Professional Documents
Culture Documents
BNWAS IS - Steisohn - A006-6
BNWAS IS - Steisohn - A006-6
A006.6
Revision
The following table lists the amendments to this user's manual which led to a new
revision.
Amendments Date Revision Author Approved
Created 24-03-06 1.000 H. Fischer R. Rober
Extension of Watch Alarm
29-03-11 1.001 B. Meinken J. Brackmann
System by Motion Sensor
Revised 01-06-11 1.002 H. Fischer J. Brackmann
Safety Distance to
23-06-11 1.003 H. Fischer J. Brackmann
Compass Added
BNWAS Connection
04-07-11 1.004 H. Fischer J. Brackmann
Drawing exchanged
Terminal X1 4,5
Connection Type
Changed
Divided in 3 Parts: 05-10-11 1.005 H.Fischer J. Brackmann
User's Manual & Drawings
User's Manual
Drawings
GL Logo added
Personal Alarm System is 23.07.13 1.006 M. Reitinger L. Biskup
optional
Text correction
Expansion of chapter 31.10.13 1.007 M. Reitinger L. Biskup
“Test and Repair”
Table of Contents
1 Introduction ................................................................................................................... 1
1.1 Priority of the User's Manual ................................................................................. 1
1.2 Purpose of Application .......................................................................................... 1
1.3 Safety Instructions ................................................................................................ 1
1.4 Designated use ..................................................................................................... 2
1.4.1 Target Group ................................................................................................ 2
1.4.2 Qualified Personnel ...................................................................................... 2
2 Engineering for an Alarm System ................................................................................. 3
2.1 Design of a Watch Alarm System ......................................................................... 3
2.2 Components of a Watch Alarm System ................................................................ 4
2.3 Components of a Personnel Alarm System .......................................................... 6
3 Installation of an Alarm System .................................................................................... 7
3.1 General Preparations ............................................................................................ 7
3.2 Installing the Components for a Watch Alarm System ......................................... 8
3.2.1 Installing the Operation Module .................................................................... 8
3.2.2 Installing the Terminal Module ...................................................................... 9
3.2.3 Installing the Alerting Elements ................................................................... 16
3.2.4 Installation of a Sensor Device ................................................................... 16
3.2.5 Installing the PCB Module ........................................................................... 17
3.2.6 Multiple Installations of PIR Motion Sensors ............................................... 17
3.3 Installing Components for a Personnel Alarm System ........................................ 17
3.3.1 Installing the Operation Module .................................................................. 17
3.3.2 Installing the Terminal Module .................................................................... 18
3.3.3 Installing the Alerting Elements ................................................................... 18
4 Commissioning the Alarm System .............................................................................. 19
5 Function and Operating .............................................................................................. 21
5.1 Functions of the Alarm Systems ......................................................................... 21
5.1.1 Dormancy Timer Function .......................................................................... 21
5.1.2 Alarm Function ........................................................................................... 22
5.1.3 Reset Function ........................................................................................... 22
5.1.4 Emergency Call .......................................................................................... 23
5.1.5 Alarm Profiles and Parameters ................................................................... 24
5.2 Operating the Watch Alarm System ................................................................... 25
5.3 Operational Components .................................................................................... 26
5.3.1 Functions of Terminal Module .................................................................... 26
5.3.2 Functions of Operation Module ................................................................... 28
5.3.3 NMEA Interface ......................................................................................... 30
5.3.4 Functions of Reset Devices ........................................................................ 31
5.3.5 Functions of Motion Sensors ...................................................................... 31
5.3.6 Functions of Output Devices ....................................................................... 32
5.4 Functions of the Personnel Alarm System .......................................................... 33
6 Test and Repair .......................................................................................................... 35
6.1 Test of the Alarm System ................................................................................... 35
6.1.1 Displaytest of Operation Module ................................................................. 35
6.1.2 Test and Adjustment ................................................................................... 35
6.1.3 Version of Firmware ................................................................................... 36
6.1.4 Flashing 'P' at the LED-Display ................................................................... 36
6.1.5 2nd Stage-Alarm ......................................................................................... 36
6.2 Repair ................................................................................................................. 37
7 Rebuilding and Disposal ............................................................................................. 39
7.1 Modifications, Spare Parts, Accessories ............................................................. 39
7.2 Disposal .............................................................................................................. 39
Structure
Part 1 INTRODUCTION
gives a short overview of the user's manual
Part 2 ENGINEERING
helps to understand and to apply the Watch Alarm System and the
Personnel Alarm System
Part 3 INSTALLATION
describes the installing procedures for all components of the Watch Alarm
System and of the Personnel Alarm System
Part 4 COMMISSIONING
describes the configurations and rules of the settings to bring the Watch
Alarm System and the Personnel Alarm System into the specified
operational states
Part 8 APPENDIX
contains the mechanical drawings with technical data, electrical drawings
and certifications
Important Abbreviations and Terms
Abbreviation Meaning
1 Introduction
NOTICE
Helpful informations follow.
1
Introduction
All informations in this manual refers to the device, application place, transport, storage,
installation, operation and maintenance.
This manual is directed at the following target groups:
• User
• Service Engineer/Customer Engineer
• Commissioner
Knowledge about automation systems are assumed. General knowledge in the area of
electrical connections and installations are also assumed.
The described device may be adjusted and operated only in connection with this manual.
Installation, commissioning and operating may be carried out only by qualified personnel.
Qualified personnel, for the purpose of the security-technical tips of this manual are persons,
who have the authorisations to install, to commission, to ground and to label devices,
systems and electric circuits according to standards of safety engineering.
Operating Instructions
The user is obliged to operate the Watch Alarm System / Personnel Alarm System only when
they are in good working order.
• Protect the Watch Alarm System / Personnel Alarm System against water, do not touch
the component parts with wet hands.
• Do not use the device if it disseminates a nasty smell or if there are unusual noises.
• Do not put objects into the devices.
In addition to the instructions given in the operating manual, please observe the following:
• relevant accident prevention regulations
• generally accepted safety regulations
• regulations effective in the country of installation
• working and safety instructions effective in the user's plant
2
Engineering for an Alarm System
The Watch Alarm System and the Personnel Alarm System both support the OOW or a
person in charge with his task of observing and standby in a confidential and secured
manner. The demand for an alarm system depends strongly on the type of ship or offshore
location. Another aspect is the area of observance with different places to stay, and the time
of day with the periods of working hours. These conditions induce the requirements for
counts of parts and the complexity of the essential configuration.
This part helps to project, or better, to apply a Watch Alarm System and a Personnel Alarm
System. The following chapter describes a typical application including all standard
components, but a real configuration can omit a standard type or replace it by another type
for doubling purposes.
The appendix includes electrical drawings, mechanical drawings, technical data and details
for further examinations of watch alarm systems. The denomination personnel alarm system
means a specialised and independent alarm system for surveillance areas others than the
bridge. It is derived from the watch alarm system and keeps its alarm control system.
3
Engineering for an Alarm System
NOTICE
The reset of the BNWAS - countdown is just allowed in areas were the OOW
has a proper look out.
The integration of PIR motion sensors with A006.6 is for the first time in a watch alarm
system.
The figure 1 shows a typical Watch Alarm System configuration.
4
Engineering for an Alarm System
NMEA VDR
RESET
BRIDGE BRIDGE
WING WING
PCB1 Terminal Module PCB2
PORTSIDE STARBOARD
RADIO CHART-TABLE ACOUSTC
ACOUSTC
CONSOLE SIGNAL
SIGNAL
RESET RESET RESET RESET
BUTTON RESET RESET BUTTON
ACCOMMODATIONS
WATERTIG ALARMPANEL ALARMPANEL WATERTIG
HT BOX Nautical Captain Cabin HT BOX
BULKHEAD Officers BULKHEAD
ACOUSTC ACOUSTC
SIGNAL SIGNAL
RESET RESET Men's ALARMPANEL RESET RESET
BUTTON Passage Way BUTTON
QUARTER Crew
5
Engineering for an Alarm System
ER
ENTRANCES
SYSTEM SYSTEM
ECR CONSOLE ON ON
Personnel
Alarm
Operation
Module
Terminal Module
ENGINE ENGINE
ROOM ROOM
PERSONNEL PERSONNEL
ALARM ALARM
RESET RESET
BUTTON Power Failure BUTTON
Supply to Alarm
24VDC System
6
Installation of an Alarm System
The installation of the components is the first step to implement the Watch Alarm System on
the vessel. After delivering, the transportation and receiving at its destination the shipment
has been unpacked and examined for completeness. The components of the Watch Alarm
System must be without visible signs of damage to eliminate reasons for malfunctioning later
on.
The installation of the Watch Alarm System is described in this paragraph and acting upon
this guidelines guarantees the success of the installation procedure.
There were many considerations which had been made by the shipbuilders to prepare places
on board and to configure lines for cables. If a plan has been made to coordinate the
installation, it might be necessary to study the guidelines in this manual for adjustments.
Before beginning there are to consider the specific requirements needed by the watch alarm
system components for its assembling.
NOTICE
If there is a power supply failure while the device is ON/AUTO, the internal
buzzer will sound.
Once the power supply is restored, press reset to turn off the internal buzzer.
NOTICE
Observe a safety distance of 0.7 m to the standard-magnetic-compass and a
safety distance of 0.4 m to the steering-magnetic-compass.
The reduced safety distance to the standard-magnetic-compass is 0.45 m
and to the steering-magnetic-compass is 0.3 m.
7
Installation of an Alarm System
The instant of time to do the installation is given when the devices having an operator for
surveillance and their locations for operating have been selected. This may take some time
There is only one operation module (A006.6-A) for the Watch Alarm System to be installed.
Its operational site at the safety console is a central place on the bridge. Before inserting the
module it must be sure which direction the panel ought to have (for instance with the key lock
oriented towards the gang way).
Screw clamps are included for locking the operation module at the console cut-out. Affix the
sign of figure 3, if not done yet, at the left corner of the front panel to mark the module as
belonging to a watch alarm system.
8
Installation of an Alarm System
The terminal module (A006.6-B) comprises all connections belonging to the watch alarm
system. The module itself is mounted on a DIN rail for a flexibly selected fixing location.
The module has two types of connections, the first establishes the connection with the
operation module (6-pole), and the second provides two rows of terminals for input and
output of feed-lines (60-pole).
NOTICE
The operational module and every reset devices have to be installed on
locations were the OOW has a proper look out.
X2
X1
Figure 5: Terminal Module
9
Installation of an Alarm System
This terminal block is the interface between operation module and terminal module. The
connection cable (A006.5-C) is used to guaranty the quality of signals. The data interface
mechanism depends on the synchronous exchange of binary data packets.
The shift register in the terminal module is read and write by the processor in the control
module. The information bits of the shift register are evaluated at the time of coming in, and
set at the time of going out.
Terminal X2 Configuration
61 + Voltage (24 VDC)
62 GND
63 Data
64 Data
65 Data
66 Data
These two rows have their terminals numbered, the lower row from 1 to 30 and the upper row
from 31 to 60. The upper row is shifted left the half of a terminal space against the lower row
ordering the upper terminals in turn with the lower ones to build a consecutive line of
terminals from left to right. This sequence is used in the column terminal of the tables
describing the configuration of the terminal blocks.
These screw fastening terminals are not detachable, the offset between upper and lower row
is given by the print terminals themselves. The terminal module uses 10 parts each having 6
terminals with three terminals in upper and lower row. The numbering is from X1-1 to X1-10
overall, and 1-2-3 / 4-5-6 from left to right for lower / upper row with one clamp.
The terminal module operates on direct current voltage. The nominal voltage is +24 V
allowing a tolerance down to 18 V and up to 32 V. The positive pole is connected to
terminals 31/32 and the negative pole to terminals 1/2.
Terminal X1 Configuration Connection Type
31/32 + Voltage (24 VDC) input
1/2 - Voltage (24 VDC) input
10
Installation of an Alarm System
NOTICE
For custom-side and combined installation:
Make sure the capacity of the battery for backup power supply supplies the
terminal module for 6 hours.
The 3 examples below describe possible installations for backup power supply.
1. Custom-Side Installation
The customer provides the external battery and ensures the cabling of main power and
backup power like shown in figure 6.
31 32 33 34 35
1 2 3 4 5
- + 24V DC UPS
Contact
Main Backup
Power Power
2. Combined Installation
The customer provides the external battery. INTERSCHALT maritime systems AG provides a
terminal block with UPS contact for connecting the main and backup power supply.
31 32 33 34 35
1 2 3 4 5
3. Integrated Installation
INTERSCHALT maritime systems AG provides a complete backup power supply.
31 32 33 34 35
1 2 3 4 5
- +
UPS
11
Installation of an Alarm System
12
Installation of an Alarm System
13
Installation of an Alarm System
14
Installation of an Alarm System
The terminal 59 holds +24 VDC over a resistor of 2.2 k Ohm, which is connected to GND to
release the reset function.
For a correct operation of the Watch Alarm System, please ensure that the contact at this
input generates a maximum of 3 impulses per second.
Terminal X1 Configuration Connection Type
59 Reset: (NO to GND) input
29 GND output
The terminal 60 holds +24 VDC over a resistor of 2.2 k Ohm, which is connected to GND to
start the system, when the key switch is set to “AUTO”.
Terminal X1 Configuration Connection Type
60 Start to GND (30) input
30 GND output
15
Installation of an Alarm System
The wall-box types of signalling elements are mounted at places with the eventuality of water
contacting situations (watertight fitting at the lower site). Panels have a front plate with
assembled elements mounted on it, but without a cage for its rear side. The panels therefore
must be placed at appropriate planes to tighten with the front and to cover the backside from
unintentional contacting and to avoid a possible damage with disabling its function. The
different consoles on the bridge have cut-outs at particular points for placing the reset push-
buttons and buzzers. The measures for console cut-outs and fixing holes of wall boxes and
panels are shown in the appropriate mechanical drawings. Before mounting an element the
electrical feed-lines for it must have been laid.
Additional devices have special mounting procedures accordingly to their functionalities. The
fixing points on the bridge are determined already in many cases, but the location for a
sensor device might be subject for change later on with commissioning.
The INTERSCHALT Watch Alarm System uses PIR motion sensors delivered in a kit of type
A006.6-E. The kit includes a wall box and the PCB module, which is mounted in the same
manner as the terminal module on a DIN rail. A cable similar of that fixed at the PIR sensor is
used to connect the PCB module and the wall box as junction point to the sensor.
NOTICE
It is just allowed to detect an area were the OOW has a proper look out.
16
Installation of an Alarm System
As mentioned with installation of sensor devices, a PCB module must be installed for
connecting the PIR motion sensor with the Watch Alarm System. Place the PCB module
nearby the the terminal module. The distance between the PCB module and wall box must
be maximum 30 metres. The distance between PCB module and terminal module must be
maximum 0.75 metres. A direct feed with the PIR sensor cable is not recommended for a
statical application. The 4 leads cable supplies the PIR sensor with voltage and the PIR
sensor uses two leads of the cable to signal moving detection to the PCB module. The PCB
module is necessary to generate the correct signal which is to be fed to the input of the
terminal module. The 3-pole connector is the feed-line input for voltage to the PCB module
and the output of signalling to be connected to external device reset input at the terminal
module A006.6-B. The reset input needs switching the GND of terminal 29 to terminal 59.
The signal line 48 of PCB module generates a pulse of ground potential for the indication of a
detection of moving. Minus 24 VDC terminal (0 V) must be connected to terminal 29 of the
terminal module to provide ground potential. The period of the ground pulse is sufficient for
activating the reset function.
The descriptions of the installation of sensor devices and installing the PCB module let one
find out, that installing two or more sensor devices may increase the requirements for means
of mounting and accessories. It is recommended to take care for the possibility of upgrading.
NOTICE
It is just allowed to detect an area were the OOW has a proper look out.
There is only one operation module for the Personnel Alarm System to be installed. Its
operational site in the engine control room at a safety console is a central place for engineers
and machine operators.
Before inserting the module it must be sure which direction the panel ought to have (for
instance with the key lock oriented towards the consol's border side).
Screw clamps are included for locking the operation module at the console cut-out. Affix the
sign of figure 3, if not done yet, at the left corner of the front panel to mark the module as
belonging to a Personnel Alarm System.
17
Installation of an Alarm System
The terminal module comprises all connections belonging to the Personnel Alarm System.
The module itself is mounted on a DIN rail for a flexibly selected fixing location. The
description is identical to that of watch alarm and must be referred for information.
Affix the sign of figure 9 at the terminal module to mark it as belonging to a Personnel Alarm
System.
The terminal module is connected with the operation module by connection cable type
A006.5-C, and is prepared for a mounting on a DIN rail.
The wall-box types of signalling elements are mounted at places with the eventuality of water
contacting situations (watertight fitting at the lower site). Panels have a front plate with
assembled elements mounted on it, but without a cage for its rear side. The panels therefore
must be placed at appropriate planes to tighten with the front and to cover the backside from
unintentional contacting and to avoid a possible damage with disabling its function. The
consoles in the engine rooms have cut-outs at particular points for placing the reset push-
buttons and buzzers. Before mounting an element the electrical feed-lines for it must have
been laid.
The table of equipment elements is identical to watch alarm and is to be referred for
information. Apparatus equipped with a housing are suited for wall mounting.
Place the illuminated push-buttons and buzzers into the related console cut-outs. The
measures for console cut-outs are shown in the appropriate mechanical drawings in the
appendix of this documentation.
18
Commissioning the Alarm System
If not familiar with devices and functions of the alarm system, it is recommended to study the
next chapters before going on with commissioning.
An alarm system of type Watch Alarm / Personnel Alarm with its centralized operation
module demands an accurate set up of its functionalities. First, the electrical connections to
the peripheral elements hold the responsibility to communicate the alarm states. Second, the
application must have been configured with its suitable alarm plan. Third, the alarm system
has stored all data for its task.
For successful commissioning of the Watch Alarm / Personnel Alarm System, it is
recommended to carry out the steps of the following description with the detailed
explications.
Profile 001 is predefined with the alarm system and confirms with the resolution
MSC.128(75). Classification and denomination is not by MSC.128(75).
To choose another profile change the actual profile number by pressing the + or – key. For
further instructions see chapter 5.
6 Turn the key switch to ON position. The alarm system is activated and in
operation constantly.
19
Commissioning the Alarm System
Control Unit
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
81...86 91...96
STAGE 2 STAGE 3 FAIL 2x RS422
+ - NMEA
STAGE 3 FAIL
to to
VDR VDR Buzzer Remote
Stb. ON
Wing SAFETY WS WS WS WS WS PORT STB. Ext.
STATION MANOEV. NAVY COMM MAN. ROUTE WING WING RESET
+ - + - STEER PLN.
UPS
Contact Buzzer Buzzer
Port Aux
Wing
Td= Selected Dormant Period Time Alarm: 1) visible indication 2) audible signal
1 alarm
st 2) >>
0 alarm
th 1) >>
Time-scale relative
to 1st alarm : 0.00 0.25 0.50 1.00 2.00~3.50 minutes
AS relative to Td: Td+0 Td+15 Td+30 Td+(120 ~ 210) seconds
AS relative to 0 15 15 90~180 sec./alarm
alarms:
20
Function and Operating
The Watch / Personnel Alarm Systems described with this manual are based on ANNEX
“Recommendation Standards for a Bridge Navigational Watch Alarm System (BNWAS)” of
the Resolution MSC.128(75)(adopted on 20 May 2002).
Differences of the alarm systems to the Resolution MSC.128(75) are pointed to.
An alarm system can be switched on and off. This is done manually by the OOW or other
responsible person with the key lock at the appropriate operation module.
NOTICE
In case of main power supply failure the display indicates a flashing "P".
Once the main power supply is restored, the display no longer indicates "P".
The functions of alarm reset and alarm signalling are concatenated by the dormancy
function.
The dormancy function starts its active execution at the end of the active reset function, or
initially, when the alarm system is switched on, with the start of the dormant period. The
duration of the dormant period has a time limit (the longest dormant period), and if the
dormancy function has reached this limit, the alarm function starts its active execution.
The actual duration of the dormant period can be reduced by the reset function. Then the
dormancy function starts again the dormant period, which is always able to last until the limit
is reached. The limit cannot be prolong by any procedures of working the alarm system.
21
Function and Operating
The alarm function is only released at the end of the dormant period and if this end has been
the limit. The dormancy function reaches the limit of the dormant period, if the reset function
has not been activated until then.
The time diagram in figure 12 shows the sequence of periods when the reset function has not
been activated during any period, neither the dormant period nor the alarm periods. Four
types of alarm periods are specified beginning at the dormant period time limit (Td) with the
start of the alarm function.
An additional alarm is starting, if the actual period has reached its limit time and if the reset
function has not been activated until then.
The reset function terminates the alarm function in a moment with all its alarms. The end of
the alarm function activates the dormancy function, which restarts the dormant period.
The following table shows an exemplary setting of the time for the Watch Alarm System.
The reset function is the object of changes and new components to reduce the efforts for
managing the alarm system working in the affected areas, and suppressing unconditioned
alarms,
The reset function has multiple inputs by which it is activated. The waiting for an input signal
and then executing is its typical cycle. The detection of a legal input signal forces the check
of the alarm state in order to shut down the activated alarm function in addition to merge the
dormancy function with its dormant period function. It is then to evaluate and monitor the
actual state of the alarm system.
The reset function can stop the sequence of the alarm at any time. It is not blocked, even not
if the last stage of the sequence lasts for longer.
NOTICE
Every reset devices has to be installed on locations were the OOW has a
proper look out.
22
Function and Operating
Time interval
15 seconds
Internal and external buzzers
are sounding.
Time interval
15 seconds
2nd stage alarm system is
~ released
~
Time interval
90 seconds
3rd stage alarm system is
~ released
~
~ RESET
~
The “Emergency Call” occurs in the event that immediate assistance is necessary. This call
is released by pressing a reset button for at least 5 seconds, regardless the position of the
key switch. Using the “Emergency Call” releases the accommodation alarm and, if the
system is not being reset within 90 seconds, the crew alarm. Pressing the reset button again,
will activate the reset function.
When the key switch is ON, this call can also be activated by the ALARM telegram.
23
Function and Operating
The following table shows the deposited profiles stored with the firmware program (see the
appropriate chapter for details of selection). The columns lists the values of most of the
parameters.
24
Function and Operating
The alarm systems are controlled by a program which resides in the built-in microprocessor
with the operation module.
Besides their operational modes, the systems can be switched into an internal mode for
parameter settings (profile settings). The parameter setting function is also provided by the
program of the operation module. A detailed description is given with the chapter of the
Operation Module.
OFF Mode
No alarm function is active. Power supply may not be plugged off as it is still needed to switch
to ON mode. But if the key is not slotted in at the operation module, dismounting of alerting
elements for repair or maintenance cannot effectively disable the watch alarm system
functionality.
ON Mode
This is the normal operation mode for the alarm function to be activated with the specified
alarm system functionality. It comes into execution when the key lock is switched to the ON
position. With the ON mode the input terminal of the Auto-pilot is not accounted for reset
function.
AUTO Mode
This is the normal operation mode for the alarm function to be activated with the specified
alarm system functionality under the condition of the auto-pilot connected to the input With
the AUTO mode only the input terminal for auto-pilot is accounted for reset function.
The AUTO mode does not automatically do an internal switch to and from the ON mode.
When the selected time interval has elapsed, a preliminary alarm is indicated by blinking
lamps at each connected reset push-button. The text of the display is also blinking.
25
Function and Operating
If none of the reset buttons is pushed within a selected time, e.g. 15 seconds in the standard
profile according to the MSC 128(75), the internal buzzer and each external buzzer
connected are switched on.
If the system is not reset within a further selected time, e.g. 15 seconds in the standard
profile according to the MSC 128(75), the output contact of the accommodation alarm is
closed.
With a delay of a further selected time, e.g. 90 seconds in the standard profile according to
the MSC 128(75), the output contact to trigger the crew alarm is closed.
Pushing and releasing one of the external reset buttons gives a reset signal to the system
and restarts the dormancy function with dormant period. It is also possible to reset the
system by an electrical signal from the workstation for navigating and manoeuvring (auto-
pilot).
This module provides the electrical output and input contacts for the external alerting and
reset devices. It supplies voltage to the operation module and incorporates the failure output
signal to VDR.
Supplied with voltage the system is operational and with the terminal module connected to it
the FAIL contacts (38) and (9) are switched.
The small one pole DIP switch labelled with 0 and 1 is for configuration of the alarm system,
which has to be done by the keyboard panel of operation module (moving switch pin to
label 1).
The connection cable between terminal and operation module brings voltage to the operation
module and exchanges control informations. The left shift logic element receives the Bits to
be evaluated by the terminal module. The right shift element sends input data of the terminal
module to the operation module. That means inputs of reset and autopilot are evaluated by
the processor component in the operation module. The information of activating or
deactivating alerting elements comes from the operation module and is transposed into
electric switch functions by the terminal module.
26
Function and Operating
The LEDs are lined up above the relays. The leftmost two LEDs (1,2 to end side of board )
are attached to the two equal relays K3 and K2 in the same order and indicate the activated
states of the relays. An activated relay signals an alarm state.
The yellow LED (3) is for illumination control. Illumination cannot be dimmed until dark state.
Blinking of illumination is not specific to a single alarm device.
The right most green LED must shine when the system is in a normal operational mode.
27
Function and Operating
The operation module combines the essential control and display functions of the alarm
system. The module itself consists of two electronic parts attached to the front-panel and the
back plane with connectors and the processor inside of the module. The front-panel has
mounted all control elements and the display unit of the alarm system with an array of 3
alphanumerical indicator pads.
The alphanumerical signs are approximated by the capabilities of the 7-segments units.
Upper and lower case characters are used.
The parameter mode is intended for commissioning and adjustment during test workings. If it
is necessary the parameter values of the chosen profile can be adjusted. The alarm system
must not be in an operation mode ON or AUTO.
This is a two button functionality with the SET button and the (+) or (–) button. The key lock
must be in “OFF” position. To select the time, carry out 3 steps:
Step Action Effect
Push and hold the SET button to show the
1
actual selected time interval
2 Change the time value by + or - button
3 Release the SET button
Result The new selected time interval is stored The display shows “oFF” again
Switching to ON mode lets immediately start the dormancy function and at the same time
counting down the dormant period although for the first 6 seconds the word 'on' is shown The
activated alarm system in ON mode does not allow to change the dormant time interval
value.
The remaining time of the dormant period is shown on the display in minutes, the resolution
is in tenths of a minute: two digits followed by a decimal point followed by one digit right of
point. This position behind the decimal point represents the expiration of 6 seconds, when the
digit is reduced by one It is ensured, that there is only a step of value 1 with the changing of
the time display. When the dormant period has elapsed completely, 3 zeroes are shown
slowly blinking.
Pressing a keypad of the operation module is directly evaluated for the reset function besides
any other meaning of the pressing. To prevent the alarm system against unauthorised
selection of another time interval value, it is recommended to take off the key when
operations with the keyboard have been done.
28
Function and Operating
AUTO mode sets the system to standby and can be started by remote control.
For the orientation of interpreting display informations in the parameter mode the table of
sequence numbers lists the parameter names being shown on the display when pressing the
+ button consecutively.
This list of parameters is assigned to each profile. The values of the parameters may be
different for each profile. The name “Pro” must be shown to select another profile.
29
Function and Operating
Example:
The profile 001 (Standard BNWAS according to MSC.128 (75)) contains the following values:
Parameter Name on Display Value Comment
Dormant time td
Lower limit dormant period in tL 30 3 minutes
tenth of a minute
Upper limit dormant period in tH 120 12 minutes
tenth of a minute
Delay buzzer in seconds d_b 15 15 seconds
Delay 2nd st. alarm in seconds d_A 15 15 seconds
Delay 3 alarm in seconds
rd
d_c 90 90 seconds
Personnel Alarm PA 0 0 = used with Watch Alarm
1 = used with Personnel
Alarm
Buzzer pattern buP 0 0 = continuous tone
1 to 3 = tone pattern
Buzzer speed buS 0 Speed of tone pattern
A new profile is effective in use until another profile will be selected for use.
The following standard NMEA 0183 telegrams according to IEC 62616 are supported:
$--ALR,hhmmss.ss,xxx,A,A,c--c*hh<CR><LF>
Alarm's description text
Alarm's acknowledge state, A=acknowledged
V=unacknowledged
Alarm condition A=threshold exceeded, V=unexceeded
Local alarm number (identifier)
Time of alarm condition change, UTC
30
Function and Operating
$--ACK,xxx*hh<CR><LF>
Local alarm number (identifier)
$--EVE,hhmmss.ss,c--c,c--c*hh<CR><LF>
Event description
Tag code used for identification of source of event
Event time
$--DDC,a,xx,a*hh<CR><LF>
Colour palette
Brightness percentage 00 to 99
Display dimming preset
Reset devices incorporate two electrical elements which are connected separately to the
terminal board. The illumination is the primary indicator of alarm state and may be
incorporated inside the push button. Pushing the reset switch must generate a ground pulse
of sufficient duration to make the alarm system registration with the acknowledge signal.
The period of the reset acknowledge signal may not become static to avoid discarding the
signal. All push button reset devices are conjuncted (OR gate with multiple inputs).
The reset function is released either by an external reset contact or by EVE telegram
(General Event Message).
The application of motion sensors with an alarm system is to automatically generate the
acknowledge signal without doing an activity targeted only for this purpose. This advantage
has to be achieved by installing the PIR motion sensor in an adequate position. The detection
area is given by individual constellations of bridge and working areas. As with reset push
buttons two or three motion sensors may be needed to build a detection area which covers
the specified working area in a high grade.
31
Function and Operating
Special light emitting and sound generating elements are in different specifications. Adapted
to the DC voltage and supplying signals by the terminal module these are mounted at
locations where it is necessary to alert persons who are responsible for alarm situations.
32
Function and Operating
Time interval
15 seconds
Internal and external buzzers
~ are sounding.
~
Time interval
90 seconds
Signal to the extension
alarm system is released
~ RESET
~
Selected time interval
5.0 – 20.0 minutes
The example in figure 14 points up time intervals and appropriate indications with alarms.
33
Function and Operating
34
Test and Repair
Firmware: 0.1.3:
Key switch “ON”: Pressing the set button all segments of the display are illuminated.
35
Test and Repair
When pushing the SET button the actual profile number is blinking indicating that the
parameter programming state is to be quitted.
With the RESET button the actually changed parameter value may be deleted by restoring
the last value.
When the operation module is connected to the power supply, the firmware version is shown
in the display up to 6 seconds.
When the contact of the UPS (Terminal 4 and 5) is open, the system shows a flashing 'P' on
the display.
No UPS is available:
1. Make a connection between terminal 4 and 5
2. Push the Reset-Button
An UPS is used
1. Check the UPS
2. Push the Reset-Button
If a 2nd stage alarm is performed before the dormant period has reached its limit, there
maybe 2 reasons for this:
36
Test and Repair
6.2 Repair
Check the fuses at the terminal module and change them, if defect. Fuse: 5mm x 20mm, 4
At (time lag).
In case an error cannot be located, please call the service department of INTERSCHALT
maritime systems AG:
tel. +49 (0) 4344 307-200
fax +49 (0) 4344 307-291
e-mail:service@interschalt.de
Enquiries will be answered efficiently by trained personnel during which the customer's
contact details, the serial number of the operation module and a brief description of the
problem are recorded.
Find the serial number on the type plate at the back of the operation module.
37
Test and Repair
38
Rebuilding and Disposal
7.2 Disposal
Dispose of components and its packaging in accordance with local regulations.
39