Rocky Restore DVD

Procedure
For New or Existing Rocky Computers on Shovels and
Draglines

22 May 2011

This procedure covers the steps to use Maintenance Station Restore


DVD to update the software installation on a Rocky MT7 or MT8
computer.

WARNING:
These steps will overwrite existing data on the Rocky hard
drive.

SAFETY NOTICE:
WHILE WORKING ON THIS EQUIPMENT / PROJECT, ALL SAFETY
REGULATIONS INCLUDING LOCK OUT / TAG OUT REQUIREMENTS
MUST BE FOLLOWED.

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 2

Contents

1. Requirements ......................................................................... 3

1.1. Hardware .................................................................................3

1.2. Software ..................................................................................3

2. Preparation ............................................................................. 4

2.1. DVD Verification ......................................................................4

2.2. USB Check................................................................................5

2.3. Data Backup.............................................................................5

2.4. Windows License Key...............................................................6

2.5. Step7 and WinCC License Keys.................................................7

3. Installation ............................................................................10

3.1. BIOS Setup .............................................................................10

3.2. Restore DVD ...........................................................................13

3.3. Windows Setup ......................................................................15

3.4. Windows First Boot ................................................................19

3.5. Windows Activation ...............................................................22

3.6. Backup Drive Setup................................................................24

3.7. Secondary Language Option..................................................27

3.8. Restore Step7 and WinCC Licenses ........................................29

3.9. Touchscreen Driver Selection ................................................30

Abbreviations..................................................................................... 34

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 3

1. Requirements

The following items are needed to successfully complete this procedure. Please check to ensure
they are available before proceeding further. With exception of the Restore DVD, these items were
previously shipped with the shovel / dragline and should be in possession of the end customer at the
mine site.
It is critical that the hard drive is installed in the Rocky computer in which it will be used for
hardware detection to be successfully performed.

1.1. Hardware
‰ DVD Drive installed in Rocky Computer
NOTE: Upgrade required for older Rocky computers which only have a CD drive
‰ Rocky MT7 Computer with 8GB or 16GB Hard Drive
‰ Rocky MT8 Computer with 32GB Hard Drive
‰ USB Flash Drive

1.2. Software
‰ Siemens Maintenance Station Restore DVD
‰ Symantec pcAnywhere CD (if applicable)
‰ Windows XP Label on Rocky Computer
‰ Step7 v5.4 (or greater) Flash Drive, Floppy Disk, or Product Box with License #
NOTE: Upgrade required for existing Step 7 v5.3 licenses
‰ WinCC v6.0 (or greater) Flash Drive, Floppy Disk, or Product Box with License #
NOTE: GTO Shovel Type A Retrofit requires WinCC v7.0 license

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 4

2. Preparation

Please perform the following steps to ensure a successful installation.

2.1. DVD Verification


‰ Each DVD is typically stamped with a Serial Number that corresponds to the specific Shovel
or Dragline for which it has been created.
‰ In some cases, e.g. due to upgrading hardware, the original DVD may no longer match the
system configuration.
‰ To verify the configuration for a 495 Shovel, please refer to the following diagram:

‰ To verify the configuration for a Dragline or Level 2 Retrofit Shovel, please refer to the
following diagrams:

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 5

2.2. USB Check


‰ Before copying any files to USB flash drive, check to ensure the USB port voltage is
approximately 5V.
‰ A USB cable (red and black wires) and voltmeter can be used for this test as shown in the
picture below. With the multimeter in DC voltage mode, measure the voltage of the USB
port you will be using.

5.03V – Good Reading 7.78V – Bad Reading

‰ If the voltage reading is greater than 5.25V (see example above) on one of the ports labeled
USB or Mouse, this most likely indicates a problem with the USB 4-port hub. Please contact
your local service personnel to obtain an RMA replacement through Siemens. You can still
complete the file transfer by using the port labeled Keyboard (which is directly connected
to the Rocky) after verifying that the voltage on this port is between 4.75V and 5.25V.

2.3. Data Backup


‰ All files on the C drive will be erased once imaging has begun with the Restore DVD. (If the
Restore DVD was previously used to create two partitions, the contents of the D drive will
not be overwritten.)
‰ It is the responsibility of the user to copy any important files from the hard drive before
using the Restore DVD.
‰ Suggested folders to copy to flash drive include the following:
C:\Logs
C:\Siemens\FaultHistory
C:\Trace
C:\Documents and Settings\All Users\Documents\Rockwell Automation\Activations
‰ Suggested files to copy to flash drive include the following:
C:\DisConfig.txt
C:\MidasIni.txt
C:\Program Files\RockySimaticServer\simatic_com_init.txt

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 6

2.4. Windows License Key


‰ The Windows Product Key is a 25-digit combination of letters and numbers found on a label
located on the bottom of the Rocky computer.
‰ The Windows Product Key is unique for each Rocky computer. To gain access to view this
label, please follow “FSA: SE&A_005 Drive Control PLC Cards Removal Procedure”.

Windows Product Key

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 7

2.5. Step7 and WinCC License Keys


‰ Each Shovel ships with a unique Step 7 License Key and a unique WinCC License Key. These
two License Key numbers are present in three locations:
(1) The Product Box
(2) The License Media
(3) The License File
‰ The Product Box contains the License Key number on the front cover as shown.

Product Box Cover

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 8

‰ The License Media format may be either a USB Flash Drive or a Floppy Disk.

License Media: USB Flash Drive License Media: Floppy Disk

‰ The License Media format is based on the software version.


Step7 WinCC
v5.3 v5.4+ v6.0 v6.2+
Format

USB USB
Media

Floppy Floppy
Flash Flash
Disk Disk
Drive Drive
License Media Format

‰ The License Media are labeled with the License Key numbers as shown. There may be two
floppy disks. Please locate the disk labeled Single License, not Emergency License.

License Key: USB Flash Drive License Key: Floppy Disk

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 9

‰ The Siemens Step 7 and WinCC license files may be stored on the hard drive of the Shovel /
Dragline or on the original License Media.
‰ If the license files cannot be located, they may be recoverable from the original license keys
by contacting the Siemens Automation Support Hotline.
‰ To check if licenses are present on the hard drive of the Shovel / Dragline, open the
Automation License Manager shortcut on the Windows Desktop.
‰ Select Local Disk (C:), highlight all the license keys, then right click and select Transfer.
(Note that several keys may exist, but the keys labeled WinCC RT and STEP 7 are the only
ones required to use the Siemens HMI and PLC programs, respectively.)

‰ Select LICENSE_KEY (F:), or whichever drive corresponds to the removable Siemens USB
memory stick and click OK

‰ Right click Safely Remove Hardware and choose Safely remove USB Mass Storage Device

‰ When the Safe to Remove Hardware message appears, unplug the Memory Stick

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 10

3. Installation

Verify Preparation steps have been completed before proceeding. The following Installation steps
will overwrite data on the Rocky hard drive.

3.1. BIOS Setup


‰ All of the Rocky MT8 computers should be setup by default to boot from CD/DVD.
‰ Some of the Rocky MT7 computers may not be setup by default to boot from CD/DVD.
‰ The remainder of this section applies to the Rocky MT7 computers (but may be used to
verify the Rocky MT8 computers).
‰ Restart the computer and press F2 to enter Setup

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 11

‰ When the BIOS Setup Utility sceen appears press the right arrow key to select the Boot page

‰ Press the down arrow key until CD-ROM Drive is highlighted, then press the plus key to
move it to the top of the list

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 12

‰ Press the right arrow key to select the Exit page then verify Exit Saving Changes is
selected and press Enter

‰ Verify Yes is selected and press Enter

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 13

3.2. Restore DVD


‰ Insert the appropriate Restore DVD into the Rocky computer CD/DVD drive
‰ Restart the computer to boot from the Restore DVD
‰ When the “twin penguins” Clonezilla screen appears, press Enter to accept the default
selection of clonezilla live with img

‰ After hardware checks are complete, a Select mode install screen will appear.
‰ Click Ok or press Enter to continue

‰ Verify that the RESTORE DVD – SOFTWARE CHECKLIST items have been completed.

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 14

‰ If so, then yes and press Enter to continue.

‰ A progress bar will be shown while the Restore DVD is loading the image to the hard drive.

‰ Once completed, the computer will automatically reboot and the disc will be ejected.
‰ At this point, it is critical that the hard drive is installed on the actual Rocky computer before
it reboots into Windows Setup.

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 15

3.3. Windows Setup


‰ After this, an initial Windows setup screen will appear. This may remain for several minutes.

‰ This is followed by another Windows XP Setup screen which will appear for a shorter time.

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 16

‰ Finally, the first Setup screen will appear. Click Next.

‰ To proceed, you must select I accept this agreement and click Next.

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 17

‰ Enter the 25-digit Product Key from the label on the Rocky and click Next. If not readily
available, click Next and click No. There is a 30-day grace period to enter this later.

‰ Enter the correct Date & Time and select the appropriate Time Zone, then click Next.

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 18

‰ A Networking Settings progress window will display momentarily.

‰ The last Setup window will display progress Performing Final Tasks.
‰ After these tasks are completed, the computer will reboot.

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 19

3.4. Windows First Boot


‰ A startup script will run on the first boot into Windows. Please allow several minutes for this
to complete.

‰ Rocky MT8 Computers


At the Terminal bus selection window, select Realtek RTL8168/8111 and click OK.

‰ Rocky MT8 Computers


Click Yes, when prompted to re-initialize communication.

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 20

‰ Rocky MT7 Computers


At the Install/Remove Interfaces window, select TCP/IP -> Realtek RTL8139 Family… and
click Close.

‰ Rocky MT8 Computers


At the Install/Remove Interfaces window, select TCP/IP -> Realtek RTL8168/8111 and click
Close.

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 21

‰ Rocky MT7 Computers


At the Set PG/PC Interface window, leave selected TCP/IP -> Realtek RTL8168/8111 and click
OK.

‰ Rocky MT8 Computers


At the Set PG/PC Interface window, leave selected TCP/IP -> Realtek RTL8168/8111 and click
OK.

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 22

3.5. Windows Activation


‰ Click Start -> Activate Windows
‰ If prompted, enter the 25-digit Product Key from the label on the Rocky and click Update

‰ Select Yes, I want to telephone a customer service representative and click Next

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 23

‰ Call 888-571-2048 with the Installation ID


‰ Enter the Confirmation ID provided and click Next

‰ Click Finish

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 24

3.6. Backup Drive Setup


‰ Open My Computer and double click on Local Disk (D:)

‰ If this is the first time a Restore DVD has been used with this hard drive, the following
prompt will appear. Click Yes to format now.

‰ (If applicable) Select Quick Format and click Start.

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 25

‰ (If applicable) Click OK to confirm format.

‰ (If applicable) Click OK to acknowledge format is complete.

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 26

‰ (If applicable) Click Close to exit the format dialog box.

‰ Double click on Local Disk (D:) then right click and choose New -> Folder

‰ Name the folder Backup and create sub folders D:\Backup\HMI, D:\Backup\PLC,
D:\Backup\SIBAS, D:\Backup\HTML
‰ For Retrofit Shovels with Allen Bradley PLCs also create D:\Backup\Rockwell
‰ Place the latest machine-specific program files in these folders

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 27

3.7. Secondary Language Option


‰ If a Secondary Language Option has been purchased, open Windows Explorer and copy the
self-extracting .zip file to D:\Backup\HTML
‰ Double click the secondary language self-extracting .zip file and click Unzip

‰ Once complete, click OK then click Close

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 28

‰ If the secondary language is Chinese or Russian, click Start -> Settings -> Control Panel
‰ Double click Regional and Language Settings
‰ Select the Languages tab and verify that both boxes are checked for East Asian languages
and complex script and right-to-left languages

‰ Select Chinese (PRC) or Russian as appropriate -- all other languages leave the default value
of English (United States) selected

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 29

3.8. Restore Step7 and WinCC Licenses


‰ Select LICENSE_KEY (F:), or whichever drive corresponds to the removable Siemens USB
memory stick, highlight all the license keys, then right click and select Transfer.
‰ (Note that several keys may exist, but the keys labeled WinCC RT and STEP 7 are the only
ones required to use the Siemens HMI and PLC programs, respectively.)

‰ Select the Backup partition Local Disk (D:), and click OK


(This is critical to ensure the licenses are not overwritten by future use of the Restore DVD.)

‰ Right click Safely Remove Hardware and choose Safely remove USB Mass Storage Device

‰ When the Safe to Remove Hardware message appears, unplug the Memory Stick

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 30

3.9. Touchscreen Driver Selection


‰ If the touch screen is not responsive, this most likely indicates the driver currently selected
does not match your touch screen or somehow the wrong COM port has been selected.
‰ Click Start -> Programs -> UPDD -> Settings to open the touch screen driver utility
‰ Draglines and 495 Shovels use COM2
Retrofit Shovels with the 4-port PCMCIA serial card use COM3
‰ The newest Vartech monitors use the Hampshire Touch, TSHARC-12/10 driver
Previous generation GE Fanuc monitors use the Elo, E281A-4002 Intellitouch driver
‰ The existing driver is shown at the top left hand corner of the screen. To change the driver,
click Remove this device

‰ Click Yes to confirm removal

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 31

‰ Click Add a new device

‰ Select the appropriate Device setup and serial port, then click OK
(Example: Dragline / 495 Shovel with Vartech Monitor)

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 32

‰ Click Calibrate

‰ Follow the onscreen calibration instructions

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 33

‰ Finally, click Close

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.
Procedure | Rocky Restore DVD | 22 May 2011 34

Abbreviations

BIOS Basic Input Output System

DMI Desktop Management Interface

CD Compact Disc

DVD Digital Versatile Disc

HDD Hard Disk Drive

HMI Human Machine Interface

L2R Level 2 Retrofit

MT7 Amrel Rocky Mobile Computer, MT786EX version

MT8 Amrel Rocky Mobile Computer, MT886EX version

NIC Network Interface Card

PLC Programmable Logic Controller

Rocky Rugged Industrial Laptop Computer used in Shovel

Step7 Siemens PLC Software

USB Universal Serial Bus

WinCC Siemens HMI Software

www.siemens.com Siemens Industry, Inc.

All rights reserved. All trademarks used Industry Solutions Division


are owned by Siemens or their respective owners. 100 Technology Drive
Alpharetta, GA 30005
© Siemens Industry, Inc. 2011

© Siemens Energy & Automation 2011. All Rights Reserved. For Internal Use Only.