Professional Documents
Culture Documents
Ceiling Diffusers: Type DLQ
Ceiling Diffusers: Type DLQ
Ceiling Diffusers: Type DLQ
Ceiling diffusers
Type DLQ
Type Page
DLQ General information DLQ – 2
Function DLQ – 3
Technical data DLQ – 4
Quick sizing DLQ – 5
Specification text DLQ – 7
Order code DLQ – 8
Variants DLQ – 9
Dimensions and weight DLQ – 11
Product details DLQ – 14
Installation examples DLQ – 15
Installation details DLQ – 16
Commissioning DLQ – 18
Basic information and nomenclature DLQ – 20
Construction features
– Spigot suitable for circular ducts to EN 1506 or
EN 13180
Schematic illustration of the DLQ, with plenum box for horizontal duct connection
⑤
⑥
④ ⑨
② ①
⑬ ⑩
⑫ ⑪
DLQ-A, DLQ-AR (supply air), sound power level and total differential pressure
Δpt LWA
Nominal size
l/s m³/h Pa dB(A)
20 72 3 <15
55 198 20 26
250
95 342 59 40
130 468 111 50
35 126 2 <15
95 342 18 24
300
155 558 47 38
210 756 87 50
75 270 2 <15
190 684 13 25
400
310 1116 35 38
430 1548 68 50
135 486 2 <15
295 1062 10 27
500
455 1638 23 39
615 2214 43 50
220 792 2 15
380 1440 8 34
600
535 1980 15 43
690 2484 24 50
250 900 2 20
400 1440 6 34
625
550 1980 12 43
700 2520 19 50
DLQ-AK (supply air), sound power level and total differential pressure
Damper blade position
0° 45° 90°
Nominal size
Δpt LWA Δpt LWA Δpt LWA
l/s m³/h Pa dB(A) Pa dB(A) Pa dB(A)
20 72 5 <15 5 <15 10 <15
35 126 14 22 16 22 31 25
250
60 216 41 38 46 38 92 41
90 324 92 51 104 51 208 53
35 126 6 9 9 11 20 19
70 252 26 30 37 32 81 39
300
100 360 53 41 75 43 165 49
135 486 96 51 137 54 301 59
75 270 9 13 15 21 33 30
130 468 28 31 46 39 98 45
400
185 666 56 42 93 50 198 57
235 846 90 50 150 61 319 67
135 486 12 16 15 19 48 35
210 756 28 32 36 35 116 49
500
285 1026 52 42 66 45 213 58
360 1296 83 50 105 53 340 65
220 792 12 18 19 26 49 35
330 1188 26 32 44 39 111 47
600
440 1584 46 42 78 49 197 57
545 1962 71 50 119 58 303 66
250 900 14 21 26 33 64 39
330 1188 24 31 46 42 111 47
625
410 1476 37 39 70 49 171 55
575 2070 74 50 138 61 336 74
Sizing example
Given data
= 300 l/s (1280 m3/h)
Square ceiling diffuser, steel, with fixed air control
blades
Maximum sound power level 40 dB(A) with
damper blade position 45°
Four-way air discharge
Quick sizing
Type DLQ
Nominal sizes: 600, 625
Selected: DLQ/600
Ceiling diffusers with square diffuser face. Supply – Lip seal made of rubber
air and extract air variants for comfort zones. – Attachments are dip coated RAL 9005, jet
Diffuser face with fixed air control blades for black
horizontal four-way air discharge. For installation – Diffuser face powder-coated RAL 9010, pure
into all types of suspended ceilings. white
Ready-to-install component which consists of the – P1: Powder-coated, RAL CLASSIC colour
galvanised sheet steel diffuser face with fixed air
control blades, a diffuser front frame with Technical data
perimeter seal and connecting frame, opposed – Nominal sizes: 250, 300, 400, 500, 600,
action blades, butterfly damper or a plenum box. 625 mm
Diffuser face suitable for central screw fixing. – Minimum volume flow rate: 20 – 250 l/s or
Sound power level of the air-regenerated noise 72 – 900 m³/h
measured according to EN ISO 5135. – Maximum volume flow rate, with
LWA ≅ 50 dB(A): 575 – 700 l/s or
Special characteristics 2070 – 2520 m³/h
– Horizontal four-way supply air discharge – Supply air to room air temperature difference:
– Diffuser face made of galvanised sheet steel –10 to +10 K
– For all types of ceiling systems
– Horizontal or vertical duct connection Sizing data
– _____________ _______________________
Materials and surfaces [m³/h]
– Diffuser face, connecting frame and butterfly – Δpt____________ _______________________
damper made of sheet steel [Pa]
– AK: Plenum box and cross bar made of Air-regenerated noise
galvanised sheet steel – LWA____________ _______________________
– X: Plenum box made of plastic and galvanised [dB(A)]
sheet steel
DLQ
Type Accessories
DLQ Ceiling diffuser No entry: without accessories
L With lip seal (only with plenum box)
Connection
A Diffuser face only Nominal size [mm]
AR Vertical, with connecting frame 250
AG Vertical, with blades (not for nominal 300
size 250) 400
C Vertical, with butterfly damper 500
ZH Horizontal, supply air, with plenum box 600
AH Horizontal, extract air, with plenum box 625
Gloss level
RAL 9010 50 %
RAL 9006 30 %
All other RAL colours 70 %
DLQ/600 DLQ/625
DLQ-A
□Q
H₂
H₁ □Q₁
DLQ-A
□Q □Q1 H1 H2 m
Nominal size
mm mm mm mm kg
250 140 248 13 29 0.8
300 190 298 13 29 1.1
400 290 398 13 29 1.9
500 390 498 13 29 2.8
600 490 598 13 29 4.0
625 515 623 13 29 4.2
DLQ-AR
□Q
H₂
□Q₁
H₁
DLQ-AR
□Q □Q1 H1 H2 m
Nominal size
mm mm mm mm kg
250 143 248 13 52 1.0
300 193 298 13 52 1.4
400 293 398 13 52 2.3
500 393 498 13 52 3.3
600 493 598 13 52 4.6
625 518 623 13 52 4.8
DLQ-C
□Q
H₂
□Q₁
H₁
DLQ-C
□Q □Q1 H1 H2 m
Nominal size
mm mm mm mm kg
250 143 248 13 52 1.5
300 193 298 13 52 2.1
400 293 398 13 52 3.5
500 393 498 13 52 5.2
600 493 598 13 52 7.4
625 518 623 13 52 7.9
DLQ-AG
□Q
H₂
□Q₁
H₁
DLQ-AG
□Q □Q1 H1 H2 m
Nominal size
mm mm mm mm kg
250 143 248 13 95 1.3
300 193 298 13 95 1.8
400 293 398 13 95 3.1
500 393 498 13 95 4.6
600 493 598 13 95 6.5
625 518 623 13 95 7.2
Square diffuser face with plenum box for horizontal duct connection
□Q₃ C
∅D
H₃
A
□Q₁
H₁
DLQ-AK
Plenum
□Q1 H1 □Q3 H3 ØD A C m
Nominal size box
mm mm mm mm mm mm mm kg
AK-Uni-
250 248 13 216 250 158 139 50 3.0
008
AK-Uni-
300 298 13 266 250 158 139 50 3.8
009
AK-Uni-
400 398 13 372 295 198 164 50 6.4
002
AK-Uni-
500 498 13 476 345 248 189 48 9.4
010
AK-Uni-
600 598 13 567 410 313 222 50 13.2
011
AK-Uni-
625 623 13 567 410 313 222 50 13.4
011
Weights apply to the supply air variant
□Q₂
□Q₁ 500 498 448 0.0675
600 598 548 0.1100
625 623 573 0.1230
① Duct
② Suspension hole
③ Diffuser face
X
④ X
① Plenum box
② Diffuser face
③ Seal
④ Ceiling tile
② ①
① Diffuser face
② Cross bar
③ Central fixing screw
④ Decorative cap
– Fix the plenum box to the ceiling – Fix plenum box (including diffuser face, if necessary)
– The ceiling tile of the grid ceiling is independent of the to the ceiling
ceiling diffuser – Adjust plasterboard ceiling tile as required
– Fix the diffuser face after the ceiling has been – If necessary, fix the diffuser face after the ceiling has
completed been completed
AK-Uni-...-MN Volume flow rate balancing AK-Uni-...-MN Volume flow rate balancing
①
①
① ②
③
X
⑦
④
⑤
X
① ②
① Measuring tube
② Pressure tap
③ Damper blade for volume flow rate balancing
④ White cord for opening the damper blade
⑤ Green cord for closing the damper blade
⑥ Digital manometer
⑦ Text label indicating plenum box variant
Volume flow rate calculation for air density Volume flow rate calculation for other air
1.2 kg/m³ densities
LWA [dB(A)] Δpt [Pa]
A-weighted sound power level of air-regenerated Total differential pressure
noise
Aeff [m²]
[m³/h] and [l/s] Effective air discharge area
Volume flow rate
All sound power levels are based on 1 pW.
Δtz [K]
Supply air to room air temperature difference, i.e.