Professional Documents
Culture Documents
Differentialtestreport: Test Parameters
Differentialtestreport: Test Parameters
Differentialtestreport: Test Parameters
Test Parameters :
Test Item : Proportion Brake Fixed-Point Test
Harmonic Brake Coefficient : 0.200 Harmonic Number : 1
Harmonic Phase Angle : 45.000
I1 Definition
Output Mode : IA, IB, IC Three-Phase Symmetry Frequency : Base Wave Phase : 0.000
I2 Definition
Output Mode : IA, IB, IC Three-Phase Symmetry Frequency : Base Wave Phase : 210.000
Digital Input : Contact 1(Normally Open Contact)
Digital Output Close : YES
Status Before Switching Value Reverse :
DO.1 Open DO.2 Open DO.3 Open DO.4 Open
Reverse Time : 0.000s Hold Time : 1.000s
Contact Chatter Free Time : 10.000s
Test Result :
Test Items Ir(A) Id(A) Test Act.Time Brake Coefficient(k)
√ Proportion Brake Fixed-Point Test 14.304 11.319 Trip
√ Proportion Brake Fixed-Point Test 7.988 6.405 No Action
√ Proportion Brake Fixed-Point Test 3.715 3.644 Trip
√ Proportion Brake Fixed-Point Test 6.595 2.429 No Action
√ Proportion Brake Fixed-Point Test 13.932 6.350 Trip
√ Proportion Brake Fixed-Point Test 18.112 9.718 No Action
Test Chart :