the series which are
FALLO_SCNA_BRAKE_EBS_VACO normally open do not close or do
198 C6h YES *1
NCAN not open the brake micro
switches
While running the inverter run
199 C7h YES FALLO_CAE_RUN_VACONCAN *1
signal fails
The control is in brake testing
Elevator Manufacturing Spain
ThyssenKrupp
CMC4+ new generation Elevator Manufacturing Spain
May 2013
97 ThyssenKrupp
Technical Service – CSC NI
Elevator Manufacturing Spain