reference colour tags

Combined Overcurrent &


Earth Fault Relay MK 2200L
MK 2200
MK 1000A
Overcurrent Relay
MK 233A
MK 234A
MK 203A
MK 204A
Earth Fault Relay
MK 231A
MK 232A
MK 201A
MK 202A
contents

Earth Leakage Relay


MK 300A / 300EA
MK 330A
MK 301A / 302A / 301E
DIN 330
DIN 310 / 310E
DIN 300 / 300E
ZCT 40S / 60S / 80S / 120S / 210S
Digital Power Meter
DVM
DAM
DPM 680
DPM 380 / 380B
DM 38
Voltage Relay
MU 2300
MU 350
MU 250 / 150
MX 210
MX 200A / 180A / 160A
MX 100 / 50
Reverse Power Relay
RPR 415A
RPR 415

Power Factor Regulator


PFR 140 / 120 / 80 / 60
PFR 96 / 96P
PFR LCD
Annunciator
AN 112 / 120 / 128
AL 24

Motor Protection Relay


MPR 500
Print Edition
June 2015

( 423468-T )
No.1 Jalan TP 7/7, Sime UEP Industrial Park,
40400 Shah Alam, Selangor, Malaysia.
Website: www.itmikro.com
Tel: +60-3-5192-7155
Fax: +60-3-5192-7166

Mikro® reserves the right to make changes without further notice


to any products herein to improve reliability, function or design.
The figures shown are without obligation.
Combined Overcurrent & Earth Fault Relay
MK2200L
Features
• Multifunction numerical relay
• Three-phase, three stages setting for phase
overcurrent
• Two stages setting for earth fault
• IDMT and definite time
• Thermal overload protection
• Two groups of protection settings
• Trip circuit supervision
• Circuit breaker failure protection
• RS232 and RS485 MODBUS-RTU communication
• Fault, alarm and tripping records with timestamp
• Multifunction programmable outputs
• Multifunction digital inputs
• Complies with IEC 60255-26 standard
• ANSI code : 49RMS, 50P, 50G, 51P, 51G,
CLP, 50BF, 74TC

Technical Data
RATINGS RECORDS Thermal Overload
Fault Record : Up to 50 records Ie > : 0.1 to 3 x In
Auxiliary Supply Event Record : Up to 250 records Te : 1 to 200 minutes
Model MK2200L-150D Alarm Record : Up to 30 records k : 1 to 1.5
Rated voltage : 30 ~ 120 V DC eTrip : 50 to 200%
Operating voltage : 24 ~ 150 V DC eAlarm : 50 to 200%
SETTING RANGES
Model MK2200L-240AD
Rated voltage : 100 ~ 240 V AC or General
140 ~ 340 V DC Line CT primary : 1 to 10,000 A MEASUREMENT RANGES
Operating voltage : 85 ~ 265 V AC or Earth CT primary : 1 to 10,000 A Phase Current Secondary:
110 ~ 370 V DC Frequency : 50 or 60 Hz 5 A input : 0 to 200 A
Rated frequency : 50 or 60 Hz 1 A input : 0 to 40 A
Operating frequency : 45 ~ 65 Hz
Power consumption : 8 VA max Phase Overcurrent Earth Current Secondary:
I> : 0.1 to 25 x In (Recommended up to 5 A input : 0 to 50 A
Current Inputs 2 x In for IDMT delay) 1 A input : 0 to 10 A
Rated current, In, Ion : 1 or 5 A by connection I> Delay type : IDMT or definite time
Frequency : 50 or 60 Hz nominal tI> : 0 to 100 s
Burden : < 0.025 VA (1 A) I> IDMT curve : NI, VI, EI, LTI, NI 1.3/10
: < 0.3 VA (5 A) ktI : 0.01 to 1.00 ENVIRONMENTAL CONDITIONS
Thermal withstand : 4 x In continuous I>> : 0.5 to 40 x In Temperature : -5˚C to 55˚C
: 40 x In for 2s tI>> : 0 to 100 s Humidity : 56 days at 93% RH and 40˚C
: 100 x In for 1s I>>> : 0.5 to 40 x In non-condensing
I>>> Sample : Yes or No
Digital Inputs tI>>> : 0 to 100 s
MK 2200L

Input type : Optically isolated MECHANICAL


Rated voltage : 20 ~ 380 V DC Mounting : Panel mounting
: 50 ~ 270 V AC Earth Fault Dimension (mm) : 142(w) x 165(h) x 198(d)
Io> : 0.02 to 2 x Ion (Recommended up Enclosure protection : IP54 at the panel
Output Contacts to 0.5 x Ion for IDMT delay) Approximate weight : 2.9 kg
Trip Contact Relay R1, R2, R3, R4, IRF Relay Io> Delay type : IDMT or definite time
Rated voltage : 250 V AC / DC tIo> : 0 to 100 s
Continuous carry :5A Io> IDMT curve: NI, VI, EI, LTI, NI 1.3/10
Expected electrical life : 100,000 operations at ktIo : 0.01 to 1.00
rated load Io>> : 0.1 to 10 x Ion
Expected mechanical life : 5 x 106 operations tIo>> : 0 to 100 s
Combined Overcurrent & Earth Fault Relay

Normal Inverse Very Inverse Extremely Inverse

Typical Application Diagram 1 Long Time Inverse

Case Dimensions
142 mm
198 mm
34 mm

Typical Application Diagram 2


165 mm

136 mm

Front Side

129 ±1 mm
139 ±1 mm

Panel Cutout
MK 2200L

Ordering Information
MODEL DESCRIPTION
MK2200L - 150D For 50/60 Hz, auxiliary voltage 24 ~ 150 V DC
MK2200L - 240AD For 50/60 Hz, auxiliary voltage 85 ~ 265 V AC
or 110 ~ 370 V DC
Combined Overcurrent & Earth Fault Relay
MK2200
Features
• Multifunction numerical relay
• Three-phase, low-set and high-set phase overcurrent
• Two sets of low-set and high-set setting for phase
overcurrent
• Low-set and high-set earth fault
• Two sets of low-set and high-set setting for earth fault
• Circuit breaker failure protection
• Four selectable IDMT characteristic curves
• Definite time for low-set and high-set
• Numeric display of phase and earth fault currents
• Display of relay settings
• 9 non- volatile records of previous tripping currents
• Recording of relay start time
• Highly flexible programmable relay outputs
• Multifunction external digital input
• Isolated RS485 Modbus - RTU communication
• Selectable 50 Hz / 60 Hz
• ANSI code : 50P, 50G, 51P, 51G, 50BF

Technical Data
INPUTS ACCURACY Time multiplier kt > : 0.02 ~ 1.0 ,
Measuring input: Protection thresholds : ± 3% step 0.01
Rated current In : 1 A or 5 A Time delay : ± 2% with a minimum Low set definite time t >, 0 ~ 300 s :
Rated frequency : 50 or 60 Hz of 30 ms 0 ~ 10.0s : step 0.01
Thermal withstand : 4 x In continuous Measurements : ± 3% 10.0 ~ 100s : step 0.1
25 x In for less than 10 sec Reset ratio : 95% typical 100 ~ 300s : step 1
100 x In for less than 1 sec Overshoot time : less than 30 ms typical
Burden : < 0.3VA at In High set definite time t >>, 0 ~ 300 s :
0 ~ 10.0s : step 0.01
Rated auxiliary voltage: EARTH-FAULT ELEMENT 10.0 ~ 100s : step 0.1
Model MK2200-150D : 24~150 V DC Low-set setting I o> : 0.05 ~ 1.0 x In , 100 ~ 300s : step 1
Model MK2200-240A : 198~265 V AC step 0.01
Model MK2200-240AD : 85~265 V AC High-set setting I o>> : 0.05 ~ 10.0 x In , ENVIRONMENTAL CONDITIONS
110~340 V DC step 0.05 Temperature : -5˚C to +55˚C
Humidity : 56 days at 93% RH and 40˚C
Power consumption: Time multiplier kt o> : 0.02 ~ 1.0 , non-condensing
AC auxiliary voltage : 6 ~ 10 VA typical step 0.01
DC auxiliary voltage : 5 ~ 9 W typical Low set definite time t o>, 0 ~ 300 s :
0 ~ 10.0s : step 0.01 MECHANICAL
Binary Input: Mounting : Panel mounting
External binary input : 18 ~ 265 V DC 10.0 ~ 100s : step 0.1
100 ~ 300s : step 1 Dimension (mm) : 142(w) x 165(h) x 198(d)
85 ~ 265 V AC Enclosure protection : IP54 at the panel
High set definite time t o>>, 0 ~ 300 s :
MK 2200

Approximate weight : 2.9 kg


0 ~ 10.0s : step 0.01
OUTPUT CONTACTS 10.0 ~ 100s : step 0.1
5 programmable contacts +1 IRF contact: 100 ~ 300s : step 1 COMMUNICATION
Rated voltage : 250 V AC / DC RS485 Modbus - RTU
Continuous carry :5A OVERCURRENT ELEMENT
Contact specification: Low-set setting I > : 0.10 ~ 2.50 x In ,
Expected electrical life : 100,000 operations step 0.01
at rated current High-set setting I >> : 0.10 ~ 40 x In ,
Expected mechanical life : 5 x 106 operations 0.1 ~ 10 In : step 0.05
10 ~ 40 In : step 0.1
Combined Overcurrent & Earth Fault Relay

Normal Inverse Very Inverse Extremely Inverse


t/s t/s t/s
100

10

10
10

k 1 k
1.0 1.0
0.9
0.8 0.8
0.7 0.6 1
0.6 0.5
0.5 0.4
1 0.4 0.3

0.3 0.2 k
1.0
0.1 0.8
0.2 0.6
0.1
0.1 0.5
0.4
0.3
0.05
0.1 0.2
0.05 0.1

0.05
0.1 0.01 0.01
1 10 20 I/I > 1 10 20 I/I > 1 10 20 I/I >

Typical Application Diagram 1 Long Time Inverse


L1
L2 t/s
L3 1 COM 34
2 5A 36
Trip Contact
35 R1
3 1A

4 COM 38
5 5A 37 R2

6 1A 40
39 R3
7 COM
8 5A
42
9 1A 41 R4

10 COM 27
11 5 A 26 R5
12 1 A
28 Internal
External 13 30 Relay
29
Binary
14 22
Failure I/I >
Input Termination Resistor
32 23 N- RS485
Auxiliary
input Uaux 33 24 P+
31 25 Communication Case Dimensions
LOAD Cable Shield
142 mm
198 mm
34 mm
Typical Application Diagram 2
L1
165 mm

136 mm

L2 Front Side
L3
N 1 COM 34
2 5A 36
Trip Contact
35 R1
3 1A
129 ±1 mm
4 COM 38
5 5A 37 R2

6 1A 40
139 ±1 mm

39 R3
7 COM
8 5A
Panel Cutout
42
9 41 R4
MK 2200

1A

10 COM 27
11 5 A 26 R5
12 1 A

13
28
30
Internal Ordering Information
External Relay
Binary 29 Failure
14 22
Input Termination Resistor MODEL DESCRIPTION
32 23 N- RS485
Auxiliary
33 24 P+
MK2200 - 150D For 50/60 Hz system, auxiliary voltage 24 ~ 150 V DC
input Uaux

LOAD
31 25 Communication MK2200 - 240A For 50/60 Hz system, auxiliary voltage 198 ~ 265 V AC
Cable Shield
MK2200 - 240AD For 50/60 Hz system, auxiliary voltage 84 ~ 265 V AC
or 110 ~ 340 V DC
Combined Overcurrent & Earth Fault Relay
MK1000A
Features
• Microprocessor based numerical relay
• Current measurement based on fundamental
frequency
• Three-phase, low-set overcurrent
• Three-phase, high-set overcurrent
• Low-set earth-fault
• High-set earth-fault
• Definite time for low-set and high-set
• Five selectable IDMT characteristic curves
• Local display of measured and set values
• Programmable relay outputs
• Non-volatile fault values recording
• Complies with IEC 60255-26 standard
• ANSI Code : 50P, 50G, 51P, 51G

Technical Data
RATINGS SETTING RANGES INDICATORS
Rated current ( In ) : 5A i ) Overcurrent elements Auxiliary supply : Green indicator
Rated frequency : 50 or 60 Hz Low-set ( I > ) : 0.5 A to 10.0 A, Pick-up : Red indicator
Burden : < 0.3 VA at In step 0.05 A Trip : 7-segment display
Themal withstand : 4 x In continuous : 10% to 200%, and red indicators
step 1%
AUXILIARY SUPPLY Low-set time multiplier ( kt >): 0.05 to 1.0,
Model MK1000A-240A(6) : 198 ~ 265 V AC step 0.01 ENVIRONMENTAL CONDITIONS
Low-set definite time ( t > ) : 0.05 to 99s
Model MK1000A-240AD(6) : 85 ~ 265 V AC Temperature : -5˚C to +55˚C
High-set ( I >> ) : 0.5 A to 99.9 A,
110 V DC ~ 340 V DC Humidity : 56 days at 93% RH and 40˚C
step 0.10 A or
Model MK1000A-150D(6) : 24 ~ 150 V DC disable non-condensing
Supply frequency : 50 or 60 Hz : 10% to 1998%,
V A rating : 3 VA typical step 2% MECHANICAL
High-set delay time ( t >> ) : 0.05 sec to 2.5 sec, Mounting : Panel mounting
ACCURACY step 0.01 Dimension (mm) : 96(w) x 96(h) x 110(d)
Protection thresholds : ± 5% Enclosure protection : IP54 at the panel
Time delay : ± 5% with a ii ) Earth-fault element Approximate weight : 0.8 kg
minimum of 50 ms Low-set ( I o > ) : 0.10 A to 5.0 A,
step 0.05 A
OUTPUT CONTACTS : 2% to 100%
MK 1000A

Low-set time multiplier(kt o>): 0.05 to 1.0,


Trip Contacts ( R1 & R2 )
step 0.01
Rated voltage : 250V AC / DC
Low-set definite time ( t o > ) : 0.05 to 99s
Contact rating : 5A High-set ( I o >> ) : 0.10 A to 50 A,
Expected electrical life : 100,000 operations step 0.10 A or
at rated current disable
Expected mechanical life : 5 x 106 operations : 2% to 1000%,
step 2%
High-set delay time ( t o >> ) : 0.05 sec to 2.5 sec,
step 0.01
Combined Overcurrent & Earth Fault Relay

Normal Inverse Very Inverse Long Time Inverse

Typical Application Diagram


Aux
L N MK1000A
NO NC COM COM NC NO
1 2 3 4 5 6 7 8

R1 R2
Extremely Inverse Normal Inverse 1.3/10 9 10 11 12 13 14 15 16

L1
L2

LOAD
L3
N

Case Dimensions
96 mm
96 mm

Front

110 mm
100 mm

Side
Ordering Information
MK 1000A

MODEL DESCRIPTION
MK1000A-240A For 50Hz system, auxiliary voltage 198 ~ 265 V AC 91.0 ± 0.5 mm
MK1000A-240AD For 50Hz system, auxiliary voltage 85 ~ 265 V AC or 110~340 V DC
MK1000A-150D For 50Hz system, auxiliary voltage 24 ~ 150 V DC
91.0 ± 0.5 mm

MK1000A-240AD6 For 60Hz system, auxiliary voltage 85 ~ 265 V AC or 110~340 V DC


Panel Cutout
MK1000A-150D6 For 60Hz system, auxiliary voltage 24 ~ 150 V DC
Overcurrent Relay
MK233A
Features
• Microprocessor based numerical relay
• Current measurement based on fundamental
frequency

• Three-phase, low-set overcurrent


• Three-phase, high-set overcurrent
• Local display of measured and set values
• Definite time for low-set and high-set
• Non-volatile fault value recording
• Programmable relay outputs
• Five selectable IDMT characteristic curves
• Complies with IEC 60255-26 standard
• ANSI Code : 50P, 51P

Technical
echnical Data
RATINGS ACCURACY INDICATORS
Rated current ( In ) : 5A Protection thresholds : ± 5% Auxiliary supply : Green indicator
Rated frequency : 50 or 60 Hz Time delay : ± 5% with a minimum of Pick-up : Red indicator
Burden : < 0.3 VA at In 50 ms Trip : 7-segment display and
Thermal withstand : 4 x In continuous red indicators

OUTPUT CONTACTS (R1 & R2)


AUXILIARY SUPPLY Rated voltage : 250 V AC / DC ENVIRONMENTAL CONDITIONS
Model MK233A-240A (6) : 198 ~ 265 V AC Contact rating : 5A Temperature : -5˚C to +55˚C
Model MK233A-110A (6) : 94 ~ 127 V AC Expected electrical life : 100,000 operations at Humidity : 56 days at 93% RH and 40˚C
Supply frequency : 50 or 60 Hz rated current non-condensing
VA rating : 3 VA typical Expected mechanical life: 5 x 106 operations

MECHANICAL
SETTING RANGES Mounting : Panel mounting
Low-set ( I > ) : 0.5 A to 6.0 A, step 0.05 A / 10% to 120%, step 1% Dimension (mm) : 96(w) x 96(h) x 110(d)
Low-set time multiplier ( kt > ) : 0.05 to 1.0, step 0.01 Enclosure protection : IP54 at the panel
Low-set definite time (t >) : 0.05 to 99 sec, step 0.01 (0.05 to 1.0) / 0.1 (1.0 to 99) Approximate weight : 0.8 kg
High-set ( I >> ) : 0.5 A to 99.9 A or disable, step 0.10 A / 10% to 1998%, step 2%
MK 233A

High-set delay time ( t >> ) : 0.05 sec to 2.5 sec, step 0.01
Overcurrent Relay

Normal Inverse Very Inverse Long Time Inverse

Typical Application Diagram


Aux
L N MK 233A
NO NC COM COM NC NO
1 2 3 4 5 6 7 8

R1 R2
Extremely Inverse Normal Inverse 1.3/10
9 10 11 12 13 14 15 16

L1
L2

LOAD
L3
N

Case Dimensions
96 mm
96 mm

Front

110 mm
100 mm

Side
Ordering Information
MODEL DESCRIPTION
MK 233A

MK233A - 240A For 50 Hz system, auxiliary voltage198 ~ 265 V AC 91.0 ± 0.5 mm


MK233A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
MK233A - 240A6 For 60 Hz system, auxiliary voltage198 ~ 265 V AC
91.0 ± 0.5 mm

MK233A -110A6 For 60 Hz system, auxiliary voltage 94 ~ 127 V AC


Panel Cutout
Overcurrent Relay
MK234A
Features
• Microprocessor based numerical relay

• Current measurement based on fundamental


frequency

• Three-phase, low-set overcurrent

• Three-phase, high-set overcurrent

• Local display of measured and set values

• Definite time for low-set and high-set


• Non-volatile fault value recording
• Programmable relay outputs
• Complies with IEC 60255-26 standard
• ANSI : 50P, 51P

Technical
echnical Data
RATINGS ACCURACY INDICATORS
Rated current ( In ) : 5A Protection thresholds : ± 5% Auxiliary supply : Green indicator
Rated frequency : 50 or 60 Hz Time delay : ± 5% with a minimum Pick-up : Red indicator
Burden : < 0.3 VA at In of 50 ms Trip : 7-segment display
Thermal withstand : 4 x In continuous and red indicators

OUTPUT CONTACTS (R1 & R2)


AUXILIARY SUPPLY Rated voltage : 250 V AC / DC ENVIRONMENTAL CONDITIONS
Model MK234A-240A (6) : 198 ~ 265 V AC Contact rating : 5A Temperature : -5˚C to +55˚C
Model MK234A-110A (6) : 94 ~ 127 V AC Expected electrical life : 100,000 operations at Humidity : 56 days at 93% RH and 40˚C
Supply frequency : 50 or 60 Hz rated current non-condensing
VA rating : 3 VA typical Expected mechanical life : 5 x 106 operations

MECHANICAL
SETTING RANGES Mounting : Panel mounting
Low-set ( I > ) : 0.5 A to 6.0 A, step 0.05 A / 10% to 120%, step 1% Dimension (mm) : 96(w) x 96(h) x 110(d)
Low-set definite time ( t > ) : 0.05 to 99 sec, step 0.01 (0.05 to 1.0) / 0.1 (1.0 to 99) Enclosure protection : IP54 at the panel
High-set ( I >> ) : 0.5 A to 99.9 A or disable, step 0.10 A / 10% to 1998%, step 2% Approximate weight : 0.8 kg
High-set delay time ( t >> ) : 0.05 sec to 2.5 sec, step 0.01
MK 234A
Overcurrent Relay

Typical Application Diagram Case Dimensions


96 mm
Aux
L N MK 234A
NO NC COM COM NC NO

96 mm
1 2 3 4 5 6 7 8 Front

R1 R2

9 10 11 12 13 14 15 16 110 mm
100 mm

L1
L2 Side
LOAD

L3
N
91.0 ± 0.5 mm

91.0 ± 0.5 mm
Panel Cutout

Ordering Information
MODEL DESCRIPTION
MK234A - 240A For 50 Hz system, auxiliary supply 198 ~ 265 V AC
MK234A - 110A For 50 Hz system, auxiliary supply 94 ~ 127 V AC
MK234A - 240A6 For 60 Hz system, auxiliary supply 198 ~ 265 V AC
MK234A -110A6 For 60 Hz system, auxiliary supply 94 ~ 127 V AC
MK 234A
Overcurrent Relay
MK203A
Features
• Microprocessor based numerical relay
• Current measurement based on fundamental
frequency

• Low-set inverse definite minimum time ( IDMT )


relay

• High-set instantaneous relay


• Separate low-set and high-set trip indicators
• Option to disable high-set relay
• Front panel access to test function
• Complies with IEC 60255-26 standard
• ANSI Code : 50P, 51P

Technical
echnical Data
RATINGS OUTPUT CONTACTS ENVIRONMENTAL CONDITIONS
Rated current ( In ) : 5A Trip contact (R1) : Manual reset type Temperature : -5˚C to +55˚C
Rated frequency : 50 Hz Rated voltage : 250 V AC Humidity : 56 days at 93% RH and
Burden : < 0.3 VA at In Contact rating : 5A 40˚C non-condensing
Thermal withstand : 4 x In continuous Expected electrical life : 100,000 operations at
rated current
Expected mechanical life: 5 x 106 operations MECHANICAL
AUXILIARY SUPPLY Mounting : Panel mounting
Model MK203A-240A : 198 ~ 265 V AC Dimension (mm) : 96(w) x 96(h) x 110(d)
Model MK203A-110A : 94 ~ 127V AC INDICATORS Approximate weight : 0.8 kg
Supply frequency : 50 Hz Auxiliary supply : Green indicator
VA rating : 3 VA typical Pick-up : Red indicator
Trip : Red indicator

SETTING RANGES
Low-set ( I > ) : 2.0 A to 6.0 A ACCURACY
: 40% to 120% Protection thresholds : ± 5%
Time multiplier ( TM ) : 0.05 to 1.0 Time delay : ± 5% with a minimum
High-set ( I >> ) : I > to 10 x I > or disable of 50 ms
High-set delay time (t >>) : Instantaneous
MK 203A

TIME CURRENT CHARACTERISTIC CURVE


- Normal Inverse
Overcurrent Relay

Typical Application Diagram Combined IDMT Overcurrent & Earth Fault Relays
Aux AUX AUX
L N MK 203A L N MK 203A L N MK 202A
NO NC COM NO NC COM NO NC COM
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

R1 R1 R1
9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16

L1
L1
L2
LOAD

L2

LOAD
L3
L3
N
N

Normal Inverse Case Dimensions


96 mm
96 mm

Front

110 mm
100 mm

Side

91.0 ± 0.5 mm
91.0 ± 0.5 mm

Panel Cutout

Ordering Information
MK 203A

MODEL DESCRIPTION
MK203A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
MK203A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
Overcurrent Relay
MK204A
Features
• Microprocessor based numerical relay
• Current measurement based on fundamental
frequency

• Low-set inverse definite time relay (IDT)


• High-set instantaneous relay
• Separate low-set and high-set trip indicators
• Option to disable high-set relay
• Front panel access to test function
• Complies with IEC 60255-26 standard
• ANSI Code : 50P, 51P

Technical
echnical Data
RATINGS OUTPUT CONTACTS ENVIRONMENTAL CONDITIONS
Rated current ( In ) : 5A Trip contact (R1) : Manual reset type Temperature : -5˚C to +55˚C
Rated frequency : 50 Hz Rated voltage : 250 V AC Humidity : 56 days at 93% RH and
Burden : < 0.3 VA at In Contact rating : 5A 40˚C non-condensing
Thermal withstand : 4 x In continuous Expected electrical life : 100,000 operations at
rated current
Expected mechanical life: 5 x 106 operations MECHANICAL
AUXILIARY SUPPLY Mounting : Panel mounting
Model MK204A-240A : 198 ~ 265 V AC Dimension (mm) : 96(w) x 96(h) x 110(d)
Model MK204A-110A : 94 ~ 127V AC INDICATORS Approximate weight : 0.8 kg
Supply frequency : 50 Hz Auxiliary supply : Green indicator
VA rating : 3 VA typical Pick-up : Red indicator
Trip : Red indicator

SETTING RANGES ACCURACY


Low-set ( I > ) : 2.0 A to 6.0 A Protection thresholds : ± 5%
: 40% to 120% Time delay : ± 5% with a minimum
Time multiplier ( TM ) : 0.05 to 1.0 of 50 ms
High-set ( I >> ) : I > to 10 x I > or disable
MK 204A

High-set delay time (t >>) : Instantaneous


Overcurrent Relay

Typical Application Diagram Combined IDMT Overcurrent & Earth Fault Relays
Aux AUX AUX
L N MK 204A L N MK 204A L N MK 201A
NO NC COM NO NC COM NO NC COM
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

R1 R1 R1
9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16

L1
L1
L2
LOAD

L2

LOAD
L3
L3
N
N

Inverse Definite Time Case Dimensions


96 mm

t/s
96 mm

Front

10
110 mm
100 mm

k
1.0
0.9 Side
0.8
0.7
1 0.6
0.5
0.4
0.3
91.0 ± 0.5 mm
0.2
91.0 ± 0.5 mm

0.1
Panel Cutout
0.1
1 10 20 I/I>

Ordering Information
MK 204A

MODEL DESCRIPTION
MK204A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
MK204A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
Earth Fault Relay
MK231A
Features

• Microprocessor based numerical relay


• Current measurement based on fundamental
frequency

• Low-set earth-fault
• High-set earth-fault
• Local display of measured and set values
• Definite time for low-set and high-set
• Non-volatile fault value recording
• Programmable relay outputs
• Complies with IEC 60255-26 standard

• ANSI Code : 50N, 51N

Technical Data
RATINGS ACCURACY INDICATORS
Rated current ( In ) : 5A Protection thresholds : ± 5% Auxiliary supply : Green indicator
Rated frequency : 50 or 60 Hz Time delay : ± 5% with a minimum Pick-up : Red indicator
Burden : < 0.3 VA at In of 50 ms Trip : 7-segment display
Thermal withstand : 4 x In continuous and red indicators

AUXILIARY SUPPLY OUTPUT CONTACTS


Model MK231A-240A (6) : 198 ~ 265 V AC Rated voltage : 250 V AC / DC ENVIRONMENTAL CONDITIONS
Model MK231A-110A (6) : 94 ~ 127 V AC Contact rating : 5A Temperature : -5˚C to +55˚C
Supply frequency : 50 or 60 Hz Expected electrical life : 100,000 operations at Humidity : 56 days at 93% RH and 40˚C
VA rating : 3 VA typical rated current non-condensing
Expected mechanical life : 5 x 106 operations

SETTING RANGES MECHANICAL


Low-set ( I > ) : 0.1 A to 5.0 A, step 0.05 A / 2% to 100%, step 1% Mounting : Panel mounting
Low-set definite time ( t > ) : 0.05 to 99 sec, step 0.01 (0.05 to 1.0) / 0.1 (1.0 to 99) Dimension (mm) : 96(w) x 96(h) x 110(d)
High-set ( I >> ) : 0.1 A to 50 A or disable, step 0.1 A / 2% to 1000%, step 2% Enclosure protection : IP54 at the panel
High-set delay time ( t >> ) : 0.05 sec to 2.5 sec, step 0.01 Approximate weight : 0.7 kg
MK 231A
Earth Fault Relay

Typical Application Diagram 1 Typical Application Diagram 2


Aux Aux
L N MK 231A L N MK 231A
NO NC COM COM NC NO NO NC COM COM NC NO
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

R1 R2 R1 R2

9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16

L1 L1
L2 L2
LOAD

L3 L3
N
N
Core Balance
Current Transformer

Case Dimensions Ordering Information


96 mm
MODEL DESCRIPTION
MK231A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
MK231A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
96 mm

Front MK231A - 240A6 For 60 Hz system, auxiliary voltage 198 ~ 265 V AC


MK231A -110A6 For 60 Hz system, auxiliary voltage 94 ~ 127 V AC

110 mm
100 mm

Side

91.0 ± 0.5 mm
91.0 ± 0.5 mm

Panel Cutout
MK 231A
Earth Fault Relay
MK232A
Features
• Microprocessor based numerical relay
• Current measurement based on fundamental
frequency
• Low-set earth-fault
• High-set earth-fault
• Local display of measured and set values
• Definite time for low-set and high-set
• Non-volatile fault value recording
• Programmable relay outputs
• Five selectable IDMT characteristic curves
• Complies with IEC 60255-26 standard
• ANSI Code : 50N, 51N

Technical Data
RATINGS ACCURACY INDICATORS
Rated current ( In ) : 5A Protection thresholds : ± 5% Auxiliary supply : Green indicator
Rated frequency : 50 or 60 Hz Time delay : ± 5% with a minimum Pick-up : Red indicator
Burden : < 0.3 VA at In of 50 ms Trip : 7-segment display
Thermal withstand : 4 x In continuous and red indicators

OUTPUT CONTACTS
AUXILIARY SUPPLY Rated voltage : 250 V AC / DC ENVIRONMENTAL CONDITIONS
Model MK232A-240A (6) : 198 ~ 265 V AC Contact rating : 5A Temperature : -5˚C to +55˚C
Model MK232A-110A (6) : 94 ~ 127 V AC Expected electrical life : 100,000 operations at Humidity : 56 days at 93% RH and 40˚C
Supply frequency : 50 or 60 Hz rated current non-condensing
VA rating : 3 VA typical Expected mechanical life : 5 x 106 operations

MECHANICAL
SETTING RANGES Mounting : Panel mounting
Low-set ( I > ) : 0.1 A to 5.0 A, step 0.05 A / 2% to 100%, step 1% Dimension (mm) : 96(w) x 96(h) x 110(d)
Low-set time multiplier ( kt > ) : 0.05 to 1.0, step 0.01 Enclosure protection : IP54 at the panel
Low-set definite time (t >) : 0.05 to 99 sec, step 0.01 (0.05 to 1.0) / 0.1 (1.0 to 99) Approximate weight : 0.7 kg
High-set ( I >> ) : 0.1 A to 50 A or disable, step 0.1 A / 2% to 1000%, step 2%
High-set delay time ( t >> ) : 0.05 sec to 2.5 sec, step 0.01

Typical Application Diagram 1 Typical Application Diagram 2


Aux Aux
L N MK 232A L N MK 232A
NO NC COM COM NC NO NO NC COM COM NC NO
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
MK 232A

R1 R2 R1 R2

9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16

L1 L1
L2 L2
LOAD

L3
L3
N
N
Core Balance
Current Transformer
Earth Fault Relay

Normal Inverse Very Inverse Long Time Inverse

Extremely Inverse Normal Inverse 1.3/10 Case Dimensions


96 mm
96 mm

Front

110 mm
100 mm

Side

91.0 ± 0.5 mm
91.0 ± 0.5 mm

Panel Cutout

Ordering Information
MODEL DESCRIPTION
MK 232A

MK232A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC


MK232A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
MK232A - 240A6 For 60 Hz system, auxiliary voltage 198 ~ 265 V AC
MK232A -110A6 For 60 Hz system, auxiliary voltage 94 ~ 127 V AC
Earth Fault Relay
MK201A
Features

• Microprocessor based numerical relay


• Current measurement based on fundamental
frequency

• Low-set definite time relay


• High-set instantaneous relay
• Separate low-set and high-set indicators
• Option to disable the high-set relay
• Front panel access to the test function
• Complies with IEC 60255-26 standard

• ANSI Code : 50N, 51N

Technical Data
RATINGS ACCURACY INDICATORS
Rated current ( In ) : 5A Protection thresholds : ± 5% Auxiliary supply : Green indicator
Rated frequency : 50 Hz Time delay : ± 5% with a minimum Pick-up : Red indicator
Burden : < 0.3 VA at In of 50 ms Trip : Red indicator
Thermal withstand : 4 x In continuous

OUTPUT CONTACTS ENVIRONMENTAL CONDITIONS


AUXILIARY SUPPLY Trip contact (R1) : Manual reset type Temperature : -5˚C to +55˚C
Model MK201A-240A : 198 ~ 265 V AC Rated voltage : 250 V AC Humidity : 56 days at 93% RH and 40˚C
Model MK201A-110A : 94 ~ 127 V AC Contact rating : 5A non-condensing
Supply frequency : 50 Hz Expected electrical life : 100,000 operations at
VA rating : 3 VA typical rated current
Expected mechanical life : 5 x 106 operations MECHANICAL
Mounting : Panel mounting
SETTING RANGES Dimension (mm) : 96(w) x 96(h) x 90(d)
Low-set ( I > ) : 0.1 A to 2.0 A Approximate weight : 0.6 kg
: 2% to 40%
Low-set delay time(DELAY): 0.05 sec to 1.0 sec
High-set ( I >> ) : I > to 10 x I > or disable
High-set delay time ( t >> ) : Instantaneous
MK 201A
Earth Fault Relay

Typical Application Diagram Combined IDMT Overcurrent & Earth Fault Relays
Aux AUX AUX
L N MK 201A L N MK 204A L N MK 201A
NO NC COM NO NC COM NO NC COM
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

R1 R1 R1
9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16

L1
L1
L2
LOAD

L2

LOAD
L3
L3
N
N

Case Dimensions
90 mm
96 mm 70 mm 91.0 ± 0.5 mm
91.0 ± 0.5 mm
96 mm

Front Side Panel Cutout

Ordering Information
MODEL DESCRIPTION
MK201A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
MK201A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
MK 201A
Earth Fault Relay
MK202A
Features

• Microprocessor based numerical relay


• Current measurement based on fundamental
frequency

• Low-set inverse definite minimum time ( IDMT )


relay

• High-set instantaneous relay


• Separate low-set and high-set trip indicators
• Option to disable high-set element
• Front panel access to test function
• Complies with IEC 60255-26 standard

• ANSI Code : 50N, 51N

Technical Data
RATINGS ACCURACY INDICATORS
Rated current ( In ) : 5A Protection thresholds : ± 5% Auxiliary supply : Green indicator
Rated frequency : 50 Hz Time delay : ± 5% with a minimum Pick-up : Red indicator
Burden : < 0.3 VA at In of 50 ms Trip : Red indicator
Thermal withstand : 4 x In continuous

OUTPUT CONTACTS ENVIRONMENTAL CONDITIONS


AUXILIARY SUPPLY Trip contact (R1) : Manual reset type Temperature : -5˚C to +55˚C
Model MK202A-240A : 198 ~ 265 V AC Rated voltage : 250 V AC Humidity : 56 days at 93% RH and 40˚C
Model MK202A-110A : 94 ~ 127V AC Contact rating : 5A non-condensing
Supply frequency : 50 Hz Expected electrical life : 100,000 operations at
VA rating : 3 VA typical rated current
Expected mechanical life : 5 x 106 operations MECHANICAL
Mounting : Panel mounting
SETTING RANGES Dimension (mm) : 96(w) x 96(h) x 90(d)
Low-set ( I > ) : 0.1A to 2.0 A TIME CURRENT CHARACTERISTIC CURVE Approximate weight : 0.6 kg
: 2% to 40% - Normal Inverse
Time multiplier ( TM ) : 0.05 to 1.0
High-set ( I >> ) : I > to 10 x I > or disable
High-set delay time (t >>) : Instantaneous
MK 202A
Earth Fault Relay

Typical Application Diagram Combined IDMT Overcurrent & Earth Fault Relays
Aux AUX AUX
L N MK 202A L N MK 203A L N MK 202A
NO NC COM NO NC COM NO NC COM
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

R1 R1 R1
9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16

L1
L1
L2
LOAD

L2

LOAD
L3
L3
N
N

Normal Inverse Case Dimensions


96 mm
96 mm

Front

90 mm
70 mm

Side

91.0 ± 0.5 mm
91.0 ± 0.5 mm

Panel Cutout

Ordering Information
MK 202A

MODEL DESCRIPTION
MK202A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
MK202A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
Earth Leakage Relay
MK300A
MK300EA
Features for MK 300A / 300EA
• Numerical earth leakage relay
• Programmable current sensitivity and time delay
MK 300A
• Detection of no connection to ZCT
• Relay trip indicator
• Relay alarm indicator
• Real-time leakage current display
• 50% pre-fault indicator
• Leakage fault current recording
• Standard DIN 96x96mm panel mounting
• Protected against nuisance tripping

Features for MK 300EA only


• Positive safety output contact
MK 300EA
• Pre-fault alarm contact
• Remote reset function

Technical Data
AUXILIARY SUPPLY INPUT INDICATORS
Model MK300A / 300EA -230A : 184 ~ 276 V AC Remote Reset : N.O. dry contact * Pre-fault alarm : Red indicator
Model MK300A / 300EA -110A : 94 ~ 127 V AC (Normal blink)
Rated frequency : 50 Hz Time delay : Red indicator
VA rating : 3 VA typical OUTPUTS (Fast blink)
Trip contact : Activated during leakage Leakage trip : 7-segment display
trip, manual test trip or and red indicator
SETTING ZCT connection error ZCT connection error : 7-segment display
Sensitivity adjustment : 30mA, 50mA, Positive safety contact*: Activated when power- and red indicator
0.10~1.00A(Step=50mA) up and relay function Real-time leakage current : 7-segment display
MK 300A / 300EA

1.00~10.0A (Step=1.00A) correctly


Time delay adjustment : Instantaneous, Alarm contact* : Activated when
0.1~3.0sec (Step=0.1s) measured leakage ZERO - PHASE CURRENT TRANSFORMER
current exceeded 50% To operate with Mikro’s ZCT series of current
of IΔn. transformer
PERFORMANCE
Setting accuracy : -15% to +0%
Timing accuracy : ±5% OUTPUT CONTACTS MECHANICAL
Rated voltage : 250 V AC Mounting : Panel mounting
Contact rating : 5 A (NO) Dimension (mm) : 96(w) x 96(h) x 90(d)
RECORD 3 A (NC) Enclosure protection : IP54 at the panel
Fault record : 3 latest tripped fault Expected electrical life : 100,000 operations at Approximate weight : 0.4 kg (excluding ZCT)
currents or “tSt” for rated current
manual test trip Expected mechanical life : 5 x 106 operations
Storage : Non-volatile memory
Earth Leakage Relay

Typical Application Diagram For MK300A Case Dimensions


AUX L1 L2 L3 N PE 96 mm
N L
MIKRO
ZCT
The EARTH wire
MK300A

96 mm
SHUNT must not pass
1 2 3 4 5 6 7 8
TRIP through the ZCT Front
TRIP
CONTACT

NC NO COM

9 10 11 12 13 14 15 16
90 mm
70 mm
LOAD

Side

Typical Application Diagram For MK300EA


91.0 ± 0.5 mm
AUX REMOTE L1 L2 L3 N PE
N L RESET MIKRO
ZCT

91.0 ± 0.5 mm
The EARTH wire
MK300EA
must not pass Panel Cutout
1 2 3 4 5 6 7 8 CONTACTOR through the ZCT
TRIP ALARM POSITIVE SAFETY
CONTACT CONTACT CONTACT

NC NO COM NO COM NC NO COM

9 10 11 12 13 14 15 16

LOAD

Ordering Information

MODEL DESCRIPTION
MK300A - 240AD For 50Hz system, auxiliary voltage 85~265VAC or 110~340VDC
MK300EA - 240AD For 50Hz system, auxiliary voltage 85~265VAC or 110~340VDC
MK300A - 230A For 50Hz system, auxiliary voltage 184~276VAC
MK300EA - 230A For 50Hz system, auxiliary voltage 184~276VAC
MK300A - 110A For 50Hz system, auxiliary voltage 94~127VAC
MK300EA - 110A For 50Hz system, auxiliary voltage 94~127VAC
MK300A - 240AD6 For 60Hz system, auxiliary voltage 85~265VAC or 110~340VDC
MK 300A / 300EA

MK300EA - 240AD6 For 60Hz system, auxiliary voltage 85~265VAC or 110~340VDC


MK300A - 230A6 For 60Hz system, auxiliary voltage 184~276VAC
MK300EA - 230A6 For 60Hz system, auxiliary voltage 184~276VAC
MK300A - 110A6 For 60Hz system, auxiliary voltage 94~127VAC
MK300EA - 110A6 For 60Hz system, auxiliary voltage 94~127VAC
Earth Leakage Relay
MK330A
Features
• Numerical auto-reclosing earth leakage relay

• Incorporated positive safety feature into trip


contact

• One programmable contact for flexibility

• Detection of no connection to ZCT

• Relay trip / alarm indicator

• Real-time leakage current display

• Leakage fault current recording

• Remote reset function

• Standard DIN 96 x 96mm panel mounting

• Protected against nuisance tripping

Technical Data
AUXILIARY SUPPLY Programmable contact: Option 0 = Disable OUTPUT CONTACTS
Model MK330A-230A : 184~276VAC Option 1 =All (Option Rated voltage : 250 V AC
Model MK330A-110A : 94~127VAC 2 to 6) Contact rating : 5 A (NO)
Rated frequency : 50Hz Option 2 =ZCT error 3 A (NC)
VA rating : 3VA typical Option 3 = Leakage trip, Expected electrical life : 100,000 operations at
test trip, rated current
PERFORMANCE re-close lockout Expected mechanical life : 5 x 106 operations
Setting accuracy : -15% to +0% Option 4 =Re-close
Timing accuracy : ±5% lockout
Option 5 = Pre-fault alarm, INDICATORS
SETTING leakage trip, Pre-fault alarm : Red indicator (Normal
Sensitivity adjustment : 30mA, 50mA, test trip, blink)
0.10~1.00A re-close lockout Time delay : Red indicator (Fast blink)
(Step=50mA) Option 6 =Re-close Leakage trip : 7-segment display and
1.00~10.0A lockout, red indicator
(Step=1.00A) ZCT error Re-close lockout : 7-segment display and
red indicator
Time delay adjustment: Instantaneous, RECORD ZCT connection error : 7-segment display and
0.1~3.0sec (Step=0.1s) Fault record : 3 latest tripped fault red indicator
currents or “tSt” for Real-time leakage current : 7-segment display
Number of shots : 0~30 (Step=1, 0=Disable manual test trip
auto re-close function) Storage : Non-volatile memory
ZERO-PHASE CURRENT TRANSFORMER
Dead time : 1~500sec (Step=1sec) INPUT To operate with Mikro’s ZCT series of current
Remote reset : N.O. dry contact transformer
MK 330A

Persistent fault time : 0~500sec (Step=1sec,


0=Disable function) OUTPUTS
Reclaim time : 0~500min (Step=1min, Trip safe contact : Activated when the relay MECHANICAL
0=Disable function) is in normal power-up Mounting : Panel mounting
condition with the Dimension (mm) : 96(w) x 96(h) x 90(d)
Lockout auto reset time: 0~200hour (Step=1Hr, measured leakage current Enclosure protection : IP54 at the panel
0=Disable function) less than 0.85 IΔn. Approximate weight : 0.6 kg (excluding ZCT)
Programmable contact: Activated according to
user setting
Earth Leakage Relay

Typical Application Diagram Case Dimensions


96 mm
AUX REMOTE L1 L2 L3 N PE
N L RESET MIKRO
ZCT

96 mm
The EARTH wire
MK330A Front
must not pass
1 2 3 4 5 6 7 8 CONTACTOR through the ZCT
TRIP SAFE PROGRAMMABLE
CONTACT* CONTACT

NC NO COM NC NO COM

9 10 11 12 13 14 15 16
90 mm
70 mm
LOAD

* The trip safe contact is activated (terminal 10-11 closed) when Side
the relay is in normal power-up condition with the measured
leakage current less than 0.85 IΔn.

91.0 ± 0.5 mm

91.0 ± 0.5 mm
Panel Cutout
Ordering Information

MODEL DESCRIPTION
MK330A-230A For 50Hz system, auxiliary voltage 184~276VAC
MK330A-110A For 50Hz system, auxiliary voltage 94~127VAC
MK330A-230A6 For 60Hz system, auxiliary voltage 184~276VAC
MK330A-110A6 For 60Hz system, auxiliary voltage 94~127VAC
MK 330A
Earth Leakage Relay
MK302A
MK301A
MK 301E MK301E
Features
• Trip starting indicator
• Detection of no connection to current transformer
for extra safety
MK 301A
• Relay tripped indicator
• High immunity to electrical interference

Features for MK 302A only


• Safety output contact
• Earth leakage level indicators
• Remote reset and remote test functions
MK 302A

Technical Data
AUXILIARY SUPPLY OUTPUT CONTACTS ZERO - PHASE CURRENT TRANSFORMER
Model MK301A / 302A -240A : 198 ~ 265 V AC Contact arrangement : 1 x manual reset type To operate with Mikro’s ZCT series of current
Model MK301A / 302A -110A : 94 ~ 127 V AC : 1 x safety contact* transformer
Rated frequency : 50 / 60 Hz : NC and NO contacts
MK 302A / 301A / 301E
VA rating : 3 VA typical available ENVIRONMENTAL CONDITIONS
Rated voltage : 250 V AC Temperature : -5˚C to +55˚C
Contact rating : 5A Humidity : 56 days at 93% RH and
SETTING RANGES Expected electrical life : 100,000 operations at 40˚C non-condensing
Sensitivity adjustment : 0.03 A to 30 A rated current
Delay time adjustment: 0 sec to 3.0 sec Expected mechanical life : 5 x 106 operations MECHANICAL
Mounting : Panel mounting
INPUTS Dimension (mm) : 96(w) x 96(h) x 90(d)
PERFORMANCE Remote Test* / Reset Inputs* : N.O. dry contact Approximate weight : 0.6 kg (excluding ZCT)
Setting accuracy : -15% to +0%
Timing accuracy : ±5% INDICATORS * Applicable to MK302A series only
Auxiliary supply : Green indicator ** Applicable to MK301E series only
Time delay : Red indicator
Trip : Red indicator
Real-time leakage current : Red indicator
Earth Leakage Relay

Typical Application Diagram Case Dimensions


AUX 96 mm
L N

LOAD PE

96 mm
NO NC COM Front
1 2 3 4 5 6 7 8 The EARTH wire
must not pass
through the ZCT
SHUNT
TRIP CONTACT TRIP
9 10 11 12 13 14 15 16 90 mm
70 mm

MK301A or MK302A

Side
N
L3
L2
L1

AUX
L N
91.0 ± 0.5 mm
LOAD PE

NO NC COM COM NC NO

91.0 ± 0.5 mm
1 2 3 4 5 6 7 8 The EARTH wire
must not pass
through the ZCT Panel Cutout
TRIP CONTACT SAFETY CONTACT*

9 10 11 12 13 14 15 16
CONTACTOR
MK302A
REMOTE
TEST*

REMOTE RESET*
N
L3
L2
L1

AUX
L N

LOAD PE

NO NC C OM COM NC NO
1 2 3 4 5 6 7 8 The EARTH wire
must not pass
through the ZCT
SHUNT
TRIP CONTACT TRIP CONTACT 2** TRIP
9 10 11 12 13 14 15 16

MK301E
MK 302A / 301A / 301E

N
L3
L2
L1

Ordering Information
MODEL DESCRIPTION
MK301A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
MK301A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
MK302A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
MK302A -110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
MK301E - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
MK301E -110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
MK301A - 240A6 For 60 Hz system, auxiliary voltage 198 ~ 265 V AC
MK301A - 110A6 For 60 Hz system, auxiliary voltage 94 ~ 127 V AC
MK302A - 240A6 For 60 Hz system, auxiliary voltage 198 ~ 265 V AC
MK302A -110A6 For 60 Hz system, auxiliary voltage 94 ~ 127 V AC
MK301E - 240A6 For 60 Hz system, auxiliary voltage 198 ~ 265 V AC
MK301E -110A6 For 60 Hz system, auxiliary voltage 94 ~ 127 V AC
Earth Leakage Relay
DIN330
Features
• Numerical auto-reclosing earth leakage relay

• Incorporated positive safety feature into trip


contact

• Detection of no connection to ZCT

• Relay trip / alarm indicator

• Real-time leakage current display

• Leakage fault current recording

• Remote reset function

• Standard 35mm DIN rail mounting

• Protected against nuisance tripping

Technical Data
AUXILIARY SUPPLY Programmable contact : Option 0 = Disable OUTPUT CONTACTS
Model DIN330-230 A(6) : 184 ~ 276 V AC Option 1 = All (Option Rated voltage : 250 V AC
Rated frequency : 50 or 60 Hz 2 to 6) Contact rating : 5 A (NO)
VA rating : 3 VA typical Option 2 = ZCT error 3 A (NC)
Option 3 = Leakage trip, Expected electrical life : 100,000 operations at
PERFORMANCE test trip, rated current
Setting accuracy : -15% to +0% re-close lockout Expected mechanical life : 5 x 106 operations
Timing accuracy : ±5% Option 4 = Re-close
lockout
SETTING Option 5 = Pre-fault alarm, INDICATORS
Sensitivity adjustment : 30 mA, 50 mA, leakage trip, 50% pre-fault alarm : Red indicator (Normal
0.10 A –1.00 A test trip, blink)
(Step = 50 mA), reclose lockout Time delay : Red indicator (Fast blink)
1.00 A – 10.0 A Option 6 =Re-close Leakage trip : 7-segment display and
(Step = 1.00 A) lockout, red indicator
Time delay adjustment: Instantaneous, ZCT error Reclose lockout : 7-segment display and
0.1s – 3.0s red indicator
Step = 0.10 sec. RECORD ZCT fault : 7-segment display and
Fault record : 3 latest tripped fault red indicator
Number of shots : 0 - 30. Step = 1. currents or “tSt” for Real time leakage current : 7-segment display
0 = Disable auto reclose manual test trip
function Storage : Non-volatile memory
Dead time : 1 - 500 sec. Step = 1 sec. To operate with Mikro’s ZCT series of current
INPUT transformer
Permanent fault time : 0 - 500 sec. Step = 1 sec. Remote reset : N.O. dry contact
0 = Disable function ENVIRONMENTAL CONDITIONS
Temperature : -5˚C to +55˚C
Reclaim time : 0 - 500 minute
DIN 330

OUTPUTS Humidity : 56 days at 93% RH and


Step = 1 min Trip safe contact : Activated when the relay 40˚C non-condensing
0 = Disable function is in normal power-up
condition with the MECHANICAL
Lockout auto reset time: 0 - 200 hour measured leakage current Mounting : Panel mounting
Step = 1 Hrs less than 0.85 IΔn. Dimension (mm) : 71(w) x 85(h) x 70(d)
0 = Disable function Programmable contact: Activated according to Approximate weight : 0.4 kg (excluding ZCT)
user setting
Earth Leakage Relay

Typical Application Diagram Case Dimensions


AUX

L1
L2
L3
PE

N
71 mm
L N REMOTE
RESET MIKRO
ZCT
The EARTH wire
must not pass 20 mm
through the ZCT
DIN330

45 mm
1 2 3 4 5 6 7 CONTACTOR
Front
TRIP SAFE CONTACT PROGRAMMABLE CONTACT

8 9 10 11 12 13 14 20 mm
COM NO NC COM NO NC

LOAD

70 mm
* The trip safe contact is activated (terminal 9-10 closed) when
the relay is in normal power-up condition with the measured
leakage current less than 0.85 IDn.

85 mm
Side

30 mm 20 mm 20 mm

Ordering Information

MODEL DESCRIPTION
DIN330 - 230 A For 50 Hz system, auxiliary voltage 230 V AC
DIN330 - 230 A6 For 60 Hz system, auxiliary voltage 230 V AC
DIN330
Earth Leakage Relay
DIN310
DIN310E
Features
• Numerical earth leakage relay

• Programmable current sensitivity and time delay

• Detection of no connection to ZCT

• Relay trip indicator

• Relay alarm indicator

• Real-time leakage current display

Features For DIN 310E only • Leakage fault current recording

• Positive safety output contact • 50% pre-fault indicator

• 50% pre-fault output contact • Standard DIN rail mounting

• Remote reset function • Protection against nuisance tripping

Technical Data
AUXILIARY SUPPLY RECORD
DIN310-230 A(6) : 184 ~ 276 V AC Fault record : 3 latest tripped fault To operate with Mikro’s ZCT series of current
DIN310E-230 A(6) : 184 ~ 276 V AC currents or “tSt” for transformer
Rated frequency : 50 or 60 Hz manual test trip
VA rating : 3 VA typical Storage : Non-volatile memory
ENVIRONMENTAL CONDITIONS
PERFORMANCE Temperature : -5˚C to +55˚C
Setting accuracy : -15% to +0% INPUT Humidity : 56 days at 93% RH and
Timing accuracy : ±5% Remote reset* : N.O. dry contact 40˚C non-condensing

SETTING
Sensitivity adjustment : 30mA, 50mA, OUTPUTS MECHANICAL
0.10~1.00A Trip Contact : Activated if relay tripped Mounting : Panel mounting
(Step=50mA) or ZCT fault Dimension (mm) : 71(w) x 85(h) x 70(d)
1.00~10.0A Positive safety contact* : Activated when ZCT is Approximate weight : 0.4 kg (excluding ZCT)
(Step=1.00A) connected properly to
the relay * Applicable to DIN310E series only
Time delay adjustment: Instantaneous, Pre-fault alarm contact*: Activated when leakage
0.1~3.0sec current exceeded 50% of
DIN 310 / 310E

Step=0.10 sec sensitivity setting

OUTPUT CONTACTS INDICATORS


Rated voltage : 250 V AC 50% pre-fault alarm : Red indicator
Contact rating : 5 A (NO) Time delay : Red indicator
3 A (NC) Leakage trip : 7-segment display and red
Expected electrical life : 100,000 operations at indicator
rated current ZCT fault : 7-segment display and red
Expected mechanical life : 5 x 106 operations indicator
Real time leakage current: 7-segment display
Earth Leakage Relay

Typical Application Diagram For DIN 310 Case Dimensions


AUX

L1
L2
L3
PE

N
L N
71 mm
MIKRO
ZCT
The EARTH wire
must not pass 20 mm
through the ZCT
DIN310

1 2 3 4 5 6 7 SHUNT

45 mm
TRIP
Front
TRIP
CONTACT

8 9 10 11 12 13 14
20 mm
COM NO NC
LOAD

70 mm

Typical Application Diagram For DIN 310E


AUX
L1
L2
L3

85 mm
PE
N

L N REMOTE Side
RESET MIKRO
ZCT
The EARTH wire
must not pass
through the ZCT
DIN310E

1 2 3 4 5 6 7 CONTACTOR

ALARM CONTACT TRIP CONTACT SAFETY CONTACT 30 mm 20 mm 20 mm

8 9 10 11 12 13 14
COM NO NC COM NO NC

LOAD

Ordering Information

MODEL DESCRIPTION
DIN310 - 230 A For 50 Hz system, auxiliary voltage 230 V AC
DIN310E - 230 A For 50 Hz system, auxiliary voltage 230 V AC
DIN310 - 230 A6 For 60 Hz system, auxiliary voltage 230 V AC
DIN310E - 230 A6 For 60 Hz system, auxiliary voltage 230 V AC

* 60Hz system, auxiliary voltage 110V AC model available upon special request.
DIN 310 / 310E
Earth Leakage Relay
DIN300
DIN300E
Features
• 25 selectable sensitivity settings:
30 mA to 30 A

• 9 selectable time delays: 0ms to 3s

• Earth leakage level indicators

• Detection of no connection to ZCT

Features For DIN 300E only • Relay tripped indicator

• 50% pre-fault output contact • Trip starting indicator

• Remote test and remote reset functions • Protected against nuisance tripping

Technical Data
AUXILIARY SUPPLY OUTPUT CONTACTS ENVIRONMENTAL CONDITIONS
Model DIN300 / 300E -240A : 198 ~ 265 V AC Contacts ( Trip / 50% pre-fault* ) Temperature : -5˚C to +55˚C
Model DIN300 / 300E -110A : 94 ~ 127 V AC Rated voltage : 250 V AC Humidity : 56 days at 93% RH and
Rated frequency : 50 / 60 Hz Contact rating : 5A
VA rating : 3 VA typical Expected electrical life : 100,000 operations at 40˚C non-condensing
rated current
Expected mechanical life : 5 x 106 operations
SETTING RANGES MECHANICAL
Sensitivity setting : 30 mA, 50 mA, 75 mA, Mounting : DIN rail mounting
100 mA, 125 mA, 150 mA, INPUT Dimension (mm) : 71(w) x 85(h) x 70(d)
200 mA, 250 mA, 300 mA, Remote test* / Reset inputs* : N.O. dry contacts Approximate weight : 0.4 kg (excluding ZCT)
500 mA, 750 mA, 1 A,
1.25 A, 1.5 A, 2 A, 2.5 A,
3 A, 5 A, 7.5 A, 10 A, 12.5 A, * Applicable to DIN300E model only
15 A, 20 A, 25 A, 30 A. To operate with Mikro’s ZCT series of current
transformer
Time delay setting : Instantaneous, 50 ms,
DIN 300 / 300E

100 ms, 150 ms, 250 ms,


350 ms, 500 ms, 1 s, 3 s. INDICATORS
Auxiliary supply : Green indicator
PERFORMANCE Time delay : Red indicator
Setting accuracy : -15% to +0% Trip : Red indicator
Timing accuracy : ±5% Leakage current* : 5 red indicators for
leakage levels
Earth Leakage Relay

Typical Application Diagram For DIN 300 Case Dimensions

L1
L2
L3
PE

N
AUX 71mm
L N
S1
The EARTH wire 20mm
must not pass
S2 through the ZCT

1 2 3 4 5 6 7

45mm
SHUNT
TRIP
TRIP CONTACT

20mm
8 9 10 11 12 13 14
COM NO NC
Front view
LOAD

71mm

Typical Application Diagram For DIN 300E


L1
L2
L3

PE
N

AUX
REMOTE RESET

REMOTE TEST

85mm
L N Side view
S1
The EARTH wire
must not pass
S2 through the ZCT

1 2 3 4 5 6 7 SHUNT
TRIP
50% PRE-FAULT CONTACT TRIP CONTACT 30mm 20mm 20mm

8 9 10 11 12 13 14
COM NO NC COM NO NC

LOAD

Ordering Information

MODEL DESCRIPTION
DIN300 - 240A For 50 Hz system, auxiliary voltage 240 V AC
DIN300 - 110A For 50 Hz system, auxiliary voltage 110 V AC
DIN300E - 240A For 50 Hz system, auxiliary voltage 240 V AC
DIN300E - 110A For 50 Hz system, auxiliary voltage 110 V AC
DIN300 - 240A6 For 60 Hz system, auxiliary voltage 240 V AC
DIN300 - 110A6 For 60 Hz system, auxiliary voltage 110 V AC
DIN300E - 240A6 For 60 Hz system, auxiliary voltage 240 V AC
DIN300E - 110A6 For 60 Hz system, auxiliary voltage 110 V AC
DIN 300 / 300E
Earth Leakage Relay
ZCT40S
40S

ZCT60S
ZCT80S
ZCT120S
ZCT210S
80S
60S

Case Dimensions
Front

A C

120S 210S E
G

ZCT 40S / 60S / 80S / 120S / 210S


Calculation to determine Inner Diameter of ZCT required
Bottom

DIMENSION
d3 d4 (mm) ZCT Model
D D
40S 60S 80S 120S 210S
A 40 60 80 120 210
B 89 105 130 180 310
C 94 110 135 195 311
3 wire 4 wire
D 6 6 6 6 6
E 37 37 37 37 37
D d3, 3 wire d4, 4 wire
F 75 87 112 159 292
MODEL ZCT inner Up till wire Up till wire
G 27 27 27 27 18
diameter (mm) diameter (mm) diameter (mm)
ZCT 40S 40 14 12
ZCT 60S 60 23 21
ZCT 80S 80 32 29 Ordering Information
ZCT 120S 120 51 46
MODEL DESCRIPTION WEIGHT
ZCT 210S 210 93 83
ZCT40S 40mm inner diameter 0.16 kg
Example: ZCT60S 60mm inner diameter 0.20 kg
For a single core CU / PVC insulated, non-sheathed 450 / 750 V 50mm2 conductor, ZCT80S 80mm inner diameter 0.28 kg
it’s nominal overall diameter is 11.7mm. To pass 4 wires through the ZCT, we can use ZCT120S 120mm inner diameter 0.57 kg
ZCT40S as the maximum diameter it can support is up till 12mm.
ZCT210S 210mm inner diameter 1.5 kg
Digital Power Meter

DVM
Features
• Built-in selector switch

• Easy-to-read, 14.2mm digit display

• DIN size casing

Technical Data
Auxiliary supply : 198 ~ 265 V AC
: 94 ~ 127 V AC
VA rating : 3 VA
Input frequency : 47 ~ 66 Hz
Maximum input voltage : 500 Vrms
Approximate weight : 0.6 kg

Typical
Typ
Typical App
Application
pplic Diagram
DVM360
DVM3
V Series DVM100 Series
L1 L
L2 N
L3
N 1 2 3 4 5 6

1 2 3 4 5 6 7 8 9 10 11 12

7 8 9 10 11 12 Aux Supply
AC 240 V

Aux Supply
AC 240 V

Case Dimensions
91.5 mm
96 mm 91.0 ± 0.5 mm
87 mm
91.0 ± 0.5 mm
96 mm

Front Side Panel Cutout

Ordering Information
DVM

MODEL DESCRIPTION
DVM360 - 240A Auxiliary voltage 240 V AC
DVM100 - 240A Auxiliary voltage 240 V AC
DVM360 - 110A Auxiliary voltage 110 V AC
DVM100 - 110A Auxiliary voltage 110 V AC
Digital Power Meter
DAM
Features
• Built-in selector switch

• Easy-to-read, 14.2mm digit display

• DIN size casing

• Wide selection of current transformer


(CT) ratio

Technical Data
Auxiliary supply : 198 ~ 265 V AC
: 94 ~ 127 V AC
VA rating : 3 VA
Input frequency : 47 ~ 66 Hz
Maximum input : 6 A continuous
Ammeter CT ratio : .../5 A
Class : 1.0
Approximate weight : 0.7 kg

Typical
Typ
Typical Ap
Application
p Diagram
DAM330 / 3000 Series DAM100 / 1000 Series

L1 L
L2 N
L3
1 2 3 4 5 6
1 2 3 4 5 6
7 8 9 10 11 12
7 8 9 10 11 12
Aux Supply
AC 240 V
Aux Supply
AC 240 V

Case Dimensions
91.5 mm
96 mm 91.0 ± 0.5 mm
87 mm
91.0 ± 0.5 mm
96 mm

Front Side Panel Cutout


DAM
Digital Power Meter

Ordering Information
MODEL WITH WITHOUT DISPLAY
UNIT
/ SERIES SELECTOR SELECTOR FORMAT
DAM330 A

DAM3000 A

DAM100 A

DAM1000 A

For primary current For primary current


from 60 A to 500 A from 600 A to 5000 A
DAM 330 - XXXX DAM 3000 - XXXX
DAM 100 - XXXX DAM 1000 - XXXX

Order number Order number

Model DAM 330 & DAM 100 Model DAM3000 & DAM1000
ORDER NUMBER *CT RATIO ORDER NUMBER *CT RATIO
0060 60 / 5 A 600 600 / 5 A
0100 100 / 5 A 800 800 / 5 A
0150 150 / 5 A 1000 1000 / 5 A
0200 200 / 5 A 1200 1200 / 5 A
0250 250 / 5 A 1500 1500 / 5 A
0300 300 / 5 A 1600 1600 / 5 A
0400 400 / 5 A 2000 2000 / 5 A
0500 500 / 5 A 2400 2400 / 5 A
2500 2500 / 5 A

Example: Model DAM 330 - 0060 for 3000 3000 / 5 A


digital ammeter with CT ratio 3200 3200 / 5 A
60 / 5 A.
3500 3500 / 5 A
4000 4000 / 5 A
*CT : Current Transformer 4500 4500 / 5 A
For other CT ratio, please contact
5000 5000 / 5 A
the manufacturer.

MODEL DESCRIPTION
DAM330 - xxxx - 240A Auxiliary voltage 240 V AC
DAM100 - xxxx - 240A Auxiliary voltage 240 V AC
DAM330 - xxxx - 110A Auxiliary voltage 110 V AC
DAM100 - xxxx - 110A Auxiliary voltage 110 V AC
DAM3000 - xxxx - 240A Auxiliary voltage 240 V AC
DAM

DAM1000 - xxxx - 240A Auxiliary voltage 240 V AC


DAM3000 - xxxx - 110A Auxiliary voltage 110 V AC
DAM1000 - xxxx - 110A Auxiliary voltage 110 V AC
Digital Power Meter
DPM680
Features
Measurement Parameters:
• Phase & Line Voltages (L-N)
• Phase Current & Neutral Current
• Bidirectional kW, kVAR & kVA
• Bidirectional kWh, kVARh & kVAh
• Frequency
• Total & Displacement Power Factor
• Voltage Total Harmonic Distortion
• Current Total Harmonic Distortion
• Avg. and Max. Thermal Current Demand
• Avg. and Max. Power (kW, kVA, kVAR) Demand
• Current Sequence Components
• Voltage Sequence Components

TFT Colour LCD Display


Serial RS-485 Modbus RTU
Modbus TCP/IP
Built-in Webserver
Voltage & Current Waveform Display
Voltage & Current Harmonics Display

Technical Data
WIRING SYSTEMS POWER & THERMAL CURRENT DEMAND Protocol : Modbus TCP/IP
3-phase 4-wire system Interval : 1 ~ 30 mins Interface : Ethernet 10M/100M BaseT
3-phase 3-wire system
VOLTAGE AND CURRENT SEQUENCE Protocol : HTTP Server
COMPONENTS Interface : Ethernet 10M/100M BaseT
Nominal current :5A Positive, negative and zero sequence
Min. measurement : 5 mA AUXILIARY POWER SUPPLY
Accuracy : 0.2% of full scale FREQUENCY MEASUREMENT AC voltage : 90 ~ 415 V AC
Burden : < 0.05 VA at 5 A Measurement range : 45 ~ 65 Hz Frequency : 50 / 60 Hz
Measurement range : 10 A Accuracy : 0.2% DC voltage : 100 ~ 300 V DC
Pulsed withstand : 100 A for 1 sec Power consumption : 3W typical
CT primary : 5 ~ 50,000 A ENERGY MEASUREMENT ACCURACY Sustained overload : 500 V AC
Active : IEC 62053-22 class 0.5
Reactive : IEC 62053-23 class 2 ENVIRONMENTAL CONDITIONS
Nominal phase voltage : 0 ~ 300 V AC Overvoltage category : IV
Minimum measurement : 10 V HARMONICS DISPLAY Pollution degree :2
Accuracy : 0.2% at full scale Fundamental up to 32nd order Operating temperature : -10˚C ~ +55˚C
Phase voltage via VT : 60 ~ 50,000 V Storage temperature : -20˚C ~ +70˚C
VOLTAGE & CURRENT WAVEFORM Humidity : 0 – 95%,
DPM 680

POWER MEASUREMENT DISPLAY non condensing


Real power, apparent power, reactive power Simultaneous 3-phase voltage or
Accuracy : 0.5% current waveforms MECHANICAL
Mounting : according to DIN 43700 /
POWER FACTOR MEASUREMENT COMMUNICATION ANSI C39.1
Total and displacement power factor Protocol : Modbus RTU Dimension (mm) : 96(w) x 96(h) x 100(d)
Accuracy : 0.5% Interface : Isolated RS485 Enclosure protection : IP63 at the panel
IP20 at the body
Approximate weight : 0.5 kg
Digital Power Meter

Typical Application Diagrams Case Dimensions


96 mm
3-PHASE 4-WIRE SYSTEM : 4 CTs, Direct V Input 3-PHASE 4-WIRE SYSTEM : 3 CTs, Direct V Input

L1 L2 L3 Ln L1 L2 L3 Ln
90~415 V AC / 90~415 V AC /
AUX 100~300 V DC AUX 100~300 V DC

96 mm
S1
S2
l1
S1
S2
l1 Front
S1 S1
l2 Ethernet l2 Ethernet
S2 S2
S1 S1
l3 l3
S2 S2

S1 S1
ln ln
S2 S2

GND GND
L1 RS 485 L1 RS 485
Modbus-RTU Modbus-RTU
L2 L2

L3 L3
Ln Ln

90 mm
LOAD LOAD

Side

3-PHASE 3-WIRE SYSTEM : 3 CTs, 3 VTs 3-PHASE 3-WIRE SYSTEM : 3 CTs, Direct V Input 83 mm
L1 L2 L3 L1 L2 L3

m
17 mm

0m
90~415 V AC / 90~415 V AC /
AUX 100~300 V DC AUX 100~300 V DC

10
S1 S1
l1 l1
S2 S2
S1 S1
l2 Ethernet l2 Ethernet
S2 S2
S1 S1

86 mm
l3 l3
S2 S2

S1
ln
S1
ln Rear
ea
S2 S2
GND GND
L1 RS 485 L1 RS 485
Modbus-RTU Modbus-RTU
L2 L2

L3 L3
Ln Ln
LOAD GND
LOAD

Test Standards Cut-Out Recommendations

IEC 61010-1
Safety requirements.

91±0.5mm
IEC 61326-1
EMC requirements.

91±0.5mm

Ordering Information 101.6±0.5mm

MODEL DESCRIPTION
DPM 680

DPM 680-415AD Auxiliary Voltage 90 ~ 415 V AC or 100 ~ 300 V DC


Digital Power Meter
DPM380
DPM380B
Features
LCD display with back lighting
Modbus-RTU communication
(for DPM380 only)

MEASUREMENT PARAMETERS:
• Phase Voltage (L-N)
• Line Voltage (L-L)
• Phase Current and Neutral Current
• Bidirectional kW (per phase & total)
• Bidirectional kVAR (per phase & total)
• Bidirectional kVA (per phase & total)
• Frequency
• Power Factor (per phase & total)
• Energy (+ and - ) for kWh, kVARh and kVAh
• THD Phase Voltage ( L-N )
• THD Phase Current
• Active Power (kW) Demand
• Maximum Active Power (kW) Demand
Technical Data
DISPLAY TYPE POWER MEASUREMENT AUXILIARY POWER SUPPLY
LCD display Real power, apparent power, reactive power AC voltage : 90 ~ 415 V AC
measurement Frequency : 50 / 60 Hz
Measuring updating period : 1 s DC voltage : 100 ~ 300 V DC
MEASUREMENTS Accuracy : 1.0% Power consumption : <3 VA
3-phase 4-wire system
3-phase 3-wire system ACTIVE POWER DEMAND
Interval : 1 ~ 30 mins COMMUNICATION
Hardware interface : Isolated RS485
CURRENT MEASUREMENT POWER FACTOR MEASUREMENT Protocol : Modbus-RTU
CT primary : 5 ~ 8000 A Total and displacement power factor Baud rate : 2400, 4800, 9600,
CT secondary : 5A Accuracy : 1.0% 19200, 38400
Minimum measurement : 5 mA
DPM 380 / 380B

Accuracy : 0.5% from 1A to ENVIRONMENTAL CONDITIONS


6 A (secondary) FREQUENCY MEASUREMENT Operating temperature : -10˚C ~ +55˚C
Burden : < 0.05 VA at 5 A Measurement range : 45 ~ 65 Hz Storage temperature : -20˚C ~ +70˚C
Sustained overload : 6A Measurement updating period : 1s Humidity : 0 – 95%,
Accuracy : 0.5% non condensing

VOLTAGE MEASUREMENT MECHANICAL


Nominal phase voltage : 20 ~ 300 V AC ENERGY ACCURACY Mounting : Panel mounting
Minimum measurement : 10 V Active (according to IEC 62053-21) : class 1 Dimension (mm) : 96(w) x 96(h) x 100(d)
Accuracy : 0.5% at full scale Reactive (according to IEC 62053-23) : class 2 Approximate weight : 0.5 kg
Phase voltage via VT : 60 ~ 33,000 V
Digital Power Meter

Typical Application Diagram Case Dimensions


3-PHASE 4-WIRE SYSTEM WITH 4 CTs CONNECTION 96 mm

L1 L2 L3 Ln
90~415 V AC /
AUX 100~300 V DC

96 mm
S1 Front
l1
S2
S1
l2
S2
S1
l3
S2

S1 * For DPM380 only


ln
S2
-

90 mm
GND
L1
RS 485 +
L2 Modbus-RTU
L3 GND Side
Ln

LOAD 83 mm

m
17 mm

0m
10
3-PHASE 4-WIRE SYSTEM WITH 3 CTs CONNECTION

L1 L2 L3 Ln

86 mm
90~415 V AC /
Rear
ea
AUX 100~300 V DC

S1
l1
S2
S1 86 mm
l2
S2
S1
l3
S2

S1 * For DPM380 only


ln
S2
-
GND
Cut-Out Recommendations
L1
RS 485 +
L2 Modbus-RTU
L3 GND
Ln

LOAD 91±0.5mm

Electromagnetic Compatibility (EMC) 91±0.5mm


Part 6-2: Generic Standards IEC61000-6-2
DPM 380 / 380B

Immunity for industrial environments.


101.6±0.5mm
Part 6-4: Generic Standards IEC61000-6-4
Emission standard for industrial environments.

Ordering Information

MODEL DESCRIPTION
DPM 380-415AD Auxiliary Voltage 90 ~ 415 V AC or 100 ~ 300 V DC, with RS 485
DPM 380B-415AD Auxiliary Voltage 90 ~ 415 V AC or 100 ~ 300 V DC
Digital Power Meter
DM38
Features
LCD display with back lighting
Modbus-RTU communication
DIN rail type

MEASUREMENT PARAMETERS:
• Phase Voltage ( L-N )
• Line Voltage ( L-L )
• Phase Current
• Bidirectional kW (per phase & total)
• Bidirectional kVAR (per phase & total)
• Bidirectional kVA (per phase & total)
• Frequency
• Power Factor (per phase & total)
• Energy (+ and - ) for kWh, kVARh and kVAh
• THD Phase Voltage ( L-N )
• THD Phase Current

Technical Data
DISPLAY TYPE POWER MEASUREMENT POWER SUPPLY
LCD display Real power, apparent power, reactive power Self supplied : 100 ~ 240 V AC
measurement Frequency : 50 / 60 Hz
Measuring updating period :1s Power consumption : <3 VA
MEASUREMENTS Accuracy : 1.0%
3-phase 4-wire system
COMMUNICATION
POWER FACTOR MEASUREMENT Hardware interface : Isolated RS485
CURRENT MEASUREMENT Total and displacement power factor Protocol : Modbus-RTU
CT primary : 5 ~ 8000 A Accuracy : 1.0% Baud rate : 2400, 4800, 9600,
CT secondary :5A 19200, 38400
Minimum measurement : 10 mA
Accuracy : 0.5% from 1A to FREQUENCY MEASUREMENT
6 A (secondary) Measurement range : 45 ~ 65 Hz ENVIRONMENTAL CONDITIONS
Burden : < 0.03 VA at 5 A Measurement updating period : 1s Operating temperature : -10˚C ~ +55˚C
Sustained overload :6A Accuracy : 0.5% Storage temperature : -20˚C ~ +70˚C
Humidity : 0 – 95%,
non condensing
VOLTAGE MEASUREMENT ENERGY ACCURACY
Nominal phase voltage : 70 ~ 300 V AC Active (according to IEC 62053-21) : class 1 MECHANICAL
Minimum measurement : 10 V Reactive (according to IEC 62053-23) : class 2 Mounting : DIN rail
DM 38

Accuracy : 0.5% at full scale Dimension (mm) : 65(w) x 85(h) x 50(d)


Approximate weight : 0.3 kg
Digital Power Meter

Typical Application Diagram

DM 38 CONNECTION DIAGRAM

RS 485 120 Ohm


S1 S2 S1 S2 S1 S2 Modbus-RTU

1 2 3 4 5 6 7 8 9 10 11
I1 I2 I3

+
GND

P1
S1
L1 ! S2
DM38

LOAD
L2
L3
P2
X
Ln
NOTE: Current transformer secondary
12 13 14 15 16 17 18 19 20 21 22
terminal MUST NOT be earthed.
L1 L2 L3 Ln

Electromagnetic Compatibility (EMC) Case Dimensions

Part 6-2: Generic Standards IEC61000-6-2


Immunity for industrial environments. Front
65 mm
Part 6-4: Generic Standards IEC61000-6-4
Emission standard for industrial environments.

45.5 mm
85 mm

Ordering Information
71 mm

MODEL DESCRIPTION
DM 38-240A Self Powered 100~240 V AC
Side
50 mm
DM 38

15.5 mm
Voltage Relay
MU2300
Features
• Multifunction numerical voltage protection relay

time or inverse-time characteristic

time

or inverse-time characteristic

time
• Negative sequence overvoltage protection (U2>)

• Neutral displacement / residual overvoltage


protection (U0
characteristic
• Can be used in single-phase or three-phase
operation
Introduction • Multi-function isolated digital input with wide
input voltage range
The MU2300 is a microprocessor based numerical • Fault record and event code recording
relay for voltage protection functions in electrical
• Five programmable voltage-free output contacts
distribution network.
• Isolated RS485 Modbus - RTU communication
• ANSI Code : 27, 47, 59, 60

Technical Data
INPUTS OUTPUT CONTACTS NEGATIVE SEQUENCE OVER-VOLTAGE
Measuring input: 5 programmable contacts +1 IRF contact: ELEMENT
Rated voltage input : 57 ~ 130 V Rated voltage : 250 V AC / DC Negative sequence over-voltage setting, U2>
Rated frequency : 50 / 60 Hz Continuous carry :5A : 5 - 200 V
Make and carry for 0.2 s : 30 A Time multiplier, TMS : 0.5 - 100
Expected electrical life : 100,000 operations 2>
Rated auxiliary voltage: at rated current : 0 - 600 s
Model MU2300-150D : 24 ~ 150 V DC Expected mechanical life : 5 x 106 operations
Model MU2300-240AD : 85 ~ 265 V AC RESIDUAL OVER-VOLTAGE ELEMENT
110 ~ 340 V DC UNDER-VOLTAGE ELEMENT Residual over-voltage setting, U0> : 0.5 - 130 V
Low set setting U< : 5 - 130 V Time multiplier, TMS : 0.5 - 100
Power consumption: High set setting U<< : 5 - 130 V 0>: 0 - 600 s
AC auxiliary voltage : 6 ~ 10 VA typical Time multiplier, TMS : 0.5 - 100
DC auxiliary voltage : 5 ~ 9 W typical : 0 - 600 s ENVIRONMENTAL CONDITIONS
MU 2300

: 0 - 600 s Temperature : -5˚C to +55˚C


Humidity : 56 days at 93% RH and
Binary Input: OVER-VOLTAGE ELEMENT 40˚C non-condensing
External binary input : 85 ~ 265 V AC/DC Low set setting U> : 5 - 200 V MECHANICAL
High set setting U>> : 5 - 260 V Mounting : Panel mounting
Time multiplier, TMS : 0.5 - 100 Dimension (mm) : 142(w) x 165(h) x 198(d)
COMMUNICATION : 0 - 600 s Enclosure protection : IP54 at the panel
RS485 Modbus - RTU te time tU>> : 0 - 600 s Approximate weight : 2.7 kg
Voltage Relay

Undervoltage Characteristic Overvoltage Characteristic Case Dimensions


100
142 mm

100
Operating time (sec)

Operating time (sec)


10

165 mm
1
Front
10
10 TMS=8 TMS=10
TMS= TMS=8
5 TMS=5
TMS=
TMS=3
TMS=
3 0.1
TMS=1

1
TMS=
1 0.01
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0 2 4 6 8 10 12 14 16 18 20
Applied voltage/relay setting voltage Applied voltage/relay setting voltage 198 mm

34 mm

Typical Application Diagrams

136 mm
A A
Side
B B
C C
2 34 Trip Contact 2 34 Trip Contact
36 R1 36 R1
3 35 3 35

5 38 5 38
37 R2 37 R2
6 6
40 40
8 39 R3 8 39 R3
129 1 mm
9 42 9 42
41 R4 41 R4
11 11
27 27
12 26 R5 12 26 R5
139 1 mm
28 Internal 28 Internal Panel Cutout
13 30 Relay 30 Relay
External
Digital 29 Failure 13 29 Failure
Input 14 22 External 22
Termination Resistor Digital 14 Termination Resistor
32 23 N- Input 23 N-
A Uaux 33 A 32
24 P+ Uaux 24 P+
33
25 Communication 25 Communication
31 Cable Shield 31 Cable Shield

C B C B
Phase rotation Phase rotation

3Vp-p + Vresidual connection 2Vp-p + Vresidual connection

A
B
A
B Ordering Information
C C
2 34 Trip Contact 2 34 Trip Contact
36 R1 36 R1
3 35 3 35 MODEL DESCRIPTION
5 38 5 38
MU2300-150D For 50 / 60 Hz system, auxiliary
37 R2 37 R2
6 6
voltage 24 ~ 150 V DC
40 40
8 39 R3 8 39 R3

9 42 9 42
MU2300-240AD For 50 / 60 Hz system, auxiliary
41 R4 41 R4
11 11 voltage 85 ~ 265 V AC or
27
26 R5
27
26 R5
110~340 V DC
12 12
MU 2300

28 Internal 28 Internal
13 30 Relay 30 Relay
External
Digital 29 Failure 13 29 Failure
External
Input 14 22 Digital 14 22
Termination Resistor Termination Resistor
Input
32 23 N- 23 N-
A Uaux 33 A 32
24 P+ Uaux 24 P+
33
25 Communication 25 Communication
31 Cable Shield 31 Cable Shield

C B C B
Phase rotation Phase rotation

3Vp-n + Vresidual connection 3Vp-n connection


Voltage Relay
MU350
Product Description
MU350 is 3-phase voltage relay that combines
various protections and starting delay.

Features
• Undervoltage
• Overvoltage
• Delay-on
• 2 voltage-free output contacts
• Voltage and frequency display
• 3-Phase
• Unbalance
• Phase loss
• Phase sequence
• With or without neutral connection
• Phase to phase or phase to neutral monitoring
• Programmable relay outputs
• ANSI Code : 27, 47, 59, 60

Technical Data
SETTING RANGES OUTPUT CONTACTS ENVIRONMENTAL CONDITIONS
Undervoltage Rated voltage : 250 V AC Temperature : -5˚C to +55˚C
Time delay for undervoltage : 0.1s to 30s Contact rating : 5A Humidity : 56 days at 93% RH and
Overvoltage Expected electrical life : 100,000 operations at 40˚C non-condensing
Time delay for overvoltage : 0.1s to 30s rated current
Start time delay : 0s to 999s Expected mechanical life : 5 x 106 operations MECHANICAL
Unbalance Mounting : Panel mounting
Time delay for unbalance : 0.5s to 30s Dimension (mm) : 96(w) x 96(h) x 90(d)
Phase loss : Fixed time <0.5s INDICATORS Approximate weight : 0.31 kg
Phase sequence : Fixed time <0.5s Auxiliary supply : Green indicator
Pickup indicator : Red indicator
Trip : 7-segment display and
AUXILIARY SUPPLY red LED indicators
MU350-415V : 380 V (-25%) to 415 V (+20%) AC
Supply frequency : 45 Hz to 65 Hz ACCURACY
Maximum power consumption: 3VA Protection thresholds : ± 3%
Time delay : 0 to 0.5s, ± 15% with
MU 350

minimum 40ms
MEASURING INPUT : 0.6s and above, < ± 3%
Line to line : 100 to 415 (+20%) VAC Measurements : ± 3%
Line to Neutral : 58 to 240 (+20%) VAC
Voltage Relay

Typical Application Diagrams Case Dimensions


96 mm
L-L 100-415V AC, L-N 58-240V AC
L1
L2

96 mm
L3
N Front
(OPTIONAL)
L1 L2 L3 N

R1 R2
90 mm
AUX 70 mm

NC NO COM NC NO COM
380-415V AC

Side

91.0 ± 0.5 mm

Ordering Information

91.0 ± 0.5 mm
Panel Cutout
MODEL DESCRIPTION
MU350-415V 3-Phase, auxiliary voltage 380 ~ 415 V AC, 45-65 Hz
MU 350
Voltage Relay
MU250
MU150
Product Description
MU150 and MU250 are voltage relays that
combine various protections and starting delay.
MU 150 MU150 is used for single-phase monitoring while
MU250 is used for 3-phase monitoring.

Features
• Microprocessor based numerical relay
• Undervoltage
• Overvoltage
• Delay-on
• 2 voltage-free output contacts
• Voltage and frequency display
• ANSI Code : 27, 47, 59, 60

MU 250 Features For MU 250 only


• 3-Phase
• Unbalance
• Phase loss
• Phase sequence
• With or without neutral connection
• Phase to phase or phase to neutral monitoring

Technical Data
SETTING RANGES POWER SUPPLY INPUT INDICATORS
Undervoltage : 1% to 25% Input voltage: Auxiliary supply : Green indicator
Time delay for undervoltage : 0.1s to 30s MU150-110V & MU250-110V Pickup indicator : Red indicator
Overvoltage : 1% to 20% : 100 V (-25%) to 120 V (+20%) AC Trip : 7-segment display and red
Time delay for overvoltage : 0.1s to 30s MU150-240V & MU250-220V LED indicators
Start time delay : 0s to 999s : 220 V (-25%) to 240 V (+20%) AC
MU250-415V ACCURACY
: 380 V (-25%) to 415 V (+20%) Protection thresholds : ± 3%
For MU250 only: Supply frequency : 45 Hz to 65 Hz Time delay : 0 to 0.5s, ± 15% with
Unbalance : 3% to 20% minimum 40ms
Time delay for unbalance : 0.5s to 30s : 0.6s and above, < ± 3%
MU 250 / 150

Phase loss : Fixed time <0.5s Maximum power consumption: Measurements : ± 3%


Phase sequence : Fixed time <0.5s MU250 : 3VA
MU150 : 2.5VA
ENVIRONMENTAL CONDITIONS
Temperature : -5˚C to +55˚C
OUTPUT CONTACTS Humidity : 56 days at 93% RH and
Rated voltage : 250 V AC 40˚C non-condensing
Contact rating : 5A
Expected electrical life : 100,000 operations at MECHANICAL
rated current Mounting : DIN rail
Expected mechanical life : 5 x 106 operations Dimension (mm) : 71(w) x 85(h) x 70(d)
Approximate weight : 0.4 kg
Voltage Relay

Typical Application Diagrams


MU250 MU150
L1 L
L2 N
L3
N
(OPTIONAL)
1 2 3 4 5 6 7

1 2 3 4 5 6 7 R1 R2

R1 R2
8 9 10 11 12 13 14
COM NO NC COM NO NC MU150
8 9 10 11 12 13 14
COM NO NC COM NO NC MU250

(Neutral connection is optional)

Case Dimensions Ordering Information


71 mm
MODEL DESCRIPTION
MU150-110V Single-Phase, 100/110/120 V AC,
20 mm
45-65 Hz power supply
45 mm

Front MU150-240V Single-Phase, 220/230/240 V AC,


45-65 Hz power supply

20 mm
MU250-110V 3-phase, 100/110/120 V AC
45-65 Hz power supply

MU250-220V 3-phase, 220/230/240 V AC


70 mm 45-65 Hz power supply

MU250-415V 3-Phase, 380/400/415 V AC,


45-65 Hz power supply
85 mm

Side

30 mm 20 mm 20 mm
MU 250 / 150
3 - Phase Voltage Relay
MX210
Features
• Numerical voltage protection relay
• Undervoltage
• Overvoltage
• Phase loss
• Phase sequence
• 3-Phase/Single-phase
• ANSI Code: 27, 47, 59

Product Description
MX210 is voltage relay that combines
overvoltage, undervoltage, phase loss,
phase sequence and delay start functions.

MX210 can be programmed by user to


set nominal voltage as well as set into 3-
phase or Single-phase mode.

Technical Data
POWER SUPPLY INPUT SETTING RANGES INDICATORS
3-Phase System Undervoltage : 78% - 98% Power supply ON : Green indicator
Phase-to-phase voltage : 380 V (-25%) to 415 V Overvoltage : 102% - 122% Output ON : Green indicator
(+20%) AC Delay time : 0.1 - 10s Undervoltage : Red indicator
Normal voltage : 380, 400, 415 Vpp, 220, Overvoltage : Red indicator
Single Phase 230, 240, Vpn Phase error : Red indicator
Phase-to-neutral voltage : 220 V (-25%) to 240 V 3-phase / Single-phase
(+20%) AC
Frequency range : 45 to 65 Hz ENVIRONMENTAL CONDITIONS
Max. power consumption : 3 VA maximum ACCURACY Temperature : -5˚C to +55˚C
Protection thresholds : ± 3% Humidity : 56 days at 93% RH and
Hysteresis : 1% 40˚C non-condensing
OUTPUT CONTACTS Delay time : 0-0.5s, ± 15%,
Rated voltage : 250 V AC 40ms minimum MECHANICAL
Contact rating : 5A : 0.5s and above, ± 3% Mounting : DIN rail
Expected electrical life : 100,000 operations at Measurements : ± 3% Dimension (mm) : 71(w) x 85(h) x 70(d)
rated current Approximate weight : 0.3 kg
Expected mechanical life : 5 x 106 operations
MX 210
3 - Phase Voltage Relay

Wiring Diagram
Single-Phase System 3-Phase System

L L1
N L2

L3

N
1 2 3 4 5 6 7

R1
1 2 3 4 5 6 7
8 9 10 11 12 13 14
R1

8 9 10 11 12 13 14

Operations Diagram
i ) Over Voltage Function ii ) Under Voltage Function

R
Over Voltage Limit Y
Hysteresis B
R Hysteresis
Y Under Voltage Limit
B
Relay T
Relay T
ON
ON
>U LED ON
<U LED ON

Case Dimensions Ordering Information

71 mm 70 mm MODEL DESCRIPTION
MX210 - 415V 3-Phase 380-415V AC
20 mm Single-Phase 220-240V AC
45-65Hz
45 mm

85 mm

Front Side

20 mm

30 mm 20 mm 20 mm
MX 210
Voltage Relay
MX 160A
MX200A
MK180A
Under Voltage Relay

MX 180A
Over Voltage Relay

MX 200A
Under & Over Voltage Relay MK160A
Features
• Electronic monitoring relay
• Voltage monitoring for single
3-phase system
• Phase failure monitoring
• Adjustable voltage limit
• Adjustable delay time
• Indicators for voltage fault
• Indicators for power and output ON
• ANSI Code : 27, 47, 59

Product Description
MX160A, MX180A & MX200A are single
or 3-phase monitoring relays. The relays
are designed for application where it
required to maintain the voltage within
set limits. A built-in adjustable time delay
prevents nuisance tripping.

Technical Data
POWER SUPPLY INPUT SETTING RANGES INDICATORS
3-Phase System Lower voltage limit * : 78% - 98% Power supply ON : Green indicator
Phase-to-phase voltage : 380 V AC ± 20% Upper voltage limit ** : 102% - 122% Output ON : Red indicator
MX 200A / 180A / 160A

400 V AC ± 20% Delay time, T : 0.1 - 10s Under voltage limit (U<) * : Red indicator
415 V AC ± 20% Over voltage limit (U>) ** : Red indicator

Single Phase HYSTERESIS


Phase-to-neutral voltage : 220 V AC ± 20% ≤1% of rms - value ENVIRONMENTAL CONDITIONS
230 V AC ± 20% Temperature : -5˚C to +55˚C
240 V AC ± 20% Humidity : 56 days at 93% RH and
Frequency range : 45 to 65 Hz OUTPUT CONTACTS 40˚C non-condensing
Max. power consumption : 3 VA Rated voltage : 250 V AC
Contact rating : 5A MECHANICAL
Input Connections Expected electrical life : 100,000 operations at Mounting : Circular 11-pin plug-in
For 3-phase model : Phase L1, L2, L3 to rated current socket
pin 5, 6, & 7 Expected mechanical life : 5 x 106 operations Dimension (mm) : 35(w) x 80(h) x 72.5(d)
Neutral to pin 11 Approximate weight : 0.3 kg
For single-phase model : Phase L to pin 5, 6 &
7***
Neutral to pin 11 * Applicable to MX160A and MX200A only
** Applicable to MX180A and MX200A only
*** For single phase connection, short pin 5,6 & 7
Voltage Relay

Wiring Diagram
Single-Phase System 3-Phase System
L L3
N L2
L1
N

5 6 7
4 8 5 6 7
3 9 4 8
2 10 3 9
1 11 2 10
1 11

Operations Diagram
i ) Over Voltage Function** ii ) Under Voltage Function*

R
Over Voltage Limit Y
Hysteresis B
R Hysteresis
Y Under Voltage Limit
B
Relay T
Relay T
ON
ON
>U LED ON
<U LED ON

Case Dimensions Ordering Information

FUNCTION
Under Over Supply
MODEL Voltage Voltage Voltage
Monitoring Monitoring V AC
MX160A - 380 YES NO 380
MX 200A / 180A / 160A

MX160A - 400 YES NO 400

80 mm MX160A - 415 YES NO 415

MX180A - 380 NO YES 380


MX180A - 400 NO YES 400
72.5 mm
MX180A - 415 NO YES 415
35 mm

MX200A - 380 YES YES 380


MX200A - 400 YES YES 400
MX200A - 415 YES YES 415
Voltage Relay
MX100
MX 50
Phase Failure monitoring

MX 100
Phase Sequence &
Phase Failure monitoring MK50
Features
• Electronic monitoring relay
• Phase sequence monitoring*
• Phase failure monitoring
• Plug-in type module
• Indicators for power and alarm status
• ANSI Code : 47

Product Description
This phase sequence and phase failure
relay is designed for application where the
3-phase supply needs to be continuously
monitored for proper sequencing and
phase loss. Commonly used to protect a
3-phase motor.

Technical Data

POWER SUPPLY INPUT INDICATORS


Phase-to-phase voltage : 230 V AC ±20% Power supply ON : Green indicator
: 400 V AC ±20% Output ON : Red indicator
Frequency range : 45 to 65 Hz
Max power consumption : 3 VA
Input connections : Phase L1 to pin 5 ENVIRONMENTAL CONDITIONS
Phase L2 to pin 6 Temperature : -5˚C to +55˚C
Phase L3 to pin 7 Humidity : 56 days at 93% RH and
Neutral (optional) to 40˚C non-condensing
pin 11

OUTPUT CONTACTS MECHANICAL


Rated voltage : 250 V AC Mounting : Circular 11-pin plug-in
MX 100 / 50

Contact rating : 5A socket


Expected electrical life : 100,000 operations at Dimension (mm) : 35(w) x 80(h) x 72.5(d)
rated current Approximate weight : 0.3 kg
Expected mechanical life : 5 x 106 operations
Voltage Relay

Wiring Diagram
Example 1 Example 2

L3 L3
L2 3~ L2 3~
L1 L1
N

6 5 6 7
5 7
4 8 4 8
3 9 3 9
2 10 2 10
1 11 1 11

Function Table
Condition Pin 5 Pin 6 Pin 7 Relay Remark
1 L1 L2 L3 ON System healthy
2 Loss L2 L3 OFF Phase failure
3 L1 Loss L3 OFF Phase failure
4 L1 L2 Loss OFF Phase failure
5 L2 L1 L3 OFF Sequence fault*
6 L3 L2 L1 OFF Sequence fault* * Applicable to MX100 model only

Case Dimensions Ordering Information

MODEL DESCRIPTION
MX100 - 230 Auxiliary voltage 184~276 V AC
MX100 - 400 Auxiliary voltage 320~480 V AC
MX50 - 230 Auxiliary voltage 184~276 V AC
MX50 - 400 Auxiliary voltage 320~480 V AC
80 mm
MX 100 / 50

72.5 mm
35 mm
Reverse Power Relay
RPR415A
Features
• Reverse power monitoring

• 3-phase, 3 or 4-wire system

• Adjustable reverse power setting

• Adjustable tripping time delay

• Indicators for auxiliary power, trip delay


and trip status

• Test button

• ANSI Code: 32

Product Description

RPR 415A relay is a directionally controlled


timing relay used to protect AC generators
from motoring. When such condition
occurs and the reverse current exceeded
the customer adjustable preset limit for a
predetermined delay time, the trip relay
operates to disconnect the circuit.

Technical Data
INPUT SETTING RANGES ENVIRONMENTAL CONDITIONS
Rated Phase-neutral voltage : 220V to 240V AC Range : 2% to 20% reverse current Temperature : -5˚C to +55˚C
Rated Phase-phase voltage : 380V to 415V AC with 1% Hysteresis Humidity : 56 days at 93% RH and 40˚C
Rated frequency : 50 or 60 Hz Time delay : 0 sec to 20 sec non-condensing
Rated current (I n) : 5A 3-Phase 4-wire (star) or 3-Phase 3-wire (delta)
Burden : < 0.3 VA at In
Thermal withstand : 1.2 x U n , 2 x I n continuous MECHANICAL
: 1.2 x U n , 10 x I n for 3 sec ACCURACY Mounting : DIN rail
Power consumption : 3 VA maximum Protection thresholds Hysteresis : ± 3% Dimension (mm) : 71(w) x 85(h) x 70(d)
Delay time : 1% Approximate weight : 0.3 kg
: 0-0.5s, ± 15%,
OUTPUT CONTACTS 40ms minimum.
Rated voltage : 250 V AC/DC Measurements : 0.5s and above, ± 3% : ± 3%
RPR 415A

Contact rating : 5A
Expected electrical life: 100,000 operations at
rated current INDICATORS
Expected mechanical life: 5 x 106 operations Auxiliary supply : Green indicator
Delay : Red indicator
Trip : Red indicator
Reverse Power Relay

Typical Application Diagram

I I
L1 L1
S1 S1
L2 Generator L2 Generator
L3 3~ L3 3~
415V
N

240V

1 2 3 4 5 6 7 1 2 3 4 5 6 7

R1 R1
S2 S1 S2 S1
8 9 10 11 12 13 14 8 9 10 11 12 13 14

3-Phase 4-wire / single-phase system 3-Phase 3-wire system

Case Dimensions
71 mm 70 mm

20 mm
45 mm

85 mm

Front Side

20 mm

30 mm 20 mm 20 mm

Ordering Information

MODEL DESCRIPTION
RPR415A 380-415Vpp AC / 220-240Vpn AC, 45-65Hz
RPR 415A
Reverse Power Relay
RPR415
Features
• Reverse power monitoring

• 3-phase-4-wire system

• Adjustable reverse power setting

• Adjustable tripping time delay

• Indicators for auxiliary power, trip delay


and trip status

• Test button

• ANSI Code : 32

Product Description

The RPR 415 relay is a directionally


controlled timing relay used to protect
AC generators from motoring. When
such a condition occurs and the reverse
current exceeded the customer adjustable
preset limit and the current persists for a
predetermined delay time, the trip relay
operates to diconnect the circuit.

Technical Data
INPUT INDICATORS
Rated voltage (Un) : 380 ~ 440 V AC Auxiliary supply : Green indicator
Rated current (I n) : 5A Delay : Red indicator
Rated frequency : 50 or 60 Hz Trip : Red indicator
Overload : 1.2 x U n , 2 x I n continuous
1.2 x U n , 10 x I n for 3 sec
ENVIRONMENTAL CONDITIONS
OUTPUT CONTACTS Temperature : -5˚C to +55˚C
Rated voltage : 250 V AC/DC Humidity : 56 days at 93% RH and 40˚C
Contact rating : 5A non-condensing
Expected electrical life: 100,000 operations at
rated current
Expected mechanical life: 5 x 106 operations MECHANICAL
Mounting : Panel mounting
RPR 415

Dimension (mm) : 96(w) x 96(h) x 142(d)


SETTING RANGES Approximate weight : 0.8 kg
Range : 2% to 20% reverse current with
1% Hysteresis
Time delay : 0 sec to 20 sec
Reverse Power Relay

Typical Application Diagram

DIRECTION OF CURRENT FOR OPERATION


P1
L1
S1
L2
L3
N

1 2 3 4 5 6 7 8

COM NC NO

9 10 11 12 13 14 15 16

Case Dimensions
142 mm
96 mm 91.0 ± 0.5 mm
132 mm
91.0 ± 0.5 mm
96 mm

Front Side Panel Cutout

Ordering Information

MODEL DESCRIPTION
RPR415 Auxiliary voltage 380 ~ 440 V AC
RPR 415
Power Factor Regulator
PFR140
PFR120
PFR80
PFR60
Features
• Microprocessor based intelligent auto switching
control

• Automatic C/K and rated step adjustment

• Automatic CT polarity correction

• Display of power factor, current & total harmonic


distortion of current

• Programmable sensitivity

• Last step can be used as alarm/fan output

• Under/over voltage alarm, under/over compensate


alarm & high harmonic distortion alarm

• User-friendly setting

• Complies with IEC 61000-6-2 standard

Technical Data
RATINGS AUXILIARY POWER SUPPLY CURRENT INPUT ENVIRONMENTAL CONDITIONS
Current Supply voltage : 220~240 V AC / Rated current ( In ) :5A Temperature : -5˚C to +55˚C
380~415 V AC Operating Limits : 0.05 A to 6.5 A Humidity : 56 days at 93% RH and
Operating Limits : -15% + 10% Rated Frequency : 50 Hz or 60 Hz 40˚C non-condensing
Consumption : 10 VA max
PFR 140 / 120 / 80 / 60

Rated frequency : 50 Hz or 60 Hz
CONTROL RANGE MECHANICAL
Power factor setting : 0.8 Ind - 0.8 Cap Mounting : Panel mounting
OUTPUT CONTACTS C/K setting : 0.03 - 1.20 / Automatic Dimension (mm) : 144(w) x 144(h) x 90(d)
Numbers of outputs : 6 / 8 / 12 / 14 ( PFR60 Switching sensitivity : 5 - 600 s/step Enclosure protection : IP54 at the panel
/ PFR80 / PFR120 / Reconnection time for Approximate weight : 1.2 kg
PFR140 ) same step : 5 - 240 s
Rated voltage : 250 V AC THD threshold : 0.20 - 3.00 ( 20% - 300% ) /
Contact rating : 5A OFF
Expected electrical life : 100,000 operations at Switching Program : Automatic / Automatic
rated current Rotate / 4-quadrant /
Expected mechanical life : 5 x 106 operations Manual
Max current for the :0/1/2/3/4/5/6/8/
common terminals : 12 A continuous 12 / 16
( Automatic if C/K set to
Auto )
Power Factor Regulator

Typical Application Diagram

MAIN
N L3 L2 L1
13 13

220~240 V AC
AUX AUX

380~415 V AC
VOLTAGE 1 VOLTAGE
14 14
2

Power Factor Regulator


1
15 2 3 15
16 3 4 16
P1 17 5
CURRENT 4
18 6 For 220~240 V AC Model Only
/5A 5
P2 19 6 7
20 11 7 8
21 12 8 9
22 13 9 10
23 14 10 11
24 12
FUSE

K14 K13 K2 K1

LOAD

Ordering Information Case Dimensions


144 mm

MODEL DESCRIPTION
PFR60 - 415 - 50 6 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
144 mm

PFR80 - 415 - 50 8 Steps, 50 Hz system, auxiliary voltage 380~415 V AC Front


PFR120 - 415 - 50 12 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
PFR140 - 415 - 50 14 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
PFR60 - 220 - 50 6 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
PFR80 - 220 - 50 8 Steps, 50 Hz system, auxiliary voltage 220~240 V AC 90 mm
76 mm
PFR120 - 220 - 50 12 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
PFR 140 / 120 / 80 / 60

PFR140 - 220 - 50 14 Steps, 50 Hz system, auxiliary voltage 220~240 V AC


PFR60 - 415 - 60 6 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
Side
PFR80 - 415 - 60 8 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
PFR120 - 415 - 60 12 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
PFR140 - 415 - 60 14 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
PFR60 - 220 - 60 6 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
138 mm
PFR80 - 220 - 60 8 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
PFR120 - 220 - 60 12 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
138 mm

PFR140 - 220 - 60 14 Steps, 60 Hz system, auxiliary voltage 220~240 V AC Panel


Cutout
Power Factor Regulator
PFR96
PFR96P
Features
• Microprocessor based intelligent auto
switching control

• Automatic C/K and rated step


adjustment

• Automatic CT polarity correction

• Display of power factor & current

• Programmable sensitivity

• Last step can be used as alarm/fan output

• Under/over voltage alarm, under/over


compensate alarm

For PFR 96 For PFR 96P • User-friendly setting

• For single-phase system • For 3-phase system • Complies with IEC 61000-6-2 standard

Technical Data
RATINGS AUXILIARY POWER SUPPLY CURRENT INPUT ENVIRONMENTAL CONDITIONS
Model PFR96 : 110 ~ 120 V AC / Rated current ( In ) :5A Temperature : -5˚C to +55˚C
220 ~ 240 V AC Operating Limits : 0.15 A to 6.5 A Humidity : 56 days at 93% RH and
Model PFR96P : 380 ~ 415 V AC Rated frequency : 50 Hz or 60 Hz 40˚C non-condensing
Operating Limits : -15% + 10%
Consumption : 10 VA max
Rated frequency : 50 Hz or 60 Hz CONTROL RANGE MECHANICAL
Power factor setting : 0.8 Ind - 0.8 Cap Mounting : Panel mounting
C/K setting : 0.03 - 1.20 / Automatic Dimension (mm) : 96(w) x 96(h) x 90(d)
OUTPUT CONTACTS Switching sensitivity : 5 - 600 s/step Approximate weight : 0.6 kg
Numbers of outputs :6 Reconnection time for
Rated voltage : 250 V AC same step : 5 - 240 s
Contact rating : 5A Switching Program : Automatic / Automatic
PFR 96 / 96P

Expected electrical life : 100,000 operations at Rotate / 4-quadrant /


rated current Manual
Expected mechanical life : 5 x 106 operations :0/1/2/3/4/5/6/8
Max current for the / 12 / 16
common terminals : 12 A continuous ( Automatic if C/K set to
Auto )
Power Factor Regulator

Typical Application Diagram


Diagram 1 - For model PFR96 Diagram 2 - For model PFR96P

MAIN MAIN
N L3 L2 L1 N L3 L2 L1

8 16 8 16
6 6
FUSE 15 FUSE
7 15
Power Factor

7 VOLTAGE

Power Factor
VOLTAGE 5 5
Regulator

Regulator
6 220 V AC / 14 6 380~415 14
4 4
110 V AC 13 V AC
5 3 5 13
3
4 12 4 12
2 2
P1 3 11 P1 3 11
CURRENT 1 CURRENT 1
2 /5A 10 2 10
/5A
P2 9 P2
1 1 9

FUSE FUSE

K1 K5 K6 K1 K5 K6

LOAD LOAD

Ordering Information Case Dimensions


96 mm
MODEL DESCRIPTION
PFR96 - 220 - 50 6 Steps, for 50 Hz system, auxiliary voltage 220~240 V AC
96mm

PFR96 - 220 - 60 6 Steps, for 60 Hz system, auxiliary voltage 220~240 V AC Front


PFR96 - 110 - 50 6 Steps, for 50 Hz system, auxiliary voltage 110~120 V AC
PFR96 - 110 - 60 6 Steps, for 60 Hz system, auxiliary voltage 110~120 V AC
PFR96P - 415 - 50 6 Steps, for 50 Hz system, auxiliary voltage 380~415 V AC
PFR96P - 415 - 60 6 Steps, for 60 Hz system, auxiliary voltage 380~415 V AC 90 mm
70 mm

Side
PFR 96 / 96P

91.0 ± 0.5 mm
91.0 ± 0.5 mm

Panel
Cutout
Power Factor Regulator
PFRLCD
Features
• 2” inch, 64 x 128 dot matrix LCD display
with back lighting
• Three phase and single phase detection
of reactive power
• 12 (or 8 for 8 step model) output with
two additional
• Independent contact for signal alarm
output and fan output
• Three phase compensation mode

• Automatic detection of C/K and rated
step value
Measurement Parameters • No Voltage release
• Active, reactive, apparent power • Up till 31st order Harmonics •
measurement in graphical and table
• Temperature format • Alarm linked signal contact
• Phase voltage and phase current • Power Factor and Displacement • Programmable fan control
Power Factor (Cosφ)
• Frequency • ModBus-RTU communication

Typical Application Diagram


PFRLCD Connection diagram for 3 Phase 12 Step model PFRLCD Connection diagram for 1 Phase 12 Step model
LOAD LOAD

K12 K2 K1 K12 K2 K1

FUSE FUSE

FUSE FUSE
31 30 24 23 14 13 12 11 10 9 8 7 6 5 4 3 2 1 20 21 22

SIG
31 30 24 23 14 13 12 11 10 9 8 7 6 5 4 3 2 1 20 21 22

SIG
32 44 43 42 41 40 39 38 37 36 35 34 33

SIG
32 44 43 42 41 40 39 38 37 36 35 34 33

SIG
N L
N L

AUX
AUX

FAN FAN
FAN FAN
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
P2

N L1 L2 L3 S1 S2 S1 S2 S1 S2
CT3

PFR LCD
PFR LCD
P1
P2

PFR LCD
CT2
P1

P2
P2

N L1 L2 L3 In Out
CT1
CT1

P1
P1

N- N-
RS485 RS485
RP RP
Modbus Modbus
P+ P+
-RTU -RTU
GND GND
T1 T1
T2 Thermistor T2 Thermistor
L1
L2
L3
L1
L2
L3

N
N

PFRLCD120P3-230-50 PFRLCD120P1-230-50
Power Factor Regulator

Technical Data
CURRENT INPUT CONTROL RANGE DISPLAY
(EACH PHASE) Target Power factor : 0.80 Inductive – 0.80 %THDI & %THDV : 0 – 500%
Nominal Current : 5 A rms Capacitive Harmonics Resolution : Up till 31st Harmonics
Operating Limits : 0.01-10 A rms C/K setting : 0.03 – 1.20 / Automatic Active power : 0– 3000 W
Rated frequency : 50 Hz or 60 Hz detect Reactive power : 0 – 3000 VAR
Sensitivity : 5 - 300s / Step Apparent power : 0 – 3000 VA
VOLTAGE INPUT Reconnection time : 5 – 240s Voltage : 0 – 300 VAC
(EACH PHASE with respect to neutral) Switching program : Automatic/ Manual/ Current : 0.00 – 10.0 A rms
Nominal Voltage : 230 Vrms Four-quadrant/ Temperature : 0 – 100 °C
Operating Limits : 0 - 277 V L-N Rotational/ Linear Frequency : 45 – 65Hz
Consumption : 0.05 VA : 0/ 1/ 2/ 3/ 4/ 5/ 6/ 8/ 12/ Power Factor : -1.00 – 1.00
Rated Frequency : 50 Hz or 60 Hz 16/ Fixed Displacement Power Factor : -1.00 – 1.00
Catagory : III Detection mode : L1 / L2 / L3 / Max Load /
Three Phase ENVIRONMENT CONDITIONS
THERMISTOR INPUT Fan Setting : Fixed on / Output On / Temperature : -5°C to +55°C
Thermistor Temperature range : 0 – 100 °C Temperature / None Humidity : 56 days at 93%RH and
Signal Contact 40°C non-condensing
programmable alarm / Pollution Degree : II
AUXILIARY
None Dielectric Withstand : IEC61010-1
Auxiliary Input Voltage Range : 85 - 265 Vrms
Consumption : 10 VA max Altitude : 2000 m
Rated Frequency : 50 Hz or 60 Hz ALARM SETTING RANGE
%THDI : 20 - 300% / OFF ELECTROMAGNETIC COMPATIBILITY (EMC)
Over Voltage : 253 – 264 V/ OFF Part 6-2: Generic standards : IEC61000-6-2
OUTPUT CONTACTS
Under Voltage : 195 – 204 V/ OFF Immunity for industrial
Number of outputs : 14 (model dependent)
Over Current : 5.50 – 7.00 A/ OFF environments
Rated voltage : 250 V AC
Under Current : 0.01 – 0.15 A/ OFF Part 6-4: Generic standards : IEC61000-6-4
Contact rating : 5A
Under Compensate : On / OFF Emission standard for industrial
Expected electrical life: 100,000 operations at
Over Compensate : On / OFF environments
rated current
*CT Polarity Error : On / OFF
Expected mechanical life : 5 x 106 operations
Step Error : On / OFF MECHANICAL
Temperature : 36 – 70 °C / OFF Mounting : Panel mounting
Dimension (mm) : 144(w) x 144(h) x 122(d)
Case Dimensions Enclosure protection : IP54 at the panel
IP20 at the body
144mm
Approximate weight : 1.2 kg
(for three phase model),
1 kg
144mm

(for single phase model)

Front View
Ordering Information
122mm
102mm

MODEL DESCRIPTION
PFRLCD120P3-230-50 12 Step, 3 Phase, 230Vrms, 50Hz Model
PFRLCD80P3-230-50 8 Step, 3 Phase, 230Vrms, 50Hz Model
PFRLCD120P1-230-50 12 Step, 1 Phase, 230Vrms, 50Hz Model
PFR LCD

Side View PFRLCD80P1-230-50 8 Step, 1 Phase, 230Vrms, 50Hz Model


138mm PFRLCD120P3-230-60 12 Step, 3 Phase, 230Vrms, 60Hz Model
PFRLCD80P3-230-60 8 Step, 3 Phase, 230Vrms, 60Hz Model
PFRLCD120P1-230-60 12 Step, 1 Phase, 230Vrms, 60Hz Model
138mm

PFRLCD80P1-230-60 8 Step, 1 Phase, 230Vrms, 60Hz Model

Panel Cutout
Annunciator
AN112
AN120
AN128
Features
• 12, 20 or 28 windows. Replaceable super-
bright LED modules, with choice of amber or
red illumination
• 11 Alarm Sequences as per ISA-18.1 standard

Programmable Alarm Annunciator programmable, either from front panel built-in
pushbutton or using PC
The AN112/120 series Alarm Annunciator provides ideal solution for all your alarm
• Option of either RS232 or RS485 MODBUS-RTU
system management and requirement. It comes with either 12, 20 or 28 windows, communication. Comes with user-friendly
and due to the use of microprocessor-based design, the alarm annunciator is highly

and industries. • Repeat relay for each window as well as


relays for connection to external equipment to
form alarm management system
Tests And Standards • Sleep or unattended mode feature is available,
Electrostatic discharge IEC61000-4-2, Class III, air discharge 8 KV for stations not permanently manned
Electrostatic discharge IEC61000-4-2, Class III, contact discharge 6 KV
Electrical fast transient IEC61000-4-4 4 KV, 5/50ns • Auto-silence and auto-acknowledge features,
Surge immunity IEC61000-4-5 4 KV, L to E with delay settable from 1 – 255 s
Enclosure protection when panel mounted Front: IP41
Enclosure: IP30 • Other amount of windows available upon
request.

Technical Data
WINDOW ALARM CONTACT INPUTS COMMUNICATION
Window Dimension : 50 x 30 mm. Opto-isolated inputs Hardware interface : AN1xx - xx - x - A: RS232
Type: White translucent lens. AN1xx-30 : 24-36 V DC AN1xx - xx - x - B : Isolated
Colours: Red, Amber. Coloured AN1xx-110 : 88-132 V DC RS485
Input current : 3 mA typical Protocol : Modbus - RTU
module. Baud rate : 300 to 57600
Windows Flash Fast: 1.4 Hz
AN 112 / 120 / 128

OUTPUT CONTACTS
Slow: 0.45 Hz Repeat relays : Potential free for each ENVIRONMENT CONDITIONS
alarm point. Operation temperature: -20 to 60˚C
Intermittent: 5 A at 250 V AC, 3 A at 30 V Storage temperature : -20 to 80˚C
DC. Resistive load. Humidity : 0 - 95% RH,
AUX1-AUX3, non condensing
ALARM SEQUENCES RBACK, SSP : 5 A at 250 V AC, 5 A at 30 V
M, A, R, R-12, F1A, F1M, F2A, F2M, F3A, F3M, DC. Resistive load.
Follower MECHANICAL
Mounting : Panel Mounting
AUXILIARY POWER INPUT TERMINALS Approximate weight : AN 112 : 2.4 kg
Fuse protected. Wire size : 28-14 AWG. ( 0.08mm2 to 2.5mm2 ) AN 120 : 3.1 kg
AN1xx-30 : 24-36 V DC or 18-27 V AC. Removable screw type terminal block AN 128 : 3.5 kg
AN1xx-110 : 88-132 V DC or 64-95 V AC.
Power consumption : AN112: 6 W, AN120: 8 W,
AN128: 10W
Annunciator

Typical Connection Diagram

4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
C12 C11 C10 C9 C8 C7 C6 C5 C4

- + - + - + - + - + - + - + - + - +
+ -
D- D+

Sleep RS485
RS232 1 2 3 4
1 2

Mute
Ack
Power Reset
- + - + - +
Ground - + Test
1Rst
Dis RBCK SSP AUX3 AUX2 AUX1
Power Button Relay output C1 C2 C3
1 2 3 1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 1 2 3 4 1 2 3 4 1 2 3 4

Case Dimensions

237 mm 132 mm 237 mm 132 mm


126 mm
157 mm

246 mm
277 mm

AN112 Front AN112 Side

237 mm 132 mm
AN128 Front AN128 Side

1.5 mm
186 mm
217 mm

132 mm

206 mm

AN120 Front AN120 Side Bottom


AN 112 / 120 / 128

Ordering Information
Order code:
A: RS 232 communication
AN1 - - - B: RS 485 communication
0: without repeat relays
1: with repeat relays
Power Supply: 30, 110 V DC
Number of Windows: 12, 20, 28
For example: 12 windows, 30 V DC, with repeat relays, RS232 communication:
AN112-30-1-A
Annunciator
AL24
Features
• Alarm monitoring
• Outputs for lamp and horn
• Indicators for output contacts

Product Description
Alarm relay provides LED indication and output
contact signalling when there is alarm signal
received. The alarm relay consist of alarm input,
alarm accept, alarm reset, lamp test controlled
input and 2 relay contacts. Red LED indication

2 (LED) turned on when alarm signal is received.

Technical Data
INPUT INPUT TYPE ENVIRONMENTAL CONDITIONS
Auxiliary input : 24 V DC ± 5% Dry contact Temperature : -5˚C to +55˚C
Max power consumption : 2 W Humidity : 56 days at 93% RH and
40˚C non-condensing
OUTPUT CONTACTS
INPUT CONNECTION Rated voltage : 250 V AC
Alarm input : Pin 7 Contact rating : 5A MECHANICAL
Aalrm accept : Pin 4 Expected electrical life : 100,000 operations at Mounting : Circular 11-pin plug-in
Lamp test : Pin 8 rated current socket
Reset : Pin 5 Expected mechanical life : 5 x 106 operations Dimension (mm) : 35(w) x 80(h) x 72.5(d)
Common : Pin 6 Approximate weight : 0.2 kg

INDICATORS
Auxiliary supply : Green indicator
Relay 1 (Lamp) : Red indicator
Relay 2 (Horn) : Red indicator
AL 24
Annunciator

Operation Diagram
Auxiliary supply (pin +2, -10)
Alarm (pin 7, 6)
Alarm accept (pin 4, 6)
Reset (pin 5, 6)
Relay 1 (Lamp)
Relay 2 (Horn)
Lamp test (pin 8, 6)

Connection Diagram Case Dimensions


ACCEPT
ALARM

ALARM
RESET

LAMP
TEST

AL 24

5 6 7 Alarm Relay

4 8
RY1 RY2
NO 3 9 NO
80 mm
2 10
1 11
COM COM AUXILIARY

+ - RELAY 1
Power Supply ( DC only ) RELAY 2

72.5 mm
35 mm

Ordering Information

MODEL DESCRIPTION
AL 24 Auxiliary voltage 24 V DC
AL 24
Motor Protection Relay
MPR500
Features
• Microprocessor based numerical relay
• Thermal overload
• Overcurrent
• Undercurrent
• Unbalance
• Phase loss
• Phase sequence
• Earth fault
• Prolonged starting/stall rotor
• 2 voltage-free output contacts
• ANSI Code : 37, 46, 47, 49, 50P, 50G

Technical Data
CT RATINGS SETTING RANGES Prolonged starting/
Rated current : 2-10A Thermal Overload stalled rotor, IS : B.
Rated frequency : 50 Hz or 60 Hz time constant, t6X : 1 – 40s. Step 0.1 x IB
Burden : <0.3 VA at rated current Step 0.1s for 1-10s, Prolonged starting
Thermal withstand: Continuous : 2x max rated step 1s for 10-40s. time delay, tStart : 0 – 60s.
45s : 6x max rated Short circuit, I>> : B. Step 0.1s for 1-10s,
1s : 10x max rated Step 1 x IB step 1s for 10-60s.
Short circuit delay time, t>> : 0 – 25s. Stalled rotor delay time, tStall : 0 – 60s.
BINARY INPUT Step 0.1s for 1-10s, Step 0.1s for 1-10s,
Rated input voltage : 12V (Supplied step 1s for 10-25s. step 1s for 10-60s.
internally) Undercurrent, I<< : B.
Step 1% INDICATORS
Undercurrent delay time, t<< : 0 – 60s. Run : Green indicator
AUXILIARY SUPPLY Step 0.1s for 1-10s, Trip/Pickup : 7-segment display
Model MPR 500-240AD : 85 ~ 265 V AC step 1s for 10-60s. and red indicator
110 ~ 370 V DC Unbalance, : Thermal : Yellow indicator
Supply frequency : 50 or 60 Hz Step 1%
Maximum power Unbalance delay time, t : 0 – 25s.
Step 0.1s for 1-10s, ENVIRONMENTAL CONDITIONS
consumption : 3 VA typical Temperature : -5˚C to +55˚C
Step 1s for 10-25s.
Earth fault, I0 : Humidity : 56 days at 93% RH and 40˚C
B.
Step 1% non-condensing
OUTPUT CONTACTS
MPR 500

Earth fault delay time, t0 : 0 – 25s.


Rated voltage : 250V AC
Step 0.1s for 1-10s,
Contact rating : 5A MECHANICAL
step 1s for 10-25s.
Expected electrical life : 100,000 operations at Mounting : Panel mounting
Phass loss : < 120ms
rated current Dimension (mm) : 96(w) x 96(h) x 110(d)
Phase sequence : < 120ms
Expected mechanical life : 5 x 106 operations Approximate weight : 0.8 kg
Motor Protection Relay

Typical Application Diagrams

L3 L2 L1 F4 L F2

F1 F2 F3 F1

K1 MPR 500 MPR 500


K1
L L
9 1 9 1
Aux Aux
10 N 10 N
2 2

11 3 NO 11 3 NO

12 4 NC S2 12 4 NC S2
R1 Stop R1 Stop
13 COM 13 COM
5 5
COM COM
14 6 S1 14 6 S1
Start K1 Start K1
R2 R2
15 7 NC 15 7 NC
Binary Binary
input NO input NO
16 8 16 8
M H1 K1 M K1
H1
Block R1/ Block R1/
Reset/ Reset/
Trip Trip
N N

Motor with higher full load current using external CT Single-Phase Motor
)

Thermal Tripping Curve Case Dimensions


time time
96 mm
2 hour 2 hour
1 hour 1 hour

30 min 30 min
20 min
96 mm

20 min
10 min 10 min Front
5 min 5 min
3 min 3 min
2 min 2 min
1 min t6x 1 min
40 sec 40s 40 sec
30 sec 30s 30 sec t6x
20 sec 40s
110 mm
20 sec 20s
30s 100 mm
10 sec 10s 10 sec 20s
5 sec 5s 5 sec 10s
3 sec 3 sec
5s
2 sec 2s 2 sec
1.05 1.05
1 sec 1s 1 sec 2s
1s Side
1 2 3 4 5 6 1 2 3 4 5 6
I/IB I/IB
(a) With 0% thermal capacity (cold start) (b) With prior 50% thermal capacity

91.0 ± 0.5 mm
91.0 ± 0.5 mm
MPR 500

Ordering Information
Panel Cutout
MODEL DESCRIPTION
MPR500-240AD For 50 / 60 Hz system, auxiliary voltage 85 ~ 265 V AC or 110 ~ 370 V DC