Low Voltage Capacitor Contactors for capacitor Switching

AX Contactor Range AF Contactor Range

www.multipletrading.net Hotline: 01730054016


89 Motijheel C/A, Lucky Chamber (3rd floor, Room #61), Dhaka-1000, Bangladesh. Tel: (02) 9559692, Fax: (02)9566596 E-mail: info@multipletrading.net
Low Voltage Capacitor
• In compliance to IS: 13340/41 & IEC 60831-1&2
• Dry type design
• Dielectric: Polypropylene film
• Extruded cylindrical aluminium can with stud
• Overpressure disconnector
• Elements inside an extruded cylindrical aluminium can, delta connected internally
• Provided with discharge resistor
• Three phase
• Self-healing technology
• Naturally air cooled
• For power factor correction in indoor applications
• Very low losses – Total losses including discharge resistors are less than 0.5 W/kVAR

Range Cylinderical type Box-type


Voltage [V] 415/440
Range [kVar] 1 – 25
Frequency [Hz] 50
Connection 3 Phase as standard construction
Discharge resistor In-built as part of the capacitor
Installation Indoor
Mounting parts Threaded stud at bottom of can Mounting bracket at rear plate
Earth Extruded stud Earth connection on the enclosure fixation
Mean life expectancy 100,000 hours (max 5,000 100,000 hours (max 5,000
switching / year) switching / year)

Contactors for Capacitor Switching


UA..RA 3-pole Contactors for Capacitor Switching
Unlimited Peak Current Î
Application
The UA..RA contactors can be used in installations in which the peak current far exceeds 100 times nominal rms current. The contactors are delivered
complete with their damping resistors and must be used without additional inductances (see table below).
The capacitors must be discharged (maximum residual voltage at terminals ≤ 50 V) before being re-energized when the contactors are making.
Their electrical durability is 250 000 operating cycles for Ue < 500 V and 100 000 operating cycles for 500 V < Ue < 690 V.

UA..RA Contactors for Capacitor Switching (UA 16..RA to UA 110..RA) with insertion of damping resistors.
The insertion of damping resistors protects the contactor and the capacitor from the highest inrush currents.
1SBC5 9144 4F0302
1SBC5 8776 4F0301
1SBC5 8777 4F0301
1SBC5 8779 4F0301

Selection Table according to IEC


Type Power in kvar – 50/60 Hz (AC-6b) Max. permissible gG type
230/240 V 400/415 V 440 V 500/550 V 690 V peak current fuses
40°C 55°C 70°C 40°C 55°C 70°C 40°C 55°C 70°C 40°C 55°C 70°C 40°C 55°C 70°C Î A max (*)
UA 16-30-10 RA 8 7.5 6 12.5 12.5 10 15 13 11 18 16 12.5 22 21 17 80
UA 26-30-10 RA 12.5 11.5 9 22 20 15.5 24 20 17 30 25 20 35 31 26 125
UA 30-30-10 RA 16 16 11 30 27.5 19.5 32 30 20.5 34 34 25 45 45 32 200
UA 50-30-00 RA 25 24 20 40 40 35 50 43 37 55 50 46 72 65 60 Unlimited 200
UA 63-30-00 RA 30 27 23 50 45 39 55 48 42.5 65 60 50 80 75 65 200
UA 75-30-00 RA 35 30 25 60 50 41 65 53 45 75 65 55 100 80 70 200
UA 95-30-00 RA 40 35 30 70 60 53 75 65 58 85 75 70 120 105 85 250
PAGE : 02

UA 110-30-00 RA 45 40 35 80 70 60 85 75 70 95 82 78 130 110 100 250


( ) The fuse ratings given in the column represent the maximum ratings ensuring type 1 coordination according to the definition of standard IEC 60947-4-1.
Main accessories
Contactor and main accessories (other accessories available)

VES AX contactor
Interlock unit

RVS, RCS
Surge suppressor

A2
A1

AX contactor

TEF5
Electronic timer
BX4-CA
Protective cover

CA5X
4-pole auxiliary
contact block
CAL5X
2-pole auxiliary
contact block CA5X
1-pole auxiliary
contact block
TA
Thermal overload relay

AF96 ...... AF750 3pole Contactors


Technical data
Main pole - Utilization characteristics according to IEC
Contactor types AC / DC operated AF96 AF116 AF140 AF146 AF190 AF205 AF265 AF305 AF370 AF400 AF460 AF580 AF750
Standards IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1 IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max. 690 V 690 V 1000 V 1000 V 1000 V 1000 V 1000 V 1000 V 1000 V
Rated frequency (without derating) 50 / 60 Hz 50/60 Hz
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C 130 A 160 A 200 A 225 A 275 A 350 A 400 A 500 A 600 A 600 A 700 A 800 A 1050 A
With conductor cross-sectional area 50 mm² 70 mm2 95 mm2 95 mm2 150 mm2 240 mm2 (3) 240 mm2 300 mm2 (4) 2 x 185 mm2(4) 2x185 mm² 2x240 mm² 2x240 mm² 800 mm² (4)
AC-1 Utilization category
For air temperature close to contactor
Ie / Rated operational current AC-1 θ ≤ 40 °C 130 A 160 A 200 A 225 A 275 A 350 A 400 A 500 A 600 A 600 A 700 A 800 A 1050 A
Ue max. ≤ 690 V, 50/60 Hz θ ≤ 60 °C 105 A 145 A 175 A 200 A 250 A 300 A 350 A 400 A 500 A 500 A 600 A 700 A 875 A
θ ≤ 70 °C 90 A 130 A 160 A 175 A 200 A 240 A 290 A 325 A 400 A 400 A 480 A 580 A 720 A
With conductor cross-sectional area 50 mm² — — 225 A 250 A 275 A 350 A 375 A 400 A 600 A 700 A 800 A 1000 A
AC-3 Utilization category — — 200 A 225 A 250 A 300 A 325 A 350 A 500 A 600 A 700 A 875 A
For air temperature close to contactor θ ≤ 60 °C — — 175 A 185 A 200 A 240 A 260 A 290 A 400 A 480 A 580 A 720 A
Ie / Max. rated operational current AC-3 (1) 70 mm2 95 mm2 95 mm2 150 mm2 240 mm2 (3) 240 mm2 300 mm2 (4) 2 x 185 mm 2(4) 2x185 mm² 2x240 mm² 2x240 mm² 800 mm² (4)
220-230-240 V 96 A
380-400 V 96 A
415 V 96 A
M 3-phase motors 440 V 96 A 116 A 140 A 146 A 190 A 205 A 265 A 305 A 370 A 400 A 460 A 580 A 750 A
3 500 V 80 A 116 A 140 A 146 A 190 A 205 A 265 A 305 A 370 A 400 A 460 A 580 A 750 A
690 V 57 A 116 A 140 A 146 A 190 A 205 A 265 A 305 A 370 A 400 A 460 A 580 A 750 A
1000 V 30A 116 A 140 A 146 A 190 A 205 A 265 A 305 A 370 A 400 A 460 A 580 A 750 A
Rated operational power AC-3 (1) 110 A 130 A 130 A 135 A 165 A 250 A 290 A 315 A 400 A 460 A 580 A 750 A
220-230-240 V 25 kW 65 A 80 A 93 A 135 A 165 A 250 A 290 A 315 A 350 A 400 A 500 A 650 A
380-400 V 45 kW — — 60 A 85 A 100 A 100 A 100 A 100 A 155 A 200 A 250 A 300 A
1500 r.p.m. 50 Hz 415 V 55 kW
M 1800 r.p.m. 60 Hz 440 V 55 kW 30 kW 37 kW 45 kW 55 kW 55 kW 75 kW 90 kW 110 kW 110 kW 132 kW 160 kW 220 kW
3 3-phase motors 500 V 55 kW 55 kW 75 kW 75 kW 90 kW 110 kW 132 kW 160 kW 200 kW 200 kW 250 kW 315 kW 400 kW
690 V 55 kW 55 kW 75 kW 75 kW 90 kW 110 kW 132 kW 160 kW 200 kW 220 kW 250 kW 355 kW 425 kW
1000 V 40 kW 75 kW 90 kW 90 kW 110 kW 132 kW 160 kW 160 kW 200 kW 220 kW 250 kW 355 kW 450 kW
Rated making capacity AC-3 75 kW 90 kW 90 kW 90 kW 110 kW 200 kW 200 kW 250 kW 250 kW 315 kW 400 kW 520 kW
Rated breaking capacity AC-3 55 kW 75 kW 90 kW 132 kW 160 kW 200 kW 250 kW 315 kW 315 kW 355 kW 500 kW 600 kW
AC-8a Utilization category — — 75 kW 110 kW 132 kW 132 kW 132 kW 132 kW 220 kW 280 kW 355 kW 400 kW
(without thermal overload relay - Ue 400 V 50/60 Hz - θ ≤ 40 °C) 10 x Ie AC-3 acc. to IEC 60947-4-1 10 x Ie AC-3 acc. to IEC 60947-4-1
Ie / Rated operational current AC-8a 120 A 8 x Ie AC-3 acc. to IEC 60947-4-1 8 x Ie AC-3 acc. to IEC 60947-4-1
Rated operational power AC-8a 65 kW
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded (2) 250 A 315 A 315 A 355 A 400 A 500 A 500 A 630 A
Ue ≤ 500 V AC - gG type fuse 200 A 1300 A 1460 A 1460 A 1900 A 2050 A 2650 A 3050 A 3700 A 630 A 800 A 1000 A 1000 A
Rated short-time withstand current Icw 1s 1200 A 928 A 1168 A 1168 A 1520 A 1640 A 2120 A 2440 A 2960 A 4600 A 4600 A 7000 A 7000 A
at 40 °C ambient temperature, 10 s 780 A 536 A 674 A 674 A 878 A 947 A 1224 A 1409 A 1709 A 4400 A 4400 A 6400 A 6400 A
in free air from a cold state 30 s 450 A 379 A 477 A 477 A 621 A 670 A 865 A 996 A 1208 A 3100 A 3100 A 4500 A 4500 A
1 min 300 A 160 A 200 A 225 A 275 A 350 A 400 A 500 A 600 A 2500 A 2500 A 3500 A 3500 A
15 min 140 A 840 A 840 A 1300 A 1300 A
Maximum breaking capacity 2000 A 3000 A 3000 A 3300 A 3500 A 3800 A 4600 A 5000 A
cos φ = 0.45 at 440 V 1150 A 1000 A 1500 A 1500 A 2200 A 2500 A 3300 A 3800 A 4000 A 4000 A 5000 A 6000 A 7500 A
at 690 V 750 A 12 W 18 W 23 W 15 W 25 W 32 W 50 W 72 W 3500 A 4500 A 5000 A 7000 A
Power dissipation per pole Ie / AC-1 8.2 W 6W 9W 10 W 7W 8W 14 W 19 W 27 W 30 W 42 W 32 W 50 W
Ie / AC-3 4.5 W 300 cycles/h 16 W 21 W 17 W 28 W
Max. electrical switching frequency AC-1 300 cycles/h 300 cycles/h 300 cycles/h
AC-3 150 cycles/h 300 cycles/h 300 cycles/h
PAGE : 03

AC-2, AC-4 60 cycles/h 60 cycles/h


(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
(2) For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".
AX09 ... AX80 3-pole contactors
Technical data
Main pole - Utilization characteristics according to IEC
Contactor types AC operated AX09 AX12 AX18 AX25 AX32 AX40 AX50 AX65 AX80
Standards IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1 IEC 60947-1 / 60947-4-1
Rated operational voltage Ue max. 690 V 690 V
Rated frequency limits 25 ... 400 Hz 25 ... 400 Hz
Rated frequency (without derating) 50 / 60 Hz 50 / 60 Hz
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C 24 A 26 A 28 A 32 A 65 A 65 A 100 A 125 A 125 A
With conductor cross-sectional area 4 mm² 4 mm² 4 mm² 6 mm² 16 mm² 16 mm² 35 mm² 50 mm² 50 mm²
AC-1 Utilization category
For air temperature close to contactor
Ie / Rated operational current AC-1 θ ≤ 40 °C 22 A 25 A 27 A 32 A 55 A 60 A 100 A 115 A 125 A
Ue max. ≤ 690 V, 50/60 Hz θ ≤ 55 °C 22 A 22 A 25 A 27 A 55 A 60 A 85 A 95 A 105 A
θ ≤ 70 °C 18 A 18 A 20 A 23 A 39 A 42 A 70 A 80 A 85 A
With conductor cross-sectional area 2.5 mm² 2.5 mm² 4 mm² 6 mm² 10 mm² 16 mm² 35 mm² 50 mm² 50 mm²
AC-3 Utilization category
For air temperature close to contactor θ ≤ 55 °C
Ie / Max. rated operational current AC-3 (1)
220-230-240 V 9 A 12 A 18 A 25 A 32 A 40 A 53 A 65 A 80 A
380-400 V 9 A 12 A 18 A 25 A 32 A 40 A 50 A 65 A 80 A
M 415 V 9 A 12 A 18 A 25 A 32 A 40 A 50 A 65 A 80 A
3-phase motors
3 440 V 9 A 9A 12 A 16 A 32 A 37 A 45 A 65 A 70 A
500 V 9 A 9A 12 A 14 A 28 A 33 A 45 A 55 A 65 A
690 V 7 A 7A 9A 10 A 21 A 25 A 35 A 43 A 46 A
Rated operational power AC-3 (1)
220-230-240 V 2.2 kW 3 kW 4 kW 6.5 kW 9 kW 11 kW 15 kW 18.5 kW 22 kW
1500 r.p.m. 50 Hz 380-400 V 4 kW 5.5 kW 7.5 kW 11 kW 15 kW 18.5 kW 22 kW 30 kW 37 kW
M 415 V 4 kW 5.5 kW 9 kW 11 kW 15 kW 18.5 kW 25 kW 37 kW 40 kW
1800 r.p.m. 60 Hz
3 440 V 4 kW 4 kW 5.5 kW 9 kW 18.5 kW 22 kW 25 kW 37 kW 40 kW
3-phase motors
500 V 5.5 kW 5.5 kW 7.5 kW 9 kW 18.5 kW 22 kW 30 kW 37 kW 45 kW
690 V 5.5 kW 5.5 kW 7.5 kW 9 kW 18.5 kW 22 kW 30 kW 37 kW 40 kW
Rated making capacity AC-3 10 x Ie AC-3 acc. to IEC 60947-4-1 10 x Ie AC-3 acc. to IEC 60947-4-1
Rated breaking capacity AC-3 8 x Ie AC-3 acc. to IEC 60947-4-1 8 x Ie AC-3 acc. to IEC 60947-4-1
AC-8a Utilization category
(without thermal overload relay - Ue 400 V 50/60 Hz - θ ≤ 40 °C)
Ie / Rated operational current AC-8a 12 A 16 A 22 A 30 A 40 A 50 A 63 A 85 A 95 A
Rated operational power AC-8a 5.5 kW 5.5 kW 7.5 kW 11 kW 20 kW 22 kW 30 kW 45 kW 45 kW
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded (2)
Ue ≤ 500 V AC - gG type fuse 25 A 25 A 32 A 32 A 63 A 63 A 100 A 125 A 160 A
Rated short-time withstand current Icw 1 s 250 A 250 A 280 A 300 A 600 A 600 A 1000 A 1000 A 1000 A
at 40 °C ambient temperature, 10 s 100 A 100 A 120 A 140 A 400 A 400 A 650 A 650 A 650 A
in free air from a cold state 30 s 60 A 60 A 70 A 80 A 225 A 225 A 370 A 370 A 370 A
1 min 50 A 50 A 55 A 60 A 150 A 150 A 250 A 250 A 250 A
15 min 26 A 26 A 28 A 30 A 65 A 65 A 110 A 135 A 135 A
Maximum breaking capacity
cos Ø = 0.45 at 440 V 250 A 250 A 250 A 250 A 820 A 820 A 1300 A 1300 A 1300 A
at 690 V 90 A 90 A 90 A 90 A 340 A 340 A 630 A 630 A 630 A
Power dissipation per pole Ie / AC-1 0.8 W 0.8 W 1W 1.2 W 2.5 W 3W 5W 6.5 W 7W
Ie / AC-3 0.1 W 0.1 W 0.2 W 0.35 W 0.9 W 1.3 W 1.3 W 1.5 W 2W
Electrical durability (1x106) 400/415V, AC-3 1.5 1.5 1.5 1.3 1.5 1.5 1.2 1.2 1.1
Max. electrical switching frequency AC-1 600 cycle/h 600 cycle/h
AC-3 1200 cycle/h 600 cycle/h
Mechanical durability
Number of operating cycles 10 millions operating cycles 10 millions operating cycles
3600 cycles/h
Max. switching frequency 3600 cycles/h
(1) For the corresponding kW/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
(2) For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".