Reg. PMC NONOC On ALH-231 Circuit Book - Outdoor (New Manauri - New Sujatpur) Rev. B
Reg. PMC NONOC On ALH-231 Circuit Book - Outdoor (New Manauri - New Sujatpur) Rev. B
2023
To: Consortium of Siemens Ltd and KEC International Ltd
Birla Aurora, Level 21, Plot No. 1080,
Dr. Annie Besant Road,
Worli, Mumbai-400030, India
Email: Pankaj.rastogi@siemens.com
A. Technical Comments:
1. Scanned Signature is not acceptable in the design.
2. CTR1 should be corrected as CTR.
3. MTP should be provided at J.B-2 & J.B-6 in outdoor design and CCP should also be
accordingly updated.
C. General Comments:
1. ‘Drawing and CAD standard’ has been mentioned under GS Appendix-7, (page nos. 228 –
229 of CA); the same should be followed in the Design.
Further,
1) This is to mention that in reference to FIDIC General Condition’s sub-clause 3.1(c), 4.11 and
5.8, approval or consent of the Engineer shall not relieve the contractor from any
obligation or responsibility under the contract. If any errors, omissions, discrepancies are
found later in the referred document (drawing and design) the contractor has to carry out
the modification on his own cost.
2) The Contractor shall be responsible for and shall bear and pay the costs for any alteration
of works arising from any discrepancies, errors or omissions in the design and drawing
supplied by him, whether such designs and drawings have been approved by the Engineer
or not (PSSW Para 1.5.2 / PSTW Para 1.6.2 of CA).
Hence, Consortium of Siemens-KEC is required to update and submit 4 copies of the design
“Circuit Book (Outdoor Drawing – 1/SG/0778) Interface Circuit: ALH – 231” along with para-wise
compliance of, but not limited to, the above comments.
Best Regards,
Kamal Sharma
Team Leader,
Authorised Signatory for SYSTRA-Mott MacDonald (JV)
ksharma1@systra.com
Prayagraj (U.P.)