Design Loadings

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

A.

DESIGN LOADINGS

Supper Impose DL External/ Internal Partion Load Live Load


Occupancy Floor No.
Loadings Units Remarks Loadings Units Remarks Loadings Units Remarks
Ceiling 0.6 kPa gypsum+furing AAC Blocks 5.3 KN/m 8"thk.‐3.4Ht. Offices 2.5 kPa
Mech 0.5 kPa AC indoor/ duct/ Pipes Normal Blocks 6.7 KN/m 8"thk.‐3.4Ht. Corridors 4 kPa
1 (typical 
Office Floor Finish 1.8 kPa screed+tiles Staircase 4 kPa
2,3 flrs.)
Partition 1.0 kPa BS 6399‐1‐5.1.4

Total 3.9 kPa

Supper Impose DL External/ Internal Partion Load Live Load


Occupancy Floor No.
Loadings Units Remarks Loadings Units Remarks Loadings Units Remarks
Ceiling 0.6 kPa gypsum+furing AAC Blocks 5.3 KN/m 8"thk.‐3.4Ht. Gym 4 kPa
Mech 0.5 kPa AC indoor/ duct Normal Blocks 6.7 KN/m 8"thk.‐3.4Ht. Corridors 4 kPa
Gym 4 Floor Finish 1.8 kPa screed+tiles Staircase 4 kPa
Partition 1.00 kPa BS 6399‐1‐5.1.4 Storage 5 kPa

Total 3.9 kPa

Supper Impose DL External/ Internal Partion Load Live Load


Occupancy Floor No.
Loadings Units Remarks Loadings Units Remarks Loadings Units Remarks
Ceiling 0.6 kPa gypsum+furing AAC Blocks 5.3 KN/m 8"thk.‐3.4Ht. Deck 1.5 kPa
Mech 0.5 kPa AC indoor/ duct 8"thk.‐1.2Ht.  Corridors 4 kPa
Roof/ 
5 Floor Finish 3.2 kPa screed+waterproof+thermal Normal Blocks 2.35 KN/m Parapet wall Staircase 4 kPa
services
AC Machine+Base 3.5 kPa
Water Tank+Base 20 kPa
Total 4.3 kPa

Other Loads:
Passenger Lift 30 to 50 kPa

You might also like