NF M87-202 EGSF
Collectively Screened, Unarmoured, LSZH Cable
APPLICATION STANDARDS
These cables are designed for safe use in petroleum and NF M 87 - 202, UTE C 32-014, EN 60331-21
petrochemical units particularly for the transmission of AC
or DC analogue signals. Suitable for aliphatic hydrocarbons Flame Retardant according to: IEC/EN 60332-1-2,
resistance applications. IEC/EN 60332-3-24
CHARACTERISTICS
ISO/IEC 17025 LABORATORY TESTED
Voltage Rating (Uo/U)
This product is subject to the Quality Assurance protocols of The Cable Lab®,
300/500V
an ISO/IEC 17025 accredited cable testing laboratory. Testing includes vertical
flame, conductor resistance, tensile & elongation, and dimensional consistency,
Temperature Range verified to published standards and approved product drawings.
Installation: 5°C to +50ºC
Operation: +90ºC ISO/IEC
17025
Accredited
Testing
Laboratory
CONSTRUCTION 8578
Conductor
Class 1 solid copper conductor
Class 2 stranded copper conductor REGULATORY COMPLIANCE
This cable is compliant with European Regulation EN 50575, the Construction
Insulation Products Regulation.
PVC (Polyvinyl Chloride)
Binder Tape
PET (Polyester Tape)
This cable meets the requirements of the Low Voltage Directive 2014/35/EU
Collective Screen and the RoHS Directive 2011/65/EU. RoHS compliance has been tested and
AlL/PET (Aluminium/Polyester Tape) confirmed by The Cable Lab® as meeting the requirements of the BSI RoHS
Trusted KitemarkTM.
Sheath
PVC (Polyvinyl Chloride) RoHS Trusted
KITEMARK™
DIMENSIONS
ELAND PART NO. NO. OF NOMINAL CROSS SECTIONAL AREA NOMINAL OVERALL DIAMETER
PAIRS/TRIPLE mm2 mm
P = Pairs
Q = Quad
T = Triple
CONDUCTORS
NOMINAL CROSS SECTIONAL AREA CONDUCTOR CLASS MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C
mm2 ohms/km
0.5 1 37.9
0.88 2 21.6
1.5 1 12.5
ELECTRICAL CHARACTERISTICS
NOMINAL CROSS CONDUCTOR CLASS MAXIMUM MUTUAL CAPACITANCE
SECTIONAL AREA pF/m
mm2
Between Conductors Between Conductors and Screens
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is
believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.