M. Design of A Single Span Beam (Special Focus On Links)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Prepared by OLOWO Michael O.

MEMBER CALCULATION OUTPUT

BEAM Beam A1/1A-2 is a beam under the second floor.


A1/1A-2 225 X 450
Loading calculation:

Beam self-weight = 5KN/m


Wall load = (3.75 x 3.0 x 1.4) = 15.75KN/m
1
Slab loading from panel 9 = 3 WLx
= 0.33 X 10.52 X 3.975
= 13.939KN/m
Total loading on the span = 34.69KN/m

34.69KN/m

3975mm

1A 2

Moment:

Moment M = WL2/8 = 0.125 X 34.69 X 3.9752

M = 68.51546KNm

𝑠𝑝𝑎𝑛
Bf = bw + (L-beam)
10

𝑠𝑝𝑎𝑛
*Note, for a simply supported T-beam, Bf = bw + 5

3975
Hence, Bf = 225 + 10

Bf = 622.5mm
Bf = 600mm

THIS DOCUMENT WAS PREPARED BY ENGR. OLOWO OLAIDE MICHAEL. IT SHALL NEITHER BE DISCLOSED TO THIRD PARTIES NOR
USED FOR OTHER PURPOSES OTHER THAN THOSE FOR WHICH IT HAS BEEEN DISCLOSED. NO EXTRACT OF THIS MANUAL MAY BE
REPRODUCED, STORED IN A RETRIEVAL SYSTEM OR TRANSMITTED IN ANY FORM OR BY ANY MEANS; ELECTRONIC,
PHOTOCOPYING, RECORDING OR OTHERWISE WITHOUT PRIOR WRITTEN PERMISSION FROM THE AUTHOR.
Prepared by OLOWO Michael O.

MEMBER CALCULATION OUTPUT

BEAM
A1/1A-2 K= M = 68515460
Fcubd2 25 X 600 X 4072

K = 0.0275746 < 0.156 (No compression reinforcement is


required)

𝐾
La = 0.5 + √0.25 − ( )
0.9

0.0275746
La = 0.5 + √0.25 − ( )
0.9
La = 0.968360497 > 0.95 (Use maximum value for La)
La = 0.95

Area of steel

AS = M
0.95FYZ

Where Z = Lad

AS = 68515460
0.95 X 410 X 0.95 x 407

As = 454.9494mm2 3Y16mm
bars BTM
Provide 3Y16mm bars BTM (AS = 603mm2)

Provide 2Y12 bars as hanger bars. 2Y12mm as


hanger bars

THIS DOCUMENT WAS PREPARED BY ENGR. OLOWO OLAIDE MICHAEL. IT SHALL NEITHER BE DISCLOSED TO THIRD PARTIES NOR
USED FOR OTHER PURPOSES OTHER THAN THOSE FOR WHICH IT HAS BEEEN DISCLOSED. NO EXTRACT OF THIS MANUAL MAY BE
REPRODUCED, STORED IN A RETRIEVAL SYSTEM OR TRANSMITTED IN ANY FORM OR BY ANY MEANS; ELECTRONIC,
PHOTOCOPYING, RECORDING OR OTHERWISE WITHOUT PRIOR WRITTEN PERMISSION FROM THE AUTHOR.
Prepared by OLOWO Michael O.

MEMBER CALCULATION OUTPUT

PROVISION FOR LINKS:


BEAM
A1/1A-2 Design Shear force, Vmax due to ultimate load
= (34.69 x 3.975 x 0.5) = 68.946375KN

Design shear stress, v = Vmax/bd = 68946.375/(225 x 407) = 0.7529 N/mm2

100As/bd = (100 X 603)/(225X407) = 0.66

400/d = 400/407 = 0.98

Design concrete shear stress, vc = 0.79 X (100AS/bd)1/3 X (400/d)1/4

vc = 0.79 X (0.66)1/3 X (0.98)1/4

vc = 0.68N/mm2

vc + 0.4 = 1.08N/mm2
0.5vc = 0.34N/mm2

0.5vc < V < vc+0.4

Hence provide minimum links at a spacing of:

Sv = (ASV X O.95FYV)
0.4bv

Sv = 157 x 0.95 x 410


0.4 x 225

Sv = 679.46mm > 0.75d (maximum)

Provide 10mm links at 300mm c/c along the span. Y10mm @


300mm c/c
as links

THIS DOCUMENT WAS PREPARED BY ENGR. OLOWO OLAIDE MICHAEL. IT SHALL NEITHER BE DISCLOSED TO THIRD PARTIES NOR
USED FOR OTHER PURPOSES OTHER THAN THOSE FOR WHICH IT HAS BEEEN DISCLOSED. NO EXTRACT OF THIS MANUAL MAY BE
REPRODUCED, STORED IN A RETRIEVAL SYSTEM OR TRANSMITTED IN ANY FORM OR BY ANY MEANS; ELECTRONIC,
PHOTOCOPYING, RECORDING OR OTHERWISE WITHOUT PRIOR WRITTEN PERMISSION FROM THE AUTHOR.
Prepared by OLOWO Michael O.

MEMBER CALCULATION OUTPUT

BEAM
A1/1A-2 Deflection check:

Span = 3975mm
Moment, M = 68515460Nmm
Asprov = 603mm2
Asreq = 454.9494mm2

From table 3.10 BS8110-1:1997, Modification factor is given by:

(477−𝐹𝑠)
MF = 0.55 + (120(0.9+𝑀/𝑏𝑑2) ≤ 0.2

2𝐹𝑦𝐴𝑠𝑟𝑒𝑞
Where the design service stress, Fs = 3𝐴𝑠𝑝𝑟𝑜𝑣

2 𝑋 410 𝑋 454.9494
Fs = = 206.22361N/mm2
3 𝑋 603

68515460
M/bd2 = = 0.6894
6000 𝑋 407 𝑋 407

(477−206.22361)
MF = 0.55 + (120(0.9+0.6894) = 1.9697315 > 2.0

𝑠𝑝𝑎𝑛
Limiting = effective span ratio X MF
𝑒𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑑𝑒𝑝𝑡ℎ

𝑠𝑝𝑎𝑛 DEFLECTION
From table 3.9, BS8110-1:1997, the basic for IS SATISFIED
𝑒𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑑𝑒𝑝𝑡ℎ 𝑟𝑎𝑡𝑖𝑜
continuous beam in rectangular section = 26
𝑠𝑝𝑎𝑛
Limiting = 20 x 1.9697315 = 39.39463
𝑒𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑑𝑒𝑝𝑡ℎ 𝑟𝑎𝑡𝑖𝑜

𝐴𝑐𝑡𝑢𝑎𝑙 𝑠𝑝𝑎𝑛 3975


= = 9.7665848
𝑒𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑑𝑒𝑝𝑡ℎ 407

Actual value < Limiting value

*Note: Readers are expected to draw the shear force and bending
moment diagram.

THIS DOCUMENT WAS PREPARED BY ENGR. OLOWO OLAIDE MICHAEL. IT SHALL NEITHER BE DISCLOSED TO THIRD PARTIES NOR
USED FOR OTHER PURPOSES OTHER THAN THOSE FOR WHICH IT HAS BEEEN DISCLOSED. NO EXTRACT OF THIS MANUAL MAY BE
REPRODUCED, STORED IN A RETRIEVAL SYSTEM OR TRANSMITTED IN ANY FORM OR BY ANY MEANS; ELECTRONIC,
PHOTOCOPYING, RECORDING OR OTHERWISE WITHOUT PRIOR WRITTEN PERMISSION FROM THE AUTHOR.

You might also like