Installation

Setup Connections > Wiring Diagram

USB

terminals
USB Ethernet Ethernet Ethernet

Screw
Host
In Device C B A
preparation

600 Vac

40
41
*1
Relay [R02] isolated Busbar voltage L2 / N
[R01] Fixed to Ready for operation
42

*1
Relay [R02] 600 Vac

38
43

[R02]
Preconfigured to Centralized alarm
Busbar voltage L1
*1
Relay [R03]
44

[R03]
Preconfigured to Starter
*1 600 Vac

36
45

[R04] Relay [R04]


Preconfigured to Fuel solenoid / gas valve Generator voltage N
46

600 Vac

34
47

*1
Relay [R05] isolated
[R05] Generator voltage L3
Preconfigured to Preglow
48

*1 600 Vac

32
49

Relay [R06] isolated


[R06] Fixed to „Command Close GCB“, if GCB Generator voltage L2
control is enabled.
50

easYgen3400XT / easYgen3500XT -P1


*1 600 Vac

30
51

Relay [R07] isolated


[R07] Fixed to „Command Open GCB“, if GCB Generator voltage L1
open control is enabled.
52

*1 600 Vac

28
53

Relay [R08] isolated


[R08] Fixed to „Command Close MCB“, if MCB Mains voltage N
control is enabled.
54

*1
Relay [R09] isolated 600 Vac

26
55

[R09] Fixed to „Command Open MCB“, if MCB


control is enabled.
Mains voltage L3
56

*1
Relay [R10]
Fixed to „Command Close GGB“, if GGB 600 Vac

24
57

[R10] control is enabled.


Mains voltage L2
*1
58

Relay [R11]
[R11] Fixed to „Command Open GGB,“ if GGB
control is enabled. 600 Vac

22
59

[R12] *1 Mains voltage L1


Relay [R12]
60

Preconfigured to Alarm class C, D, E or F

20
61

Earth
Analog output [AO 02]
(+/-10Vdc / +/-20mA / PWM) +

19
NC
62

[AO 02]
Voltage Biasing
Do not
+

18
63

Power supply connect !

Isolated, 8 to 40 Vdc *2 Analog output [AO 01]


- -

17
64

(+/-10Vdc / +/-20mA / PWM)


Auxiliary excitation D+ Speed Biasing +

16
65

[AO 01]
isolated
Engine

15
66

Common (terminals 67 to 78) GND


*1
Discrete Input [D01] isolated
[D01] +
14
67

Emergency Stop
*1 [AI 03]
Discrete Input [D02] isolated
[D02] -
13
68

Start in Auto
*1 Analog Input Type 1
Discrete Input [D03] isolated
[D03] +
12
69

Low oil pressure (0 to 2000 Ohm /


*1
[AI 02]
Discrete Input [D04] isolated 0/4 to 20mA /
[D04] -
11
70

Coolant temperature 0 to 1V)


*1
Discrete Input [D05] isolated
[D05] +
10
71

Alarm acknowledgement
*1 [AI 01]
Discrete Input [D06] isolated
[D06] -
72

Enable MCB
Discrete Input [D07] isolated
[D07] s1
73

Reply: MCB open


L3
Discrete Input [D08] isolated
[D08] s2
74

Reply: GCB open


*1
Discrete Input [D09] isolated
[D09] Fixed to „Reply GGB open“, if GGB Generator current s1
75

control is enabled.
*1 (isolated) L2
Discrete Input [D10] isolated
[D10] 1A / 5A compatible s2
76

Fixed to „Load busbar is dead“, if GGB


control is enabled.
*1
[D11] s1
77

Discrete Input [D11] isolated


4

Alarm input
*1
L1
[D12] Discrete Input [D12] isolated s2
78

Alarm input or Neutral Contactor

+ Mains s1
79

MPU input or Ground current (isolated) L1


- 1A / 5A compatible s2
80

1: RS485_A
1: CAN_GND CAN#3 1: CAN_GND RS485#1 2: RS485_B
terminals

terminals
Screw

Screw

2: CAN_L 2: CAN_L 3: RS485_GND


3: CAN_SHIELD 3: CAN_SHIELD 4: RS485_SHIELD
4: CAN_H CAN#1 4: CAN_H CAN#2 5: RS485_Y
6: RS485_Z

*1
Subject to technical modifications configurable via LogicsManager easYgen-3000XT Series Wiring DiagramPCB1

Fig. 21: Wiring diagram easYgen-3400XT/3500XT-P1(-LT)

37580C easYgen-3400XT-P1/3500XT-P1/3500XT-P1-LT | Genset Control 55