DETC THREE-PHASE TAP CHANGERS SERIES 010 TYPE AT

- De-energized operation
- For oil immersed transformer
- Bridge connection
- 24 kV / 36 kV / 52 kV / 72,5 kV
- 600 A
- From 2 to 7 positions
- Regulation 2,5% per position Dimension in mm

1.12.130
α =54°

10 ±2

15
O 14 X

L
82

50 G+40
G
= =

80
60

B 100 26
A 126

80
9

75
120
45
Z 77,5 77,5 23 80 23
30 C F C F C E D 77 3

9 (2x) DET. X

TIPO KV POS. A B C D E F G Z
AT 622 2 707 470 90 77 170 80 45 45
AT 623 3 887 560 135 122 170 80 45 45
AT 624 4 1067 650 180 167 170 80 45 45
24
AT 625 5 1247 740 225 212 170 80 45 45
AT 626 6 1427 830 270 257 170 80 45 45
AT 627 7 1607 920 315 302 170 80 45 45
AT 632 2 857 595 90 77 220 130 105 45
AT 633 3 1037 685 135 122 220 130 105 45
AT 634 4 1217 775 180 167 220 130 105 45
36
AT 635 5 1397 865 225 212 220 130 105 45
AT 636 6 1577 955 270 257 220 130 105 45
AT 637 7 1757 1045 315 302 220 130 105 45
AT 652 2 1007 720 90 77 270 180 145 45
AT 653 3 1187 810 135 122 270 180 145 45
AT 654 4 1367 900 180 167 270 180 145 45
52
AT 655 5 1547 990 225 212 270 180 145 45
AT 656 6 1727 1080 270 257 270 180 145 45
AT 657 7 1907 1170 315 302 270 180 145 45
AT 672 2 1227 900 90 77 330 260 225 45
AT 673 3 1407 990 135 122 330 260 225 45
AT 674 4 1587 1080 180 167 330 260 225 45
72,5
AT 675 5 1767 1170 225 212 330 260 225 45
AT 676 6 1947 1260 270 257 330 260 225 45 For "L" please specify
AT 677 7 2127 1350 315 302 330 260 225 45

010-AT-03
Rev. 02 - 27/02/2015

LDT-010 Pag. 9/33