Ceiling Diffusers: Type DLQ

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

X XDLQtestregistrierung

Ceiling diffusers
Type DLQ

Horizontal air discharge

With plenum box

For four-way horizontal supply air discharge, with fixed ​


With damper blade
air control blades – sheet steel diffuser face
Square ceiling diffusers
■■ Nominal sizes 250, 300, 400, 500, 600, 625
■■ Volume flow rate range 20 – 700 l/s or 72 – 2520 m³/h
■■ Square diffuser face
■■ Diffuser face made of sheet steel, powder-coated
■■ For supply and extract air
■■ For variable and constant volume flows
■■ For all types of ceiling systems
With connecting frame ■■ High induction results in a rapid reduction of the temperature difference and ​
airflow velocity

Optional equipment and accessories


■■ Exposed diffuser face available in RAL CLASSIC colours
■■ Horizontal or vertical duct connection
■■ Blanking plates for adjusting the discharge direction
■■ Duct cross bar for installation without plenum box
■■ Plenum box with cord-operated damper blade and pressure tap
With butterfly damper

02/2017 – DE/en PD – DLQ – 1


Ceiling diffusers
General information DLQ

Type Page
DLQ General information DLQ – 2
Function DLQ – 3
Technical data DLQ – 4
Quick sizing DLQ – 5
Specification text DLQ – 7
Order code DLQ – 8
Variants DLQ – 9
Dimensions and weight DLQ – 11
Product details DLQ – 14
Installation examples DLQ – 15
Installation details DLQ – 16
Commissioning DLQ – 18
Basic information and nomenclature DLQ – 20

Application Application differences from –10 to +10 K


– Type DLQ ceiling diffusers are used as supply ​ – For room heights up to 4 m (lower edge of ​
air or extract air diffusers for comfort zones suspended ceiling)
– Attractive design element for building owners ​ – For all types of ceiling systems
and architects with demanding aesthetic ​
requirements Special characteristics
– Horizontal four-way supply air discharge for ​ – Horizontal four-way supply air discharge
mixed flow ventilation – Diffuser face made of galvanised sheet steel
– High induction results in a rapid reduction of ​ – For all types of ceiling systems
the temperature difference and airflow velocity ​ – Horizontal or vertical duct connection
(supply air variant)
Nominal sizes
– For variable and constant volume flows
– 250, 300, 400, 500, 600, 625
– For supply air to room air temperature ​

Description Variant Materials and surfaces


– Square diffuser face – Diffuser face, connecting frame and butterfly ​
damper made of sheet steel
Connection – AK: Plenum box and cross bar made of ​
– A: Diffuser face only galvanised sheet steel
– AR: Vertical duct connection, with connecting ​ – X: Plenum box made of plastic and galvanised ​
frame sheet steel
– AG: Vertical duct connection, with blades – Lip seal made of rubber
– C: Vertical duct connection with butterfly ​ – Attachments are dip coated RAL 9005, jet ​
damper black
– AK: Horizontal duct connection, with plenum ​ – Diffuser face powder-coated RAL 9010, pure ​
box white
– P1: Powder-coated, RAL CLASSIC colour
Parts and characteristics
– Square diffuser face with fixed air control ​ Standards and guidelines
blades – Sound power level of the air-regenerated noise ​
– Diffuser front frame measured according to EN ISO 5135
– Simple installation of the diffuser face due to ​
central fixing screw with decorative cap Maintenance
– Maintenance-free as construction and ​
Accessories materials are not subject to wear
– Lip seal – Inspection and cleaning to VDI 6022

Construction features
– Spigot suitable for circular ducts to EN 1506 or ​
EN 13180

PD – DLQ – 2 02/2017 – DE/en


Ceiling diffusers
Function DLQ

Functional description only very little turbulence in the occupied zone.


Ceiling diffusers direct the air from air conditioning ​ Type DLQ ceiling diffusers have fixed blades. ​
systems into the room. The resulting airflow ​ Horizontal air discharge is four-way. The supply air ​
induces high levels of room air, thereby rapidly ​ to room air temperature difference may range from​
reducing the airflow velocity and the temperature ​ –10 to +10 K.
difference between supply air and room air. ​ To give rooms an aesthetic, uniform look, ​
Ceiling diffusers allow for large volume flow rates. ​ Type DLQ diffusers may also be used for extract ​
The result is a mixed flow ventilation in comfort ​ air.
zones, with good overall room ventilation, creating ​

Schematic illustration of the DLQ, with plenum box for horizontal duct connection


④ ⑨

② ①

⑬ ⑩

⑫ ⑪

① Diffuser face Optional


② Central fixing screw ⑦ Lip seal
③ Plenum box ⑧ Damper blade for volume flow rate balancing
④ Cross bar ⑨ Pressure tap
⑤ Suspension hole ⑩ Green cord for closing the damper blade
⑥ Spigot ⑪ White cord for opening the damper blade
⑫ Text label indicating plenum box variant
⑬ Measuring tube

Air patterns Horizontal air discharge

02/2017 – DE/en PD – DLQ – 3


Ceiling diffusers
Technical data DLQ

Nominal sizes 250, 300, 400, 500, 600, 625 mm


Minimum volume flow rate 20 – 250 l/s or 72 – 900 m³/h
Maximum volume flow rate, with LWA ≅ 50 dB(A) 575 – 700 l/s or 2070 – 2520 m³/h
Supply air to room air temperature difference –10 to +10 K

PD – DLQ – 4 02/2017 – DE/en


Ceiling diffusers
Quick sizing DLQ

Quick sizing tables provide a good overview of the ​


volume flow rates and corresponding sound ​
power levels and differential pressures.
The maximum volume flow rates apply to a sound ​
power level of approx. 50 dB (A).
Exact values for all parameters can be determined ​
with our Easy Product Finder design programme.

DLQ-A, DLQ-AR (supply air), sound power level and total differential pressure
 Δpt LWA
Nominal size
l/s m³/h Pa dB(A)
20 72 3 <15
55 198 20 26
250
95 342 59 40
130 468 111 50
35 126 2 <15
95 342 18 24
300
155 558 47 38
210 756 87 50
75 270 2 <15
190 684 13 25
400
310 1116 35 38
430 1548 68 50
135 486 2 <15
295 1062 10 27
500
455 1638 23 39
615 2214 43 50
220 792 2 15
380 1440 8 34
600
535 1980 15 43
690 2484 24 50
250 900 2 20
400 1440 6 34
625
550 1980 12 43
700 2520 19 50

02/2017 – DE/en PD – DLQ – 5


Ceiling diffusers
Quick sizing DLQ

DLQ-AK (supply air), sound power level and total differential pressure
Damper blade position
  0° 45° 90°
Nominal size
Δpt LWA Δpt LWA Δpt LWA
l/s m³/h Pa dB(A) Pa dB(A) Pa dB(A)
20 72 5 <15 5 <15 10 <15
35 126 14 22 16 22 31 25
250
60 216 41 38 46 38 92 41
90 324 92 51 104 51 208 53
35 126 6 9 9 11 20 19
70 252 26 30 37 32 81 39
300
100 360 53 41 75 43 165 49
135 486 96 51 137 54 301 59
75 270 9 13 15 21 33 30
130 468 28 31 46 39 98 45
400
185 666 56 42 93 50 198 57
235 846 90 50 150 61 319 67
135 486 12 16 15 19 48 35
210 756 28 32 36 35 116 49
500
285 1026 52 42 66 45 213 58
360 1296 83 50 105 53 340 65
220 792 12 18 19 26 49 35
330 1188 26 32 44 39 111 47
600
440 1584 46 42 78 49 197 57
545 1962 71 50 119 58 303 66
250 900 14 21 26 33 64 39
330 1188 24 31 46 42 111 47
625
410 1476 37 39 70 49 171 55
575 2070 74 50 138 61 336 74

Sizing example

Given data
 = 300 l/s (1280 m3/h)
Square ceiling diffuser, steel, with fixed air control ​
blades
Maximum sound power level 40 dB(A) with ​
damper blade position 45°
Four-way air discharge

Quick sizing
Type DLQ
Nominal sizes: 600, 625
Selected: DLQ/600

PD – DLQ – 6 02/2017 – DE/en


Ceiling diffusers
Specification text DLQ

This specification text describes the general ​


properties of the product. Texts for variants can be ​
generated with our Easy Product Finder design ​
programme.

Ceiling diffusers with square diffuser face. Supply ​ – Lip seal made of rubber
air and extract air variants for comfort zones. ​ – Attachments are dip coated RAL 9005, jet ​
Diffuser face with fixed air control blades for ​ black
horizontal four-way air discharge. For installation ​ – Diffuser face powder-coated RAL 9010, pure ​
into all types of suspended ceilings. white
Ready-to-install component which consists of the ​ – P1: Powder-coated, RAL CLASSIC colour
galvanised sheet steel diffuser face with fixed air ​
control blades, a diffuser front frame with ​ Technical data
perimeter seal and connecting frame, opposed ​ – Nominal sizes: 250, 300, 400, 500, 600, ​
action blades, butterfly damper or a plenum box. 625 mm
Diffuser face suitable for central screw fixing. – Minimum volume flow rate: 20 – 250 l/s or ​
Sound power level of the air-regenerated noise ​ 72 – 900 m³/h
measured according to EN ISO 5135. – Maximum volume flow rate, with ​
LWA ≅ 50 dB(A): 575 – 700 l/s or ​
Special characteristics 2070 – 2520 m³/h
– Horizontal four-way supply air discharge – Supply air to room air temperature difference: ​
– Diffuser face made of galvanised sheet steel –10 to +10 K
– For all types of ceiling systems
– Horizontal or vertical duct connection Sizing data
– _____________ _______________________
Materials and surfaces ​[m³/h]
– Diffuser face, connecting frame and butterfly ​ – Δpt____________ _______________________
damper made of sheet steel ​[Pa]
– AK: Plenum box and cross bar made of ​ Air-regenerated noise
galvanised sheet steel – LWA____________ _______________________
– X: Plenum box made of plastic and galvanised ​ ​[dB(A)]
sheet steel

02/2017 – DE/en PD – DLQ – 7


Ceiling diffusers
Order code DLQ

DLQ

DLQ – ZH – M – L / 500 / P1 – RAL ...

     

 Type  Accessories
DLQ Ceiling diffuser No entry: without accessories
L With lip seal (only with plenum box)
 Connection
A Diffuser face only  Nominal size [mm]
AR Vertical, with connecting frame 250
AG Vertical, with blades (not for nominal ​ 300
size 250) 400
C Vertical, with butterfly damper 500
ZH Horizontal, supply air, with plenum box 600
AH Horizontal, extract air, with plenum box 625

 Damper blade for volume flow rate balancing  Exposed surface


No entry: without damper blade No entry: powder-coated RAL 9010, pure ​
Only for connections ZH, AH white
M With damper blade P1 Powder-coated, specify RAL CLASSIC ​
MN With cords and pressure tap colour

Gloss level
RAL 9010 50 %
RAL 9006 30 %
All other RAL colours 70 %

Order example: DLQ-AK-M-L/500


Connection Horizontal, with plenum box
Damper blade for volume flow rate balancing With damper blade
Accessories With lip seal
Nominal size 500
Exposed surface RAL 9010, pure white, gloss level 50 %

PD – DLQ – 8 02/2017 – DE/en


Ceiling diffusers
Variants DLQ

DLQ/250 DLQ/300 DLQ/400 DLQ/500

DLQ/600 DLQ/625

DLQ-A Parts and characteristics


– Square diffuser face
Variant – Simple installation of the diffuser face due to ​
– Ceiling diffuser with square diffuser face central fixing screw with decorative cap
Nominal sizes
– 250, 300, 400, 500, 600, 625

DLQ-AR Parts and characteristics


– Square diffuser face
Variant – Connecting frame for installation of the diffuser ​
– Ceiling diffuser with square diffuser face into vertical ducts
– With connecting frame – Simple installation of the diffuser face due to ​
central fixing screw with decorative cap
Nominal sizes
– 250, 300, 400, 500, 600, 625

DLQ-C Parts and characteristics


– Square diffuser face
Variant – Connecting frame for installation of the diffuser ​
– Ceiling diffuser with square diffuser face into vertical ducts
– With connecting frame – Butterfly damper for volume flow rate balancing
– With butterfly damper – Simple installation of the diffuser face due to ​
central fixing screw with decorative cap
Nominal sizes
– 250, 300, 400, 500, 600, 625

DLQ-AG – Square diffuser face with fixed air control ​


blades
Variant – Connecting frame for installation of the diffuser ​
– Ceiling diffuser with square diffuser face into vertical ducts
– With connecting frame – Damper blade for volume flow rate balancing
– With opposed action blades – Simple installation of the diffuser face due to ​
central fixing screw with decorative cap
Nominal sizes
– 250, 300, 400, 500, 600, 625

Parts and characteristics

02/2017 – DE/en PD – DLQ – 9


Ceiling diffusers
Variants DLQ

DLQ-AK airflow through the diffuser face (supply air ​


variant)
Variant – Simple installation of the diffuser face due to ​
– Ceiling diffuser with square diffuser face central fixing screw with decorative cap
– With plenum box for horizontal duct connection – Damper blade for volume flow rate balancing ​
(optional)
Nominal sizes
– Pressure tap and cord-operated damper blade ​
– 250, 300, 400, 500, 600, 625
for volume flow rate balancing (optional)
Parts and characteristics – Lip seal (optional)
– Square diffuser face
Construction features
– Plenum box for horizontal duct connection
– Spigot suitable for circular ducts to EN 1506 or ​
– Square opening to accommodate the diffuser ​
EN 13180
face
– Equalising element that ensures a uniform ​

PD – DLQ – 10 02/2017 – DE/en


Ceiling diffusers
Dimensions and weight DLQ

DLQ-A

□Q

H₂
H₁ □Q₁

DLQ-A
□Q □Q1 H1 H2 m
Nominal size
mm mm mm mm kg
250 140 248 13 29 0.8
300 190 298 13 29 1.1
400 290 398 13 29 1.9
500 390 498 13 29 2.8
600 490 598 13 29 4.0
625 515 623 13 29 4.2

DLQ-AR

□Q
H₂

□Q₁
H₁

DLQ-AR
□Q □Q1 H1 H2 m
Nominal size
mm mm mm mm kg
250 143 248 13 52 1.0
300 193 298 13 52 1.4
400 293 398 13 52 2.3
500 393 498 13 52 3.3
600 493 598 13 52 4.6
625 518 623 13 52 4.8

02/2017 – DE/en PD – DLQ – 11


Ceiling diffusers
Dimensions and weight DLQ

DLQ-C

□Q

H₂

□Q₁
H₁

DLQ-C
□Q □Q1 H1 H2 m
Nominal size
mm mm mm mm kg
250 143 248 13 52 1.5
300 193 298 13 52 2.1
400 293 398 13 52 3.5
500 393 498 13 52 5.2
600 493 598 13 52 7.4
625 518 623 13 52 7.9

DLQ-AG

□Q
H₂

□Q₁
H₁

DLQ-AG
□Q □Q1 H1 H2 m
Nominal size
mm mm mm mm kg
250 143 248 13 95 1.3
300 193 298 13 95 1.8
400 293 398 13 95 3.1
500 393 498 13 95 4.6
600 493 598 13 95 6.5
625 518 623 13 95 7.2

PD – DLQ – 12 02/2017 – DE/en


Ceiling diffusers
Dimensions and weight DLQ

Square diffuser face with plenum box for horizontal duct connection

□Q₃ C

∅D
H₃

A
□Q₁

H₁
DLQ-AK
Plenum ​
□Q1 H1 □Q3 H3 ØD A C m
Nominal size box
mm mm mm mm mm mm mm kg
AK-Uni-​
250 248 13 216 250 158 139 50 3.0
008
AK-Uni-​
300 298 13 266 250 158 139 50 3.8
009
AK-Uni-​
400 398 13 372 295 198 164 50 6.4
002
AK-Uni-​
500 498 13 476 345 248 189 48 9.4
010
AK-Uni-​
600 598 13 567 410 313 222 50 13.2
011
AK-Uni-​
625 623 13 567 410 313 222 50 13.4
011
Weights apply to the supply air variant

02/2017 – DE/en PD – DLQ – 13


Ceiling diffusers
Product details DLQ

Diffuser face DLQ DLQ


Nominal ​ □Q1 □Q2 Aeff
size mm mm m²
250 248 198 0.0095
300 298 248 0.0175
400 398 348 0.0370

□Q₂
□Q₁ 500 498 448 0.0675
600 598 548 0.1100
625 623 573 0.1230

PD – DLQ – 14 02/2017 – DE/en


Ceiling diffusers
Installation examples DLQ

Installation in T-bar ceilings, arrangement in a ​ Installation in continuous ceilings


row

02/2017 – DE/en PD – DLQ – 15


Ceiling diffusers
Installation details DLQ

Installation and commissioning


– Preferably for rooms with a clear height up to ​
4.0 m
– Flush ceiling installation
– Horizontal or vertical duct connection
– If necessary, carry out volume flow rate ​
balancing with the damper blade

These are only schematic diagrams to illustrate ​


installation details.

Flush ceiling installation with square plenum ​


box

① Duct
② Suspension hole
③ Diffuser face

– Horizontal duct connection


– Four suspension holes
– Suspension with cords, wires or hangers, to be ​
provided by others

Diffuser face – sealing

X
④ X

① Plenum box
② Diffuser face
③ Seal
④ Ceiling tile

– The self-adhesive sealing tape (supplied) has to be ​


applied to the return edges of the plenum box by ​
others

PD – DLQ – 16 02/2017 – DE/en


Ceiling diffusers
Installation details DLQ

Diffuser face – central screw fixing

② ①

① Diffuser face
② Cross bar
③ Central fixing screw
④ Decorative cap

– Using the central fixing screw, fix the diffuser face to ​


the cross bar of the plenum box
– Attach the decorative cap

Ceiling systems Installation into grid ceilings Installation in continuous ceilings

– Fix the plenum box to the ceiling – Fix plenum box (including diffuser face, if necessary) ​
– The ceiling tile of the grid ceiling is independent of the ​ to the ceiling
ceiling diffuser – Adjust plasterboard ceiling tile as required
– Fix the diffuser face after the ceiling has been ​ – If necessary, fix the diffuser face after the ceiling has ​
completed been completed

Installation in T-bar ceilings

– Fix the plenum box to the ceiling


– The T-bar ceiling is independent of the ceiling diffuser
– Fix the diffuser face below the T-bars after the ceiling ​
has been completed

02/2017 – DE/en PD – DLQ – 17


Ceiling diffusers
Commissioning DLQ

Volume flow rate balancing


When several diffusers are connected to just one ​
volume flow controller, it may be necessary to ​
balance the volume flow rates.
– Ceiling diffusers with universal plenum box and ​
damper blade (variant -M): The diffuser face ​
can be removed to access the damper blade; ​
the damper blade can then be set to any ​
position between 0 and 90°
– Ceiling diffusers with universal plenum box, ​
damper blade and pressure tap (variant -MN): ​
The diffuser face need not be removed since ​
the damper blade can be set with two cords ​
(white and green).

Volume flow rate measurement


Ceiling diffusers with universal plenum box, ​
damper blade and pressure tap (variant -MN) ​
allow for volume flow rate balancing even with the ​
diffuser face in place.
– Connect the measuring tube to the digital ​
manometer
– Read the effective pressure
– Read the volume flow rate off the characteristic ​
or calculate it
– If necessary, adjust the damper blade position ​
with the cords

A characteristic is included with each AK-Uni ​


plenum box.

AK-Uni-...-MN Volume flow rate balancing AK-Uni-...-MN Volume flow rate balancing


① Damper blade ① Damper blade


② White cord for opening the damper blade ② Green cord for closing the damper blade

Open, 0° Closed, 90°

PD – DLQ – 18 02/2017 – DE/en


Ceiling diffusers
Commissioning DLQ

AK-Uni-...-MN volume flow rate measurement

① ②

X



X

① ②

① Measuring tube
② Pressure tap
③ Damper blade for volume flow rate balancing
④ White cord for opening the damper blade
⑤ Green cord for closing the damper blade
⑥ Digital manometer
⑦ Text label indicating plenum box variant

Volume flow rate calculation for air density ​ Volume flow rate calculation for other air ​
1.2 kg/m³ densities

 =C× ∆pw  =C× ∆pw × 1.2


ρ

02/2017 – DE/en PD – DLQ – 19


Ceiling diffusers
Basic information and nomenclature DLQ

Principal dimensions suspended ceiling to the lower edge of the d


​ iffuser
face
ØD [mm]
Outer diameter of the spigot H₂ [mm]
Height of a ceiling diffuser, from the lower edge of ​
ØD₁ [mm] the suspended ceiling to the upper edge of the ​
Outer diameter of a circular diffuser face spigot
ØD₂ [mm] H₃ [mm]
Diameter of a circular diffuser face style Height of a ceiling diffuser with plenum box, from ​
the lower edge of the suspended ceiling to the ​
ØD₃ [mm]
upper edge of the plenum box or of the spigot
Diameter of a circular plenum box
A [mm]
□Q₁ [mm]
Position of the spigot, defined by the distance of ​
Outer diameter of a square diffuser face
the spigot centre line to the lower edge of the ​
□Q₂ [mm] suspended ceiling
Dimensions of a square diffuser face style
C [mm]
□Q₃ [mm] Length of the spigot
Dimensions of a square plenum box
m [kg]
H₁ [mm] Weight
Distance (height) from the lower edge of the ​

Nomenclature supply air temperature minus room temperature

LWA [dB(A)] Δpt [Pa]
A-weighted sound power level of air-regenerated ​ Total differential pressure
noise
Aeff [m²]
 [m³/h] and [l/s] Effective air discharge area
Volume flow rate
All sound power levels are based on 1 pW.
Δtz [K]
Supply air to room air temperature difference, i.e. ​

PD – DLQ – 20 02/2017 – DE/en