Professional Documents
Culture Documents
Combined PAD Footing Design
Combined PAD Footing Design
Combined PAD Footing Design
GRID
REF.NO DESIGN CALCULATION:
CF2 LOAD ON COLUMN C1 W1 = 399.807 KN FCK 20 MPA
LOAD ON COLUMN C2 W2 = 760.012 KN
SELF WT. OF FOOTING 115.9819 KN
TOTAL DESIGN LOAD ON FOOTING(P)= 1275.8009 KN
S.B.C OF SOIL = 140 KN/M2
REQ.AREA OF FOOTING = P/S.B.C 9.11286357 M2
FOOTING SIZE PROV. L = 5.48 M B= 2 M
AREA OF FOOTING PROVIDED = 10.96 M2
AREA PROV > AREA REQ. OK
CENTER TO CENTER DIST. BET.COLUMN(b) = 4.267 M
GEOMETRIC CENTER ,G.C =b/2 2.1335 M
(X)DIST. OF C.G OF COLM.FROM CENTER OF FOOTING(X)=W2Xb/(W1+W2)=
2.7961011 M
PROJ.a1 FROM CENTER OF COLUMN (C2)=
a1 =(L/2-X) = -0.0561011 M
PROJ.a2 FROM CENTER OF COLUMN (C1)=
a2=(L-a1-b) = 1.2691011 M
NET UPWARD PRESSURE(QNET)=(W1+W2)/(A PROV)=
105.8229 KN/M2
MINI.ECCEN.Emin =.02M 0.02 M
MOMENT DUE TO Emini = 23.19638 KN-M
AVAILABLE ECCEN, =(b/2-x)= -0.662601 M
MOMENT DUE TO AVAILABLE ECCE.= -845.347104 KN-M
CONSIDERING FULL WIDTH OF FOOTING
BM CALCULATION:
QNET = 105.8229 KN/M2
MAX PRESSURE =QNET+6XM/BXLXL 108.140191 KN/M
MINI PRESSURE = QNET-6XM/BXLXL 103.505612 KN/M
STRIP PRESSURE(q)=QNETXB = 211.645803 KN/M
SHEAR FORCE V1=qxa1= -11.8735664 KN
V2 =W1-V1 411.680566 KN
V3 =qxa2 = 268.599925 KN
V4=W2-V2= 348.331434 KN
POSITION OF ZERO SHEAR (Y)=(W1-q*a1)/q
Y= 1.945139 M
BENDING MOMENT CALCULATION:
M1 = q*a1*a1/2 KN-M 0.33306 KNM
M2 = q*a2*a2/2 KN-M 170.4402 KN-M
M3 = q*(y+a1)2/2-w1*y KN-M -400.054962 KN-M