Doc.No.: QM5611/ID-TS/1 of 7.Rev.

00

INTERIM INSPECTION REPORT


of

AEON MALL DELTAMAS PROJECT


PT AMSL DELTAMAS

October 11th, 2022

Approved by :
ME Manager Technical Director
Doc.No.: QM5611/ID-TS/6 of 7 Rev.00
Page :
INTERIM INSPECTION REPORT
PT AMSL DELTAMAS
AEON MALL DELTAMAS PROJECT Inspected by : Helmi, Hiryanur
October 11th, 2022
Reported by : Dadan
1
Case number: 1 Location of Defect : GF Zone A CL A 10 / AJ
Grade :
Drag the repair photo here :

Comment: Comment:
Don’t use this material for close hole of pipe, please Already use dop PVC to close the hole STATUS
use dop PVC to close the hole

Case number: 2 Location of Defect : GF Zone A CL A 10 / AJ


Grade :
Drag the repair photo here :

Comment: Comment:
Install concrete cussion ( every 2 meter ) to support Already add concrete cushion STATUS
the pipe

Case number: 3 Location of Defect : 1st FL Zone A A12 / AC-AD


Grade :
Drag the repair photo here :

Comment: Comment:
The cable can't touch the floor, please hang this Cable roll move the position from floor to STATUS
cable or move the temporary fabrication of cable the nearest column above the floor.
rack near position of panel
The cable can't touch the floor, please hang this Cable roll move the position from floor to
cable or move the temporary fabrication of cable the nearest column above the floor.
rack near position of panel
Doc.No.: QM5611/ID-TS/6 of 7 Rev.00
Page :
INTERIM INSPECTION REPORT
PT AMSL DELTAMAS
AEON MALL DELTAMAS PROJECT Inspected by : Helmi, Hiryanur
October 11th, 2022
Reported by : Dadan
2
Case number: 4 Location of Defect : 1st FL Zone A CL A8-A9/AD-AE
Grade :
Drag the repair photo here :

Comment: Comment:
Install bounding grounding at join cable rack / tray This item still in discussion between STATUS
Kinden and Takenaka.

Case number: 5 Location of Defect : 1st FL Zone A CL A8-A9/AD-AE


Grade :
Drag the repair photo here :

Comment: Comment:
For Extra Low Voltage Cable, better to provide with ELV colour installation cable is follow our STATUS
different colour for easy to check and control each approval material. UTP cable colour is
electronic system blue & STP AWG cable colour is black.

Case number: 6 Location of Defect : Zone C BF CL B8-B9


Grade :
Drag the repair photo here :

GOOD POINT

Comment: Comment:
Bonding grounding for cable rack/tray already STATUS
installed with good connection ( use lock washer).
Please use for all bounding grounding cable rack
Bonding grounding for cable rack/tray already
installed with good connection ( use lock washer).
Please use for all bounding grounding cable rack
Doc.No.: QM5611/ID-TS/6 of 7 Rev.00
Page :
INTERIM INSPECTION REPORT
PT AMSL DELTAMAS
AEON MALL DELTAMAS PROJECT Inspected by : Helmi, Hiryanur
October 11th, 2022
Reported by : Dadan
3
Case number: 7 Location of Defect : Zone C BF CL B10
Grade :
Drag the repair photo here :

Comment: Comment:
Please check installation of c channel parking It is enough to install fix support at beam STATUS
system, if not enaough use hanging support please for c-channel parking system. No need
add horizontal fix support at the coloumn to prevent to install fix support at column.
cable rack from swing

Case number: 8 Location of Defect :


Grade :
Drag the repair photo here :

Comment: Comment:
STATUS

Case number: 9 Location of Defect :


Grade :
Drag the repair photo here :

Comment: Comment:
STATUS
Doc.No.: QM5611/ID-TS/7 of 7 Rev.00
PT. TAKENAKA INDONESIA
LIST OF INSPECTION RESULT

Project Name : Aeon Mall Deltamas Project Page 1 of 1


Client Name : PT AMSL Deltamas Date of inspectio : October 11th, 2022

No. Location Case Remark

Don’t use this material for close hole of pipe, please use dop
1 GF Zone A CL A 10 / AJ
PVC to close the hole

2 GF Zone A CL A 10 / AJ Install concrete cussion ( every 2 meter ) to support the pipe

3
1st FL Zone A A12 / AC- The cable can't touch the floor, please hang this cable or move
AD the temporary fabrication of cable rack near position of panel

4 BF Zone C CL B10 Install horizontal fix Support for c chanel every coloumn

5
1st FL Zone A CL A8- For Extra Low Voltage Cable, better to provide with different
A9/AD-AE colour for easy to check and control each electronic system
Bonding grounding for cable rack/tray already installed with
6 Zone C BF CL B8-B9 good connection ( use lock washer). Please use for all bounding
grounding cable rack
Please check installation of c channel parking system, if not
7 Zone C BF CL B10 enaough use hanging support please add horizontal fix support
at the coloumn to prevent cable rack from swing
Doc.No.: QM5611/ID-TS/7 of 7 Rev.00
PT. TAKENAKA INDONESIA
LIST OF INSPECTION RESULT

Project Name : Aeon Mall Deltamas Project Page 1 of 1


Client Name : PT AMSL Deltamas Date of inspectio : October 11th, 2022

No. Location Case Remark