REPUBLIC OF THE PHILIPPINES

DEPARTMENT OF TRADE AND INDUSTRY


CORDILLERA ADMINISTRATIVE REGION
PINE LAKE VIEW BUILDING, 9 OTEK ST., CORNER
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600

CONSTRUCTION OF ONE-STOREY WITH ROOFDECK


RICE PROCESSING CENTER
ANGGACAN, TANUDAN, KALINGA

PREPARED BY: RECOMMENDING APPROVAL: APPROVED BY:

BOB JOHN A. BONGNGAT LINO D. CUNGIHAN MYRNA P. PABLO


SERVICE PROVIDER, ROCKWELL BUILDERS PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR
GENERAL CONSTRUCTION NOTES
1.THE PLANS ARE INTENDED TO PROVIDE FOR A PLUMB & LEVEL STRUCTURE AND ANY NOTATION
AND/ OR DIMENSION INDICATE TO THAT IS CONTRARY SHALL BE REFERRED TO THE ARCHITECT
FOR CLARIFICATION. Republic of the Philippines
2.PRECAUTIONARY MEASURE SHALL BE TAKEN BY THE CONTRACTOR TO PROTECT AND SAVE FROM TABLE OF CONTENTS DEPARTMENT OF PUBLIC WORKS
ANY DAMAGE OF ALL EXISTING UTILITY LINE WITHIN THE SITE.
3.ANY DAMAGE DONE INCIDENTALLY TO THIS CONSTRUCTION SHALL BE PREPARED AND MADE
TRANSPORTATION & COMMUNICATIONS
GOOD AT THE EXPENSE OF THE CONTRACTOR. OFFICE OF THE BUILDING OFFICIAL
4.STANDARDS SYSTEM INTERNATIONAL D' UNITES (SI) NOTATION ARE ADHERED TO UNLESS
OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS. PERSPECTIVE
5.NO CHANGE OR MODIFICATION SHALL BE MADE WITHOUT THE DESIGNER'S WRITTEN CONSENT SITE DEVELOPMENT PLAN
A LOCATION MAP
2 GENERAL CONSTRUCTION NOTES 1 GENERAL CONSTRUCTION NOTES
TYPICAL REFERENCE MARK CITY/DISTRICT/MUNICIPALITY
A 1 SCALE NTS TABLE OF CONTENTS PROVINCE OF KALINGA
MODULE NUMBER/LETTER SIGNATORIES
A A FLOOR PLAN LAND USE AND ZONING
ELEVATIONS
ARROW POINT
TOWARDS NORTH
GRID MARK
DIRECTION OF SECTION
2
NORTH INDICATOR
SECTIONS
A
DESIGNATION A FLOOR PATTERN LAYOUT
REFLECTED CEILING PLAN
1
SET NUMBER
1
DRAWING NUMBER
SHEET NUMBER
3 TOILET BLOW-UP PLAN
A-6
SET NUMBER
DOORS AND WINDOW SCHEDULE
LINE AND GRADE
1
SET NUMBER SECTION TARGET
A CANOPY FRAME CONNECTION
DETAILS
15
SHEET NUMBER
1
DRAWING NUMBER
SHEET NUMBER
4 PARTITION CABINET DETAILS
SHEET NUMBER A-4
ELEVATION TARGET
EXTERIOR PERSPECTIVE S STRUCTURAL GENERAL NOTES
3 TYP. REFERENCE MARK 1
NEW
GAOGAO PATIKING MAGNAO TANGLAG A 1 SCALE NTS FLOOR FRAMING PLAN
TOMIANGAN ARCHITECTURAL
ROOF FRAMING PLAN
GAWIDAN BANAT BALANI
S I T ETANIOC S COLUMN SCHEDULE
DUPAG
NANENG
PINAGAN ANGGACAN, TANUDAN, KALINGA
TULYAOCOORDINATE: 17.33835, 121.22709 A B C 2 COLUMN-FOOTING DETAILS
LUCOG BANTAY BEAMS SCHEDULE
BADO 4
DANGWA A-2
DANGOY 8000
BEAM SCHEDULE W/ DETAILS
LUBUAGAN DUPAG
RICE FIELD
RICE FIELD
S TRUSS-1 DETAIL
R

POB. LINAS 1000 4000 4000 1000


AMLAO
3 TRUSS-2 DETAIL
R

MALIN-AWA 3
E

POB. SUYANG
LUBUAGAN BALATOC 2
E
V

TANGLAG BALAWAG

1000
MABELONG MABATO TRUSS DETAILS CIVIL/STRUCTURAL
V
I

CHB TYPICAL CONNECTION DETAILS


R

CONCRETE HOLLOW BLOCKS NOTES


R

1000
LOWER
S
O

TALOCTOC SLAB ON FILL DETAIL


1 4
N

TYPICAL SLAB JOINT DETAIL


C

UPPER DALNACAN
MABONGTOT TALOCTOC SLAB DEPRESSION DETAIL
I

PAGUGO
MANANGOL
H

LINTEL BEAM DETAIL


D

C2 MATTELED
LICUTAN
C

BAWAC
3 5
U

3125
DALKINSON TANGILIG AWINGAN MABACA SE-ET DUPLIGAN ELECTRICAL GENERAL NOTES
N

LOWER MANGALI A-2 A-2


MALLANGO DARULOG LOCATION MAP
A

UPPER ANGGACAN GUIMMA


BANGAD ABBREVIATIONS SANITARY/PLUMBING
T

GUMBOWOY

10251
6251
MANGALI CENTRO ANGGACAN SUR
LEGEND
AMMABOY 2
BANGAD
CENTRO POBLACION CABUGAO
BAKKUNG LAY-ASAN E LIGHTING LAYOUT PLAN
POWER LAYOUT PLAN
PANGOL 3125
1 LOADS SCHEDULE AND
BABBANOY ROOFDECK COMPUTATIONS
AMBATO UPPER LUBO LOWER LUBO
PANEL DIAGRAM
TINGLAYAN RISER DIAGRAM
R

PROPER TANUDAN
E

3
V

LUPLUPA PLUMBING GENERAL NOTES ELECTRICAL


I

1000

LOCATION MAP
R

GA-ANG
ABBREVIATIONS
P
O

WATER LINE LAYOUT PLAN

1000
C

BASAO
1 SEWERAGE LAYOUT PLAN
I
H

DACALAN 1
WATERLINE PLUMBING ISOMETRY
C

4
2 PLUMBING- SEWERAGE ISOMETRY
A-2
SEPTIC TANK VOLUME
TO BARLIG, 12000 COMPUTATION
MT.PROVINCE SEPTIC TANK DETAILS
MECHANICAL
P FLOOR CLEAN OUT DETAIL
SEWERAGE BRANCH DETAIL
2 TOILET FIXTURE MOUNTING DETAILS
CATCH BASIN DETAILS
1 LOCATION MAP 4 SITE DEVELOPMENT PLAN AIR CHAMBER DETAILS

A 1 SCALE NTS A 1 SCALE 1:80m


PEOPLES ORGANIZATION BENEFICIARY: SET SHEET
DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY PERSPECTIVE


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE LOCATION MAP
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER GENERAL CONSTRUCTION NOTE 1 1
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA SITE DEVELOPMENT PLAN
BUILDING DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR A-4 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
4 1 2 3
A-2 A B C CURTAIN STEEL ROLL-UP DOOR

38mmØ STAINLESS STEEL PIPE HANDRAIL( 1 @


4100 4000 800mm ht., 1@ 600mm ht.)
150mm THK. CHB PLASTERED FINISHED,
FIN. PARAPET LINE, +4100mm PAINTED W/ FLAT LATEX
2300 2300 3400

900
FIN. ROOFDECK FLOOR LINE, +3200mm
1300 1500 1300

4100
W W W W
5 ramp 1100 1
5 5

3200
1 up
W
2000

900
3
WASH CR DRESS OPERATING AREA
AREA D

3125
ROOM FIN. FLOOR LINE, +200mm
4 W
2
STOCK AREA NATURAL GRADE LINE, 0.00mm
D D
3 3 HALL WAY
W W D

2
6 7 2
3 L E F T- S I D E E L E V A T I O N

1000
MPVS A 2 SCALE 1:80m
3 W
5
A-2 W STORAGE A-2
3125
3 6 W
& 2
ADMINISTRATIVE DISPLAY AREA
OFFICE 1
D A- 3 ALUMINUM
1 SLIDING WINDOW W/ 6mm THK. GLASS S.798

3
D
1 C B A 38mmØ STAINLESS STEEL PIPE HANDRAIL( 1 @
W W 800mm ht., 1@ 600mm ht.)
4 FIN. FLOOR LINE 1
ELEV. +200mm 150mm THK. CHB PLASTERED FINISHED,
ramp FIN. GRADE LINE FIN. PARAPET LINE, +4100mm PAINTED W/ FLAT LATEX
dn ELEV. 0.00mm

900
2
A-2 2 FIN. ROOFDECK FLOOR LINE, +3200mm
A- 3

4100
3200
1 F L O O R P L A N W
2

A 2 SCALE 1:80m FIN. FLOOR LINE, +200mm

NATURAL GRADE LINE, 0.00mm

4 REAR E L E V A T I O N
A 2 SCALE 1:80m

A B C 3 2 1
ALUMINUM
SLIDING WINDOW W/ 6mm THK. GLASS S.798

ALUMINUM 38mmØ STAINLESS STEEL PIPE HANDRAIL( 1 @


SLIDING WINDOW W/ 6mm THK. GLASS S.798 800mm ht., 1@ 600mm ht.)
PARAPET WALL,150mm THK. CHB PLASTERED FINISHED, 150mm THK. CHB PLASTERED FINISHED,
PAINTED W/ FLAT LATEX PAINTED W/ FLAT LATEX
FIN. PARAPET LINE, +4100mm
150mm THK. CHB PLASTERED FINISHED,

900
FIN. PARAPET LINE, +4100mm PAINTED W/ FLAT LATEX
FIN. ROOFDECK FLOOR LINE, +3200mm
900

RICE PROCESSING CENTER


FIN. ROOFDECK FLOOR LINE, +3200mm

4100
3200
4100
3200

W W

900
1 1

W W FIN. FLOOR LINE, +200mm


900

3 2

FIN. FLOOR LINE, +200mm NATURAL GRADE LINE, 0.00mm

NATURAL GRADE LINE, 0.00mm

2 F R O N T ELEVATION 5 RIGHT-SIDE E L E V A T I O N
A 2 SCALE 1:80m A 2 SCALE 1:80m

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY FLOOR PLAN


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE ELEVATIONS
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER 2 2
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
BUILDING DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR A-4 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
150mm THK. CHB PLASTERED FINISHED,
PAINTED W/ FLAT LATEX
4
A-2 A B C 3 2 1 ALUMINUM SLIDING
WINDOW W/ 6mm THK. GLASS S.798

4100 4000

2300 2300 3400 FIN. PARAPET LINE, +4100mm

9000
FIN. ROOFDECK FLOOR LINE, +3200mm
1300 1500 1300 SEE SLAB DETAILS

W W W 800 1100
5 ramp 1100
5 5

4100
1 up

3200
SSPB RG
HDHTT D
HDPP HDPP
2000

WORKSTATIONS WORKSTATIONS

800
WASH CR DRESS OPERATING AREA

900
AREA

3125
ROOM RRD
GMM HSB CRM FIN. FLOOR LINE, +200mm
STOCK AREA
D D NATURAL GRADE LINE, 0.00mm

1000
3 3 HALL WAY

2 HDPP
3 LONGITUDINAL SECTION

1000
MPVS
3 A 3 SCALE 1:80m
A-2 STORAGE
A B C
3125
&
ADMINISTRATIVE DISPLAY AREA
OFFICE HDPP HDPP
ALUMINUM SLIDING
WINDOW W/ 6mm THK. GLASS S.798

3
FIN. FLOOR LINE
ELEV. +200mm
FIN. PARAPET LINE, +4100mm
ramp FIN. GRADE LINE

9000
dn ELEV. 0.00mm
2 FIN. ROOFDECK FLOOR LINE, +3200mm
SEE SLAB DETAILS
A-2

1 SSF EQUIPMENT LAY-OUT

4100
3200
A 2 SCALE 1:80m
ADMIN. OFFICE DISPLAY AREA

900
WORKSTATIONS
FIN. FLOOR LINE, +200mm

NATURAL GRADE LINE, 0.00mm

A B C
1 TRAVERSE SECTION
4000 4000 A 3 SCALE 1:80m

2300 2300 3400


A B C
4000 4000

2300 3400 80012


WF-01 WF-01
1
WF-01 1000
WF-01

WF-01
3125

CF-03
FF-03 FF-03
1
FF-03

2 2300

3125
CF-02
FF-03 WF-01
FF-03
3125

FF-01 FF-03
2 CF-02

WF-01
LEGEND 3

3125
WF-01 WF-01 LEGEND CF-02 CF-02
1200

WF-01 CEMENT PLASTER FINISH FF-03


POLYCARBONATE SHEETS SECURED
CF-01
ON STEEL TUBE 2" x 4" FRAMING
600mmX600mm PORCELAIN
FF-01 (VERIFY HEIGHT)
HOMOGENOUS TILES 3

1200
FF-02 300mmX300mm UNGLAZED CERAMIC 4.5mm THK. FICEM BOARD CEILING CF-03
TILES CF-02
2 FLOOR PATTERN LAYOUT ON METAL FURRING ON FLAT LATEX
PAINT FINISH (VERIFY HEIGHT)
FF-03 ROUGH CEMENT PLASTER FINISH
A 3 SCALE 1:80m CF-03 4.5mm THK. FICEM BOARD
CEILING, PAINT FINISH
4 REFLECTED CEILING PLAN
A 3 SCALE 1:80m
PEOPLES ORGANIZATION BENEFICIARY: SET SHEET
DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY SSF EQUIPMENT LAY-OUT


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE SECTIONS
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER FLOOR PATTERN LAY-OUT 3 3
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA REFLECTED CEILING PLAN
BUILDING DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR A-4 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
2800 X
1300 1500 1300

D D D D
1 2 3 4 300mmX300mm
UNGLAZED
CERAMIC TILES
900 800 600

2700

2000
2100

2100

2000
Y

FINISHED FLOOR LINE


DESCRIPTION SOLID WOOD PANEL DOOR DESCRIPTION SOLID WOOD PANEL DOOR DESCRIPTION FLUSH TYPE SWING DESCRIPTION CURTAIN STEEL
JAMP (2.1X9M) JAMP (2.1x8M)
PVC DOOR ROLL-UP DOOR
AREA 3.78 sq.m AREA 1.47 sq.m AREA 2.4 sq.m AREA 7.56 sq.m PLAN
QUANTITY 2 QUANTITY 1 QUANTITY 2 QUANTITY 1
LOCATION MAIN ENTRANCE LOCATION WORKSTATIONS LOCATION CR, DRESS ROOM LOCATION WORKSTATIONS

1 DOORS SCHEDULE
A 4 SCALE 1:50m
4.5mm THK. FIBEM BOARD
CEILING ON METAL FURRING
ON FLAT LATEX PAINT FINISH
2800 1920 (2.75m HEIGHT)
2700
725 675 675 725 1350 1350
960 960 PLASTERED CHB WALL,
FINISHED PAINT

TISSUE PAPER HOLDER


W W W
1 2 3 SIPHON VORTEX
WATER CLOSET

WALL HUNG
1200

1200

1200

3050
LAVATORY
900

900

900
FINISHED FLOOR LINE

1100
DESCRIPTION ALLUMINUM SLIDING WINDOW DESCRIPTION ALLUMINUM 1FRAMED SLIDING DESCRIPTION ALLUMINUM FRAMED SLIDING

800
750
WINDOW W/ 4" THK. GLASS WINDOW W/ 14" THK. GLASS
W/ 41" THK. GLASS S. 798 S. 798 S.798
AREA 3.36 sq.m AREA 6.48 sq.m AREA 2.3 sq.m
4.5mm THK. FIBEM BOARD
QUANTITY 1 QUANTITY 2 QUANTITY 1
CEILING ON METAL FURRING
LOCATION WORKSTATIONS LOCATION WORKSTATIONS LOCATION WORKSTATIONS, ADMIN OFFICE ON FLAT LATEX PAINT
S E C T I O N T H R U "X" FINISH (2.75m HEIGHT)

POWDER COATED ALUMINUM


2100 1500 1940 AWNING TYPE WINDOW W/ 6mm
THK. COATED GLASS (REFLECTIVE)
1050 1050 750 750 970 970 600 PLASTERED CHB WALL,
FINISHED PAINT

W W
6 7 SIPHON VORTEX WATER
W W
4 5 CLOSET

WALL HUNG LAVATORY


1800

1800

600
1200

3050
300mmX300mm UNGLAZED CERAMIC
TILES
1750

1500
900

900
900

1100

800
FINISHED FLOOR LINE

DESCRIPTION ALLUMINUM FRAMED FIX DESCRIPTION ALLUMINUM FRAMED FIX DESCRIPTION ALLUMINUM FRAMED SLIDING DESCRIPTION POWDER COATED FRAMED AWNING
WINDOW W/ 14" THK. GLASS S.798 WINDOW W/ 41" THK. GLASS WINDOW W/ 14" THK. GLASS
WINDOW W/ 14" THK. GLASS S. 798 S. 798 S.798 S E C T I O N T H R U "Y"
AREA 7.56 sq.m AREA 2.7sq.m AREA 2.33 sq.m AREA 1.08 sq.m
QUANTITY 2 QUANTITY 1 QUANTITY 1 QUANTITY 2
LOCATION ADMIN OFFICE LOCATION ADMIN OFFICE LOCATION WORK STATION LOCATION CR, DRESS ROOM

2 WINDOW S S C H E D U L E 5 TOILET BLOW-UP PLAN


A 4 SCALE 1:50m A 3 SCALE 1:30m
PEOPLES ORGANIZATION BENEFICIARY: SET SHEET
DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY SCHEDULE OF DOORS


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE SCHEDULE OF WINDOWS
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER TOILET BLOW-UP PLAN 4 4
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
BUILDING DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR A-4 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
3.0 FOUNDATION ENGINEER PRIOR TO FABRICATION & INSTALLATION
GENERAL NOTES 3.1. FINISHED GRADE LINE SHALL BE 95 DEGREE OF COMPACTION. 4.2.8 DEVELOPMENT LENGTH (Ld) OF REINFORCING BARS SHALL BE AS FOLLOWS:
3.2. ASSUMED SOIL BEARING CAPACITY SHALL BE 96 KPa (2,000 PSF) SIZE OF REBARS DEVELOPMENT LENGTH
1.0 STANDARDS AND REFERENCES 3.2.1 IN CASE THE ACTUAL LOCATION OF THE STRUCTURE IS LESS THAN THE
ASSUMED DISTANCE FROM THE SEISMIC SOURCE OF 40km; NOTIFY THE DIRECTOR, 10mm 170mm
THE FOLLOWING SHALL GOVERN THE DESIGN, FABRICATION AND CONSTRUCTION OF
THE PROJECT. BUREAU OF DESIGN FOR PROPER REVISION OF THE DESIGN. REFER TO THE SEISMIC 12mm 220mm
1.1. NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (N.S.C.P.) VOL. 1. 6TH EDITION, SOURCE MAP PROVIDED IN THE NATIONAL STRUCTURAL CODE OF THE PHILIPPINES OR
PHIVOLCS SEISMIC SOURCE MAP. 16mm 270mm
2010.
3.2.2 SOIL TEST SHALL BE CONDUCTED PRIOR TO START OF CONSTRUCTION. 20mm 380mm
2.0 DESIGN CRITERIA 3.2.3 IN CASE THE ACTUAL SOIL BEARING IS LESS THAN THE ASSUMED, 96 kPa; NOTIFY THE 25mm 600mm
DIRECTOR, BUREAU OF DESIGN FOR PROPER REVISION OF FOUNDATION.
2.1.LOADINGS 3.2.4 NO FOOTING SHALL REST ON FILL. 4.3 STRUCTURAL STEEL
A. DEAD LOAD 3.2.5 BOTTOM OF FOOTING SHALL BE AT LEAST 1.00m. BELOW NATURAL GRADE LINE. 4.3.1 ALL STRUCTURAL STEEL SHALL CONFORM TO ASTM A36 AND SHALL HAVE MINIMUM YIELD
CONCRETE - 23.56 kN/m³ STRESS, Fy = 248 MPa (36,000 psi)
3.2.6 SOIL BEARING CAPACITY SHALL BE INCREASE BY 33% WHEN IN COMBINATION WITH
STEEL - 76.93 kN/m³
SEISMIC OR WIND LOAD. 4.3.2 ALL STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH THE
150mm THK. CHB WALL - 2.73 kPa
100mm THK. CHB WALL - 2.11 kPa
3.3 ALL COLUMN FOOTINGS & TIE BEAMS SHALL REST ON 100mm THK. WELL COMPACTED GRAVEL AISC SPECIFICATIONS AND CODE OF STANDARD PRACTICE AS AMMENDED TO DATE.
B. LIVE LOAD BASE COURSE.
4.3.3 ALL BOLTS SHALL CONFORM TO THE ASTM A-307 UNLESS OTHERWISE INDICATED.
ROOF - 1.0 kPa 3.4 BACK FILL SHALL BE PLACED IN LAYER AND EACH LAYER SHALL BE 200mm THE AND SHALL BE
CLASSROOMS, LABORATORY - 1.90 kPa COMPACTED TO 95% MAXIMUM DRY DENSITY. 4.3.4 SHOP AND FIELD WELDING SHALL BE IN ACCORDANCE WITH AWS D1.1 AND PERFORMED
TOILETS - 2.40 kPa BY BY QUALIFIED WELDERS.
CORRIDOR ABOVE, STAIRS - 3.80 kPa 3.5 WHERE LOOSE/SOFT MATERIAL IS ENCOUNTERED AT DEPTH OF EMBEDMENT INDICATED,
4.3.5 UNLESS OTHERWISE INDICATED, WELDING ELECTRODES SHALL BE E60.
CORRIDOR ON GROUND - 4.80 kPa EXCAVATE TO FIRM LAYER AND REPLACE LOOSE/MATERIALS UNDERNEATH THE FOOTING
C. WIND LOAD (NSCP 2010) WITHIN THE FOOTING AREA PLUS 1/2 DEPTH OF SOFT MATERIAL ON ALL SIDES WITH SELECT 4.3.6 NO STEEL SHALL BE FABRICATED OR ERECTED UNTIL SHOP DRAWINGS HAVE BEAN
BASIC WIND VELOCITY, V=250 KPH GRANULAR BACKFILL. COMPACT SELECT GANULAR BACKFILL TO 95% OF MAXIMUM DRY APPROVED BY THE STRUCTURAL ENGINEER.
P = qh [(GCpf) - (GCpi)] (DESIGN WIND PRESSURE) DENSITY. 4.3.7 WELDS (CONFORM WITH AMERICAN WELDING STANDARDS) USING E 60xx ELECTRODES.
WHERE: qh = VELOCITY PRESSURE, kPa
GCpf = EXTERNAL PRESSURE COEFFICIENT fy = 93.77MPa.
GCpi = INTERNAL PRESSURE COEFFICIENT 4.0 MATERIALS 4.3.8 ANCHOR BOLTS (CONFORM WITH ASTM A-307) ft = 96.60 MPa., fv = 69 MPa.
D. SEISMIC LOAD (NSCP 2010)
V = CvI / RT W (DESIGN BASE SHEAR) 4.1 CONCRETE 4.3.9 BENDS & HOOKS
Vmax = 2.50 Cal / R W Vmin = 0.11 CalW 4.1.1 CONCRETE COVER OVER REINFORCING BARS SHALL BE AS FOLLOWS: HOOKS AND BENDS SHALL BE AS SHOWN IN THE FOLLOWING TABLE
Vmin = 0.8 ZNvI / R W (ZONE 4) A. FOOTINGS, FOOTING-TIE BEAMS (CAST AGAINST EARTH) 75mm A

Do
Do
db
WHERE: W = TOTAL DEAD LOAD B. BEAMS AND COLUMNS (TO STIRRUPS AND TIES) 40mm

A
SIZE END HOOKS STIRRUP & TIE STIRRUP END HOOK
T = NATURAL PERIOD = Ct (hn)² ³ C. WALLS, SIDE OF FOOTIN-TIE BEAMS (CAST AGAINST FORMS) 40mm TIE A
OF

A
WHERE: C = NUMERICAL COEFFICIENT D. SUSPENDED SLAB 20mm BARS 180° 90° 90° 135° 135°
h = BUILDING HEIGHT 4.1.2 BEFORE CONCRETE IS POURED, CHECK WITH ALL TRADES TO ENSURE PROPER 10 125 150 100 100 125
I = IMPORTANCE FACTOR = 1.50 PLACEMENT OF ALL OPENINGS, SLEEVES, CURBS, CONDUITS, ETC. RELATING TO THE

D
db db
WORK. 12 150 200 113 113 163 db
R = NUMERICAL FACTOR = 8.50
4.2 REINFORCING BARS STIRRUP & TIE HOOK STIRRUP - TIE
16 175 250 150 138 200
SEISMIC COEFFICIENT Cv = 0.44Nv 4.2.1 ALL REINFORCING BARS SHALL BE CLEAN OF RUST, GREASE OR OTHER Do = 6 db for db < 30 D = 4 db for db < 20
Ca = 0.64N MATERIALS THAT WILL IMPAIR BOND. Do = 8.7 db for db > 30 D = 6 db for db > 30
4.2.2 ALL REINFORCING BARS SHALL BE ACCURATELY AND SECURELY PLACED
NEAR SOURCE FACTOR (10km) Nv = 1.2 BEFORE POURING CONCRETE OR APPLYING MORTAR OR GROUT.
Na = 1.0 4.2.3 LAPPED SPLICES SHALL BE STAGGERED WHERE POSSIBLE. 4.4 CONCRETE HOLLOW BLOCKS (CHB):
Z = SEISMIC ZONE = 0.4 (ZONE 4) 4.2.4 UNLESS OTHERWISE INDICATED, SPLICING OF REINFORCEMENT SHALL BE IN ACCORDANCE
WITH ACI-318M, EXCEPT THAT THE MINIMUM LAP SPLICE SHALL BE 40 BAR DIAMETER BUT 4.4.1 UNLESS OTHERWISE INDICATED, CHB USED IN THIS WORK SHALL HAVE A MINIMUM
S = SOIL TYPE = 0 NOT LESS THAT 600mm. ULYIMATE COMPRESSIVE STRENGTH f'm = 3.45MPa (500psi)
2.1. DESIGN STRESSES 4.2.5 UNLESS SHOWN OTHERWISE ON PLANS, SPLICES SHALL BE AS FOLLOWS: 4.4.2 ALL CHB CELLS SHALL BE FILLED SOLIDLY WITH GROUT.
A. CONCRETE A. INTERMEDIATE BEAMS: TOP BARS SHALL BE SPLICED AT MID-SPAN, BOTTOM BARS
COMPRESSIVE STRENGTH @ 28 DAYS fc' = 20.7 MPa (3,000 psi) AT THE SUPPORT.
B. BEAMS FRAMING TO COLUMNS: TOP BARS SHALL BE SPLICED AT MID-SPAN AND 5.0 CONSTRUCTION JOINT
B. REINFORCING BARS
BOTTOM BARS SHALL NOT BE SPLICED WITHIN THE COLUMN OR WITHIN A 5.1 CONSTRUCTION JOINT NOT INDICATED ON THE PLANS SHALL BE MADE SO AS TO LEAST OF
a. FOR BARS 16mmØ AND GREATER fy = 275 MPa (40,000 psi)
DISTANCE OF TWICE THE MEMBER DEPTH FROM THE FACE OF THE COLUMN. THE THE IMPAIR THE STRENGTH OF THE STRUCTURE AND SHALL BE SUBJECT TO THE APPROVAL OF THE
b. FOR BARS LESS THAN 16mmØ fy = 230 MPa (33,000 psi) SPLICED LENGTH SHALL NOT BE LESS THAN 1.4 TIMES THE DEVELOPMENT LENGTH ENGINEER EXCEPT SLAB ON GRADE.
(Ld) IN 4.2.8
C. STRUCTURAL STEEL, ASTM-A36 5.2 UNLESS SHOWN OTHERWISE, SLAB ON GRADE SHALL HAVE CONTROL JOINTS SPACED AT
C. COLUMNS: LAP SPLICES SHALL BE MADE WITHIN THE CENTER HALF OF HEIGHT AND
FOR TRUSSES, BRACINGS AND STRUTS fy = 248 MPa (36,000 psi) THE SPLICE SHALL NOT BE LESS THAN 30 BAR DIAMETER. WELDING OR THE USE OF 6000mm MAXIMUM CENTER TO CENTER.
D. PURLINS APPROVED MECHANICAL DEVICES MAY BE PERMITTED PROVIDED NOT MORE THAN 5.3 BEAM CONSTRUCTION JOINT SHALL BE LOCATED WITH IN THE MIDDLE THIRD SPAN. IT
ALTERNATE BARS ARE WELDED OR SPLICED AT ANY LEVEL AND THE MINIMUM SHALL BE PROVIDED WITH 3 EXTRA STIRRUPS @ 75mm O.C. ON EACH SIDE OF THE JOINT.
COLD FORMED LIGHT CAGE SHAPES fy = 248 MPa (36,000 psi) VERTICAL DISTANCE BETWEEN TWO ADJACENT BAR SPLICES SHALL BE 600mm.
E. MASONRY UNIT (CHB) D. CHB WALLS: VERTICAL BARS SHALL BE SPLICED AT THE TOP WALL FOOTINGS OR
NON-LOAD BEARING CHB WALLS fm' = 3.45 MPa (500 psi) FOOTING-TIE BEAMS AND AT THE BOTTOM OF REINFORCED CONCRETE LINTEL
BEAMS OR BEAMS.
F. WELDS-USED E-60xx ELECTRODE 4.2.6 UNLESS OTHERWISE INDICATED: ALL BEAMS TERMINATING AT A COLUMN SHALL HAVE
G. STRUCTURAL BOLTS, ASTM-A307 TOP AND BOTTOM BARS EXTENDING TO THE FAR FACE OF THE COLUMN, TERMINATING IN
A STANDARD 90 HOOK LENGTH OF ANCHORAGE SHALL NOT BE LESS THAN 600mm.
a. Ft = 96.60 MPa (14,000 psi)
4.2.7 SHOP DRAWING FOR REINFORCEMENT SHALL BE SUBMITTED FOR APPROVAL OF THE
b. Fv = 69 MPa (10,000 psi)

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY GENERAL NOTES


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER 1 5
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
A B C A B C A B C
4000 4000 1000 4000 4000 1000 4000 4000

1750

#16@225 C/C

#16@225 C/C
1250 1300 B4 CB4 S2 S3
#16@225 C/C

CB2

CB2

CB2
CB3 B3 B4 CB4

1750

1250

1300
3 3 3
C1 C1 C1 C1 C1 C1 C1 C1 C1
#16@225 C/C #16@225 C/C

#16@225 C/C

#16@225 C/C

#16@225 C/C

#16@225 C/C
FC2 FC3 S4 S1 S1
FC1 S4

3125
3125
3125

B2

B2

B2

B2

B2
1250 1250 1300

#16@225 C/C #16@225 C/C


CB3 B3 B4 CB4 S
1250

1250

1300
2 2 2 C1 C1 C1
C1 C1 C1 C1 C1 C1 1 4
#16@225 C/C #16@225 C/C

#16@225 C/C

#16@225 C/C

#16@225 C/C

#16@225 C/C
FC4 FC5 FC6 S4 S1 S1 S4

3125
3125
3125

B1

B1

B1

B1
B1
1300 1250 1350

#16@225 C/C #16@225 C/C

#16@225 C/C

#16@225 C/C
CB3 B3 B4 CB4 S3 S2 S2 S3
1300

1250

1350
1 1 1 #16@225 C/C
C1 C1 #16@225 C/C
C1 C1 C1 C1 C1 C1

1000

CB1
#16@225 C/C #16@225 C/C

CB1

CB1

CB1
CB1
CB3 B3 B4 CB4
FC7 FC8 FC9

S SLAB S1,S2,S3,S4:(150MM THK)


3 3

1 FOUNDATION PLAN 2 ROOFDECK BEAM PLAN 3 SLAB REINFORCEMENT PLAN


S 2 SCALE 1:80m
S 2 SCALE 1:80m
S 2 SCALE 1:80m

R.C. FOOTING
BLINDING
50mm.THK WELL COMPACTED CRUSHER FINE

B 150 THK.SAND LAYER WELL COMPACTED ( 95% MIN.)

300 150
A B C A B C 300 mm. DESERT FILL TYPE A
(WELL COMPACTED USING 20T VIBRO ROLLER )
3 TO 6 HARD CORE

300
(WELL COMPACTED USING 20T VIBRO ROLLER )
4000 4000 1000 4000 4000 1000

600
6 TO 9 HARD CORE
(WELL COMPACTED USING 20T VIBRO ROLLER )
1100 * THIS PROPOSAL OF STRUCTURAL FILLING ONLY APPLICABLE UNDER THIS CONDITION.
* BEARING CAPACITY FOR THE SOIL SHOULD BE VERIFIED BY THE CONTRACTOR
S2 S3
TO SATISFY HIMSELF AND ENGINEER APPROVAL .

CB2
GB2 GB2 CB3 B3 B4
3 3
C1 C1 C1 100mm THK. SLAB W/ 10mm C1 C1 C1
Ø TEMP. BARS SPACED @
400mm ON CENTER BOTHWAYS S4 S1 S1 S4
6 TYP. SEC. VARIOUS FILLING & THEIR LEVELS
3125

GB1

GB1

GB1

GB1

3125

B2

B2

B2

B2

B2
S 2 SCALE NTS

2 C1
GB2
C1
GB2
C1 1
S
3
2
CB3
C1
B3
C1
B4 CB4
C1
SLOPE SLOPE
S4 S1 S1 S4
0.25% CL 0.25%
3125

A
GB1

GB1

GB1

GB1

3125

A
B1

B1

B1

B1
B1

GB2 GB2 CB3 B3 B4 CB4


1 S3 S2 S2 S3
C1 C1 C1
1 C1 C1 C1
1000

CB1

CB1
5000 5000
CB1

B3 B4
S
2 3

B
L=10000

4 GROUND BEAM FRAMING PLAN 5 SLAB PLAN 7 SLAB GRADE LINE


S 2 SCALE 1:80m
S 2 SCALE 1:80m S 2 SCALE NTS

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:
CONSTRUCTION OF ONE-STOREY FOUNDATION PLAN
REPUBLIC OF THE PHILIPPINES
ROOFDECK BEAM PLAN
DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER
SLAB REINFORCEMENT PLAN
GROUND BEAM FRAMING PLAN
2 6
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR SLAB PLAN
SLAB GRADE LINE DETAIL
S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
250 250 250

3-#16 3-#16 3-#16

1049.4(ANCHORAGE)

1049.4(ANCHORAGE)

350

350

350
A 1 2 3 B 1 2 3 C STP 2L-#10 STP 2L-#10 STP 2L-#10
2-#16 2-#16 2-#16
320 320 320
3680 3680
(LOC: 0 TO 920) (LOC: 920 TO 2760) (LOC: 2760 TO 3680)
920 920 920 920
SECTION 1-1 (GB2) SECTION 2-2 (GB2) SECTION 3-3 (GB2)
3-#16 3-#16 3-#16 3-#16 3-#16 3-#16
(SCALE 1:25) (SCALE 1:25) (SCALE 1:25)
1049.4(ANCHORAGE)

1049.4(ANCHORAGE)
2-#16 2-#16

38-2L-#10 38-2L-#10
@100 C/C @100 C/C

1 2 3 1 2 3
C1 C1 C1
GB2:250x350 GB2:250x350
(SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50)
1 TYP. GROUND BEAM SECTION A DETAIL
S 3 SCALE 1:80m

1 1 2 3 2 1 2 3 250 250 250


627(ANCHORAGE)

627(ANCHORAGE)
320 320 320
2805 2805 3-#16 3-#16 3-#16

350

350

350
STP 2L-#10 STP 2L-#10 STP 2L-#10
3-#16 2-#16 3-#16
3-#16 3-#16
(LOC: 0 TO 705) (LOC: 705 TO 2100) (LOC: 2100 TO 2805)
SECTION 1-1 (GB1) SECTION 2-2 (GB1) SECTION 3-3 (GB1)
627(ANCHORAGE)

627(ANCHORAGE)
3-#16 2-#16 3-#16 3-#16 2-#16 3-#16 (SCALE 1:25) (SCALE 1:25) (SCALE 1:25)
705 705 705
30-2L-#10 30-2L-#10
@100 C/C @100 C/C

C1 1 2 3 C1 1 2 C1
GB1:250x350 GB1:250x350
(SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50)

2 TYP. GROUND BEAM SECTION B DETAIL


S 3 SCALE 1:80m

250 250 250 250


1 1 1 2 3 2 1 2 3 3 1 STP 2L-#10
890.4(ANCHORAGE)
890.4(ANCHORAGE)

3-#16 3-#16
320 320 320 2-#16 2-#16 2-#16 3-#16
840 2805 2805 840

300

300

300

300
SFR 1-#16EF STP 2L-#10 STP 2L-#10 STP 2L-#10
840 705 705 840
3-#16 3-#16 2-#16 2-#16
3-#16 2-#16 3-#16 2-#16 3-#16
2-#16 CB1 (LOC: 0 TO 840) (LOC: 840 TO 2100) (LOC: 2100 TO 2805)
1 - T15.9 EF 1 - T9.5 EF 1 - T15.9 EF (SCALE 1:25) SECTION 1-1 (B1) SECTION 2-2 (B1) SECTION 3-3 (B1)
(SCALE 1:25) (SCALE 1:25) (SCALE 1:25)
532(ANCHORAGE)

3-#16 3-#16 2-#16 3-#16


430 840 430
10-2L-#10 30-2L-#10 30-2L-#10 10-2L-#10
@100 C/C @100 C/C @100 C/C @100 C/C 250 250 250 250

3-#16 2-#16 3-#16 3-#16


1 C1 1 2 3 C1 1 2 3 C1 1 STP 2L-#10 STP 2L-#10 STP 2L-#10 STP 2L-#10
300

300

300

300
SFR 1-#16EF SFR 1-#16EF SFR 1-#16EF SFR 1-#16EF
CB1:250x300 B1:250x300 B2:250x300 CB2:250x300 2-#16 2-#16 2-#16 3-#16
(SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50)
(LOC: 0 TO 705) (LOC: 705 TO 1965) (LOC: 1965 TO 2805) CB2
SECTION 1-1 (B2) SECTION 2-2 (B2) SECTION 3-3 (B2) (SCALE 1:25)
(SCALE 1:25) (SCALE 1:25) (SCALE 1:25)

3 TYP.ROOFDECK BEAM SECTION B DETAIL


S 3 SCALE 1:80m

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY AS SHOWN


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER 3 7
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
1 A 1 2 3 4 B 1 2 3 C 1

890.4(ANCHORAGE)
890.4(ANCHORAGE)
250 STP 2L-#10 250 250 250 250
320 320 320
840 3680 3680 840 3-#16 3-#16 3-#16 3-#16
920 920 920 920 2-#16 2-#16 2-#16 3-#16 2-#16

300

300

300

300

300
SFR 1-#16EF STP 2L-#10 STP 2L-#10 STP 2L-#10 STP 2L-#10
3-#16 3-#16 3-#16 3-#16 3-#16
2-#16 2-#16 2-#16 3-#16 2-#16 3-#16 3-#16 3-#16
1 - T15.9 EF 1 - T9.5 EF
CB3 (LOC: 0 TO 840) (LOC: 840 TO 920) (LOC: 920 TO 2760) (LOC: 2760 TO 3680)
SECTION 1-1 (B3) SECTION 2-2 (B3) SECTION 3-3 (B3) SECTION 4-4 (B3)
532(ANCHORAGE)
(SCALE 1:25)
3-#16 2-#16 3-#16 3-#16
430 840 (SCALE 1:25) (SCALE 1:25) (SCALE 1:25) (SCALE 1:25)
10-2L-#10 38-2L-#10 38-2L-#10 10-2L-#10
@100 C/C @100 C/C @100 C/C @100 C/C

1 C1 1 2 3 4 C1 1 2 3 C1 1
250 250 250 250
CB3:250x300 B3:250x300 B4:250x300 CB4:250x300 STP 2L-#10
(SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50) 3-#16 3-#16 3-#16
2-#16 3-#16 2-#16 2-#16

300

300

300

300
STP 2L-#10 STP 2L-#10 STP 2L-#10 SFR 1-#16EF
3-#16 3-#16 3-#16 3-#16

(LOC: 0 TO 920) (LOC: 920 TO 2760) (LOC: 2760 TO 3680) CB4


SECTION 1-1 (B4) SECTION 2-2 (B4) SECTION 3-3 (B4) (SCALE 1:25)

A
1 TYP.ROOFDECK BEAM SECTION A DETAIL B (SCALE 1:25) (SCALE 1:25) C (SCALE 1:25)

S 4 SCALE 1:80m

250 250 250 250 250


750 2880 2880 750
190 190 720 720 720 720 190 190
#16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C

#16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C

#16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C


B1 B1 B1 B1 B1
#16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C

SLAB S4 SLAB S1 SLAB S1 SLAB S4


(ONE WAY) (150 THK) (TWO WAY) (150 THK) (TWO WAY) (150 THK) (ONE WAY) (150 THK)

2 SLAB SECTION A-A


3 2 1
S 4 SCALE 1:80m

250 250 250 250 250


750 2880 2880 750
190 190 720 720 720 720 190 190
#16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C

#16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C

#16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C


B4 B4 B4 B4 B4
#16@225 C/C #16@225 C/C #16@225 C/C #16@225 C/C

SLAB S2 SLAB S1 SLAB S1 SLAB S2


(ONE WAY) (150 THK) (TWO WAY) (150 THK) (TWO WAY) (150 THK) (ONE WAY) (150 THK)

SECTION B-B

3 SLAB SECTION B-B


SCALE 1:80m
S 4
PEOPLES ORGANIZATION BENEFICIARY: SET SHEET
DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY AS SHOWN


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER 4 8
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
3

EL. 4.200 COVER = 40MM


TOC CONFINING ZONE = 450 MM

@125 C/C
(2),(3) #10
2 1.2M

750
(1) 8-#16

@150 C/C
(2),(3) #10
Z1 MAIN LINK Z1 OTHERS Z2 LINKS

425
1 1 TO
#10 @ 125 #10 @ 125 #10 @ 150

480
@150 C/C
(2),(3) #10
4.2M

320
955
#16

480
320

@150 C/C
(2),(3) #10 8-#16
320

(1) 8-#16

1350
C25 : COVER = 50MM

425
CONFINING ZONE = FULL HEIGHT
@125 C/C
(2),(3) #10

EL. 1.200
320
450
0M
TOC
@125 C/C
(2),(3) #10

SECTION 1-1 TO
Z1 MAIN LINK Z1 OTHERS Z2 LINKS

(SCALE 1:25) (1) 8-#16 #10 @ 125 #10 @ 125 ---


300

@150 C/C
(2),(3) #10

EL. 0 1.2M
230

1 1 BOF

320
#16
320

8-#16

1 TYPICAL C O L U M N D E T A I L S COLUMN MARKED C1


S 5 SCALE 1:50m

COLUMN AND WALL SCHEDULE


(SCALE 1:25)
NOTES:
1. BE = BOUNDARY ELEMENT AS PER ACI 318. PROVIDE CONFINING REINFORCEMENT ACROSS ENTIRE HEIGHT OF WALL IN THE BOUNDARY ELEMENT
2. Z1 = SPECIAL CONFINING ZONE AS PER ACI 318, Z2 = REMAINING ZONES AS PER ACI 318

CONCRETE HOLLOW BLOCKS REINFORCEMENT

REINFORCEMENT NOTES

THK. HORIZONTAL VERTICAL A. MINIMUM SPLICE AT LAP= 250mm 3 C O L U M N SECTION & D E T A I L S


100mm 10mm Ø @ EVERY THREE LAYER OF CHB 10mm Ø @ 600mm O.C. B. WHERE CHB WALLS ADJOINING COLUMN, R.C. BEAM,
WALL DOWEL W/ SAME SIZE AS VERTICAL OR
S 5 SCALE 1:50m
150mm 10mm Ø @ 600mm O.C. 10mm Ø @ 600mm O.C. HORIZONTAL REINFORCEMENT SHALL BE PROVIDED

2 CONCRETE HOLLOW BLOCKS NOTES


S 5 SCALE NTS

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY COLUMN DETAIL


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE CONCRETE HOLLOW BLOCK NOTES
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER COLUMN SECTION & DETAIL 5 9
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
100mm X 200mm LINTEL BEAM W/
note:PROVIDE LINTEL BEAM FOR DOOR OPENING, 2-12mmØ CONTINUOUS BARS W/ 10mmØ
STIFFENER BEAM FOR WINDOW OPENING TIES SPACED @ 100mm O.C.

COLUMN LINKS

COLUMN LINKS
A 100mm THK. CHB W/ 2-12mmØ VERTICAL
1-16mmØ VERTICAL DEFORMED BAR
BARS SPACED @ 0.60m AND HORIZONTAL
BARS @ EVERY THREE LAYER OF CHB

LD

LD
100mm THK. CHB W/ 2-12mmØ VERTICAL
BARS SPACED @ 0.60m AND HORIZONTAL BARS
@ EVERY THREE LAYER OF CHB
100mm X 200mm LINTEL BEAM W/
2-12mmØ CONTINUOUS BARS W/ 10mmØ
TIES SPACED @ 100mm O.C.

EL. 0.000 EL. 0.000


varies

varies
BOF BOF

L B

SECTION 1-1 SECTION 2-2

200
DETAIL OF FOOTING FC DETAIL OF FOOTING FC OPENING

OPENING
2

100

#16 RSB
S E C T I O N T H R U "A"

4 L I N T E L B E A M DETAILS
#16 RSB
S 6 SCALE 1:10m

1 1
L

10mmØ TEMPERATURE BARS


SPACED @ 400mm O.C.B.W. FOR REINFORCEMENT, SEE
NOTE ON CONCRETE HOLLOW BLOCKS

VERIFY

300
B DOWELS TO MATCH CHB
300 HORIZONTAL BARS

3 SLAB ON FILL DETAIL


2 S 6 SCALE 1:10m

FOOTING FC- PLAN

10mmØ VERTICAL BARS SPACED


AT 600mm O.C.

10mmØ HORIZONTAL BARS SPACED


1 FOOTING D E T A I L MAIN REINFORCING BARS,
AT EVERY THREE LAYERS OF CHB 5 CHB TYPICAL CONNECTION DETAILS
SCALE 1:10m
S 6 10mmØ BENT BARS SPACED AT 200mm
O.C. PLACED ALTERNATELTY W/ 10mmØ
S 6 SCALE 1:10m

TOP AND BOOTOM CONTINOUS BARS TEMP. BARS SPACED AT 200mm O.C.
PROVIDES SHEAR RODS WHERE
JOINT IS @ POINT OF STRESS 10mmØ TEMPERATURE BARS SPACED
AT 200 mm O.C.
COMFORT ROOM
VERIFY

2 T Y P. S L A B J O I N T D E T A I L 4 SLAB DEPPRESSION DETAIL


S 6 SCALE 1:10m
S 6 SCALE 1:10m

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY


AS SHOWN
DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER 6 10
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
FOOTING SCHEDULE

FOOTING DIMENSION FOOTING REINFORCEMENT STIRRUPS


FOOTING COLUMN FOOTING SFR REMARKS
BOTTOM TOP
NUMBERS NUMBERS TYPE STEP L B D1 D2 ALONG B ALONG L
ALONG B ALONG L ALONG B ALONG L
FC1 C1 Pad - 1750 1750 500 - #16@220 C/C #16@220 C/C - - - - - -

FC2 C2 Pad - 1250 1250 500 - #16@210 C/C #16@210 C/C - - - - - -

FC3 C3 Pad - 1300 1300 500 - #16@220 C/C #16@220 C/C - - - - - -

FC4 C4 Pad - 1250 1250 500 - #16@210 C/C #16@210 C/C - - - - - -

FC5 C5 Pad - 1250 1250 500 - #16@210 C/C #16@210 C/C - - - - - -

FC6 C6 Pad - 1300 1300 500 - #16@220 C/C #16@220 C/C - - - - - -

FC7 C7 Pad - 1300 1300 500 - #16@220 C/C #16@220 C/C - - - - - -

FC8 C8 Pad - 1250 1250 500 - #16@210 C/C #16@210 C/C - - - - - -

FC9 C9 Pad - 1350 1350 500 - #16@225 C/C #16@225 C/C - - - - - -

GROUND BEAM SCHEDULE( LEVEL :1.2m)

BEAM SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT SHEAR STIRRUPS


SFR DIAGONAL REMARKS
NUMBERS B D LEFT MID SPAN RIGHT LEFT MID SPAN RIGHT LEFT MID SPAN RIGHT
GB1 250 350 3-#16 2-#16 3-#16 3-#16 3-#16 3-#16 8-2L-#10@100 C/C 14-2L-#10@100 C/C 8-2L-#10@100 C/C - - -

GB2 250 350 2-#16 2-#16 2-#16 3-#16 3-#16 3-#16 8-2L-#10@100 C/C 22-2L-#10@100 C/C 8-2L-#10@100 C/C - - -

SLAB SCHEDULE
BOTTOM REINFORCEMENT TOP REINFORCEMENT

SLAB SLAB ALONG SHORT SPAN ALONG LONG SPAN OVER LONG SUPPORT OVER SHORT SUPPORT REMARKS
MARKED THICKNESS DISTRIBUTION
FULL LENGTH CURTAILED FULL LENGTH CURTAILED CONTINUOUS END CONTINUOUS END
SUPPORT SUPPORT SUPPORT SUPPORT
S2,S4 150 #16 @ 225 C/C --- #16 @ 225 C/C --- #16 @ 225 C/C #16 @ 225 C/C --- #16 @ 225 C/C #16 @ 225 C/C ---

S3 150 #16 @ 225 C/C --- #16 @ 225 C/C --- #16 @ 225 C/C #16 @ 225 C/C #16 @ 225 C/C #16 @ 225 C/C #16 @ 225 C/C ---

S1 150 #16 @ 225 C/C --- #16 @ 225 C/C --- #16 @ 225 C/C --- #16 @ 225 C/C --- #16 @ 225 C/C ---

1 FOOTING, GROUNDBEAM & SLAB SCHEDULE


S 7 SCALE 1:50m

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:
CONSTRUCTION OF ONE-STOREY FOOTING, GROUND BEAM &
REPUBLIC OF THE PHILIPPINES
WITH ROOFDECK RICE SLAB SCHEDULE
DEPARTMENT OF TRADE AND INDUSTRY
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER 7 11
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
SIZE 320 X 320
1.2M
STEEL 8-#16
TO
LINKS #10@125 C/C + #10@150 C/C
4.2M
MATERIAL C21:Fy276

SCR ZONE 450

SIZE 320 X 320


0M
STEEL 8-#16
TO
LINKS #10@125 C/C + #10@150 C/C
1.2M
MATERIAL C21:Fy276

SCR ZONE FULL HEIGHT

COLUMN MARKED C1

TYPICAL COLUMN SCHEDULE

ROOFDECK BEAM SCHEDULE (C21:Fy 276) (LEVEL: 4.2m)

BEAM SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT SHEAR STIRRUPS


SFR DIAGONAL REMARKS
NUMBERS B D LEFT MID SPAN RIGHT LEFT MID SPAN RIGHT LEFT MID SPAN RIGHT
CB2 250 300 3-#16 3-#16 3-#16 3-#16 3-#16 3-#16 4-2L-#10@100 C/C 2-2L-#10@100 C/C 4-2L-#10@100 C/C 1-#16EF - CANTILEVERED

CB3,CB1 250 300 3-#16 3-#16 3-#16 3-#16 3-#16 3-#16 4-2L-#10@100 C/C 2-2L-#10@100 C/C 4-2L-#10@100 C/C 1-#16EF - CANTILEVERED
+ + +
2-#16 2-#16 2-#16

B3 250 300 2-#16 3-#16 3-#16 3-#16 3-#16 3-#16 7-2L-#10@100 C/C 24-2L-#10@100 C/C 7-2L-#10@100 C/C - - -
+ +
2-#16 2-#16

B4 250 300 3-#16 3-#16 3-#16 3-#16 3-#16 3-#16 7-2L-#10@100 C/C 24-2L-#10@100 C/C 7-2L-#10@100 C/C - - -
+ +
2-#16 2-#16

CB4 250 300 3-#16 3-#16 3-#16 3-#16 3-#16 3-#16 4-2L-#10@100 C/C 2-2L-#10@100 C/C 4-2L-#10@100 C/C 1-#16EF - CANTILEVERED
+ + +
2-#16 2-#16 2-#16

B1 250 300 3-#16 2-#16 2-#16 3-#16 2-#16 3-#16 7-2L-#10@100 C/C 16-2L-#10@100 C/C 7-2L-#10@100 C/C - - -
+
2-#16

B2 250 300 2-#16 2-#16 2-#16 3-#16 2-#16 3-#16 7-2L-#10@100 C/C 16-2L-#10@100 C/C 7-2L-#10@100 C/C 1-#16EF - -

1 COLUMN & ROOFDECK BEAM SCHEDULE


S 8 SCALE 1:50m

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY COLUMN & ROOFDECK BEAM


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE SCHEDULE
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER 8 12
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
1049.4(ANCHORAGE)

1049.4(ANCHORAGE)
A B C
320 320 320 ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS
3680 3680
MARK NOS. DIA. SHAPE LENGTH
(MM) A B C D E F G R
920 T2-3NOS-T16 920 920 920
B
T1-3NOS-T16 T3-3NOS-T16 T4-3NOS-T16 T5-3NOS-T16 GB2 T1 3 16 A 1650 516 1173 48
D
T2 3 16 C
A B F
G
E 2145 150 97 16 1650 16 97 150

1049.4(ANCHORAGE)
1049.4(ANCHORAGE)
A
B6-2NOS-T16 B7-2NOS-T16 T3 3 16 2160 2160
S8-38NOS-T10-@100 S9-38NOS-T10-@100 D
T4 3 16 C
A B F
G
E 2145 150 97 16 1650 16 97 150
B
T5 3 16 1650 516 1173 48
GB2:250x350 GB2:250x350 A

(SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50) B6 2 16 A


5775 703 5111 48
C1 C1 C1 B
E C A
B7 2 16 D 4570 703 2915 97 16 891 48
B
A
S8 38 10 B 1185 170 270 30
A
S9 38 10 B 1185 170 270 30

1 GROUND BEAM 2 BAR CUTTING LIST


SCALE NTS
S 9

1 2 3
627(ANCHORAGE)

627(ANCHORAGE)
320 320 320
2805 2805 ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS
MARK NOS. DIA. SHAPE LENGTH
705 (MM) A B C D E R
T1-3NOS-T16 T2-3NOS-T16 B
GB1 T1 3 16 A C
E
D 5835 228 5423 58 10 150 30
B
T2 3 16 1165 228 961 30
627(ANCHORAGE)

627(ANCHORAGE)
A
B3+B4-3NOS-T16 B5-1NOS-T16 B6-1NOS-T16 B7-1NOS-T16
A
705 705 705 B3 1 16 1235 322 935 30
B
S8-30NOS-T10-@100 S9-30NOS-T10-@100 A
B4 2 16 4185 322 3887 30
B

A
B5 1 16 4360 322 4060 30
B10:250x350 B11:250x350 B

C8 (SCALE: H = 1:50 / V = 1:50) C5 (SCALE: H = 1:50 / V = 1:50) C2 E C A


B6 1 16 D 3335 322 2446 58 10 532 30
B

A
B7 1 16 1235 322 935 30
B
A
S8 30 10 B 1185 170 270 30
A
S9 30 10 B 1185 170 270 30

2 GROUND BEAM 1 BAR CUTTING LIST


S 9 SCALE NTS

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY AS SHOWN


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER 9 13
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
S6DL-T10-@125
SUMMARY : C1

BAR DIA 10 16 TOTAL


ELEMENT BAR LEVEL BAR BAR BAR CUTTING DIMENSIONS
LGT (M) 61 44 105
MARK NOS. DIA. SHAPE LENGTH
(MM) A B C D E R
WT (KG) 36 66 102

S9DL-T10-@125
B
C1 B1 1 4 16 A C
E
D 3300 300 1153 97 16 1827 48
S7DL-T10-@125 B
B2 1 4 16 A C
E
D 2825 300 1153 97 16 1350 48
EL. 4.200
S5DL-T10-@125 TOC
B

S8DL TO S10DL
B3 2 4 16 D
E C A 1875 300 1028 97 16 477 48
B
B4 2 4 16 D 2350 300 1505 97 16 477 48

750
E C A
8-#16

S8L TO S10L
A
S5DL 1 7 10 B 1200 220 220 30
S10DL-T10-@125

425
2 2 A
S6DL 1 7 10 375 220 30

S8DL TO S10DL
S8DL-T10-@125
A
S7DL 1 7 10 350 204 30

955

B3

B3
A
S8L 2 4 10 B 1125 220 220 30

S8L TO S10L

B4
B1

B1
B2

S8DL TO S10DL
S8DL 2 18 10 1200 220 220 30

425
B
8-#16
B4 B4
8-#16 EL. 1.200 S9L 2 4 10
A
375 220 30

450
B2 B2
TOC
S5DL TO S7DL

B4
S9DL 2 18 10 375 220 30

B3

B3
B2

A
B1

B1

8-#16 S10L 2 4 10 350 204 30


300

EL. 0 S10DL 2 18 10
A
350 204 30
230
1 1 BOF

2 DETAIL OF COLUMN (C1)


1 DETAIL OF COLUMN (C1) E1 ELEVATION OF COLUMN C1 - (SCALE 1:25)
- (SCALE 1:25) - C25, Fy 420, COVER:50mm
(SCALE 1:50) /C
5C
22 #16@225 C/C
6@
#1
E1 450 ROOFDECK
E1

150
#16@225 C/C

1 TYPICAL COLUMN BAR CUTTING LIST


S 10 SCALE NTS

150 THK

3150.00
/C

15
0C
20

0.0
6@

00
#1

0
C /C
25
6 @2
#1
0
45 SECTION
#16@225 C/C
#16@225 C/C
#16@225 C/C
1000

0
150

45

#16@225 C/C
450
6000.00
#16@225 C/C

PLAN

1000.00

2 RAMP DETAIL
S 10 SCALE NTS

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY TYPICAL COLUMN BAR CUTTING LIST
DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE RAMP DETAIL
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER 10 14
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS
A B C MARK NOS. DIA. SHAPE LENGTH
(MM) A B C D E F G R
320 320 320
840 3680 3680 840
B
920 920 920 920 CB3, T1 3 16 A 2285 263 2060 48
T1-3NOS-T16 T3-3NOS-T16 T4-3NOS-T16 T6-3NOS-T16 T7-3NOS-T16 B3, B

T2-2NOS-T16 T5-2NOS-T16 T8-2NOS-T16 B4, T2 2 16 A 2195 231 2003 48


F19-2NOS-T16 F20-2NOS-T10 CB4 D
T3 3 16 C
A B F
G
E 2145 150 97 16 1650 16 97 150
SB21 SB22 SB23 SB24 A
B9+B10-3NOS-T16 B13-3NOS-T16 B14-3NOS-T16 T4 3 16 2160 2160
430 840 B12-1NOS-T16
B11-2NOS-T16 A
T5 2 16 2160 2160
S15-10NOS-T10-@100 S16-38NOS-T10-@100 S17-38NOS-T10-@100 S18-10NOS-T10-@100
D
C1 C1 C1 T6 3 16 C
A B F
G
E 2145 150 97 16 1650 16 97 150
CB3:250x300 B3:250x300 B4:250x300 CB4:250x300 T7 3 16
B
2285 263 2060 48
A
(SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50)
B
T8 2 16 A 2195 231 2003 48
A E
B9 2 16 C D 1035 263 164 97 16 532 30
B

A
B10 1 16 1030 263 792 30
B

A
B11 2 16 5745 5745
A
B12 1 16 4055 4055
D
B13 3 16 C
A B 4535 891 97 16 3547
E C A
B14 3 16 D 1035 263 164 97 16 532 30
B
A
S15 10 10 B 1170 210 260 30
A
S16 38 10 B 1245 210 260 30
A
S17 38 10 B 1245 210 260 30
A
S18 10 10 B 1170 210 260 30
B
F19 2 16 A 2565 150 2451 48
A
F20 2 16 820 820
A
SB21 1 16 230 230
A
SB22 2 16 230 230
A
SB23 2 16 230 230
A
SB24 1 16 230 230

2 TYP. ROOFDECK BEAM SECTION A BAR CUTTING LIST


SCALE NTS
S 9

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE ROOFDECK BEAM BAR
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER CUTTING LIST 11 15
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
1 2 3 ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS
MARK NOS. DIA. SHAPE LENGTH
320 320 320 (MM) A B C D E R
840 2805 2805 840
B
840 705 705 840 T1 1 16 2205 263 1980 48
CB1, B1 A

T1+T2-3NOS-T16 T4-1NOS-T16 B2, CB2 B


T3-2NOS-T16 T5-1NOS-T16 T6-1NOS-T16 T2 2 16 A 5195 263 4970 48
F17-2NOS-T16 F18-2NOS-T10 F19-2NOS-T16 B
T3 2 16 A 2115 231 1923 48
SB20 SB21 B
B7-3NOS-T16 B8+B9-3NOS-T16 B10-2NOS-T16 B11+B12-3NOS-T16 T4 1 16 5195 263 4970 48
A
430 840 430
B
S13-10NOS-T10-@100 S14-30NOS-T10-@100 S15-30NOS-T10-@100 S16-10NOS-T10-@100 T5 1 16 D
E C A 4350 255 3145 97 16 891 48
C1 C1 C1 T6 1 16
B
2205 263 1980 48
A

CB1:250x300 B1:250x300 B2:250x300 CB2:250x300 A E


(SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50) (SCALE: H = 1:50 / V = 1:50) B7 3 16 C D 1035 263 164 97 16 532 30
B

A
B8 1 16 1695 1695
A
B9 2 16 4870 4870
D
B10 2 16 C
A B 3660 891 97 16 2672
A
B11 1 16 1565 263 1324 30
B
E C A
B12 2 16 D 1035 263 164 97 16 532 30
B
A
S13 10 10 B 1170 210 260 30
A
S14 30 10 B 1245 210 260 30
A
S15 30 10 B 1245 210 260 30
A
S16 10 10 B 1170 210 260 30
B
F17 2 16 A 2565 150 2451 48
A
F18 2 16 2785 2785
A
F19 2 16 820 820
A
SB20 1 16 230 230
A
SB21 1 16 230 230

2 TYP. ROOFDECK BEAM SECTION B BAR CUTTING LIST


S 9 SCALE NTS

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE ROOFDECK BEAM BAR
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER CUTTING LIST 12 16
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
SUMMARY : FC1 SUMMARY : FC6
ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS BAR DIA 16 TOTAL ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS BAR DIA 16 TOTAL
MARK NOS. DIA. SHAPE LENGTH MARK NOS. DIA. SHAPE LENGTH
(MM) A B C D E R LGT (M) 32 32 (MM) A B C D E R LGT (M) 18 18
A C
FC1 B1 9 16 1805 150 1585 150 48 WT (KG) 50 50 FC6 B1 7 16 A C
1355 150 1135 150 48 WT (KG) 29 29
B
B
A C
B2 9 16 1805 150 1585 150 48 B2 7 16 A C
1355 150 1135 150 48
B
B

SUMMARY : FC2
ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS BAR DIA 16 TOTAL
MARK NOS. DIA. SHAPE LENGTH
(MM) A B C D E R LGT (M) 18 18

A C
FC2 B1 7 16 1305 150 1085 150 48 WT (KG) 28 28
B

B2 7 16 A C
1305 150 1085 150 48 SUMMARY : FC7
B

ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS BAR DIA 16 TOTAL
MARK NOS. DIA. SHAPE LENGTH
(MM) A B C D E R LGT (M) 18 18
SUMMARY : FC3
A C
FC7 B1 7 16 1355 150 1135 150 48 WT (KG) 29 29
ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS BAR DIA 16 TOTAL B
MARK NOS. DIA. SHAPE LENGTH A C
B2 7 16 1355 150 1135 150 48
(MM) A B C D E R LGT (M) 18 18 B

A C
FC3 B1 7 16 1355 150 1135 150 48 WT (KG) 29 29
B

A C
B2 7 16 1355 150 1135 150 48
B

SUMMARY : FC4
ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS BAR DIA 16 TOTAL
MARK NOS. DIA. SHAPE LENGTH
SUMMARY : FC8
(MM) A B C D E R LGT (M) 18 18
ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS BAR DIA 16 TOTAL
FC4 B1 7 16 A C
1305 150 1085 150 48 WT (KG) 28 28 MARK NOS. DIA. SHAPE LENGTH
B (MM) A B C D E R LGT (M) 18 18
A C
B2 7 16 1305 150 1085 150 48 A C
B FC8 B1 7 16 1305 150 1085 150 48 WT (KG) 28 28
B

A C
B2 7 16 1305 150 1085 150 48
B

SUMMARY : FC5
ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS BAR DIA 16 TOTAL
MARK NOS. DIA. SHAPE LENGTH
(MM) A B C D E R LGT (M) 18 18

A C
FC5 B1 7 16 1305 150 1085 150 48 WT (KG) 28 28
B

B2 7 16 A C
1305 150 1085 150 48
SUMMARY : FC9
B

ELEMENT BAR BAR BAR BAR CUTTING DIMENSIONS BAR DIA 16 TOTAL
MARK NOS. DIA. SHAPE LENGTH
(MM) A B C D E R LGT (M) 20 20

A C
FC9 B1 7 16 1405 150 1185 150 48 WT (KG) 30 30
B

A C
B2 7 16 1405 150 1185 150 48
B

TOTAL QUANTITY
BAR DIA 16 TOTAL

LGT (M) 178 178

1 FOOTING BAR CUTTING LIST WT (KG) 279 279

S 12 SCALE NTS

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY FOOTING BAR CUTTING LIST


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER 13 17
CEDRICK MAR A. KIMPALONG BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
STRUCTURAL DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR S-13 20
PRC. NO: 0140412 TIN. NO:326376510
PTR. NO:2854865 PRC VALIDITY: 04/23/2024
ELECTRICAL GENERAL NOTES LOAD COMPUTATION
LEGEND: CIRCUIT LOAD DESCRIPTION PROTECTION CONDUIT SIZE
SWITCH VOLTAGE WATTAGE AMPERES WIRE SIZE (mm) APPLYING 80% DEMAND FACTOR
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST NO LIGHTING CONVENIENCE OTHERS AT AF (mm)
EDITION OF THE PHILIPPINE ELECTRICAL CODE, EXISTING APPLICABLE ORDINANCES, RULES AND 2 x 40W T8 FLUORESCENT OUTLET OUTLET TOTAL AMPS= 12,200(0.80)/230
REGULATIONS OF THE LOCAL GOVERNMENT AND WITH THE REQUIREMENTS OF THE LOCAL POWER LIGHTING FIXTURE LCKT-01 7 2 230 700 3.043 15 Amp. 50 2.00 mm² 12.7 mmØ x 3m PVC PIPE TOTAL AMPS= 42.435
COMPANY. LCKT-02 5 3 230 600 2.608 15 Amp. 50 2.00 mm² 12.7 mmØ x 3m PVC PIPE SIZE OF SERVICE ENTRANCE WIRE
USE 8.00 mm² THHN COPPER WIRES
2. THE TYPE OF SERVICE POWER SUPPLY TO BE USED SHALL BE SINGLE-PHASE, 2-WIRE, 230V, 60 HERTZ, 150mm Ø CIRCULAR RECESSED PCKT-03 5 230 1,000 4.348 20 Amp. 50 3.50 mm² 19mmØ x 3m PVC PIPE USE 5.50 mm² GROUND WIRES
A.C. LED DOWNLIGHT (PINLIGHT) PCKT-04 1 220 700 3.182 20 Amp. 50 3.50 mm² 19mmØ x 3m PVC PIPE
3. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR
CONNECTION TO THE POWER COMPANY SERVICE POINT. PCKT-05 2 220 1200 5.455 20 Amp. 50 3.50 mm² 19mmØ x 3m PVC PIPE
2 GANG 15A SWITCH, 250 VOLTS,
4. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZES OF WIRE AND GALVANIZED RIGID STEEL CONDUIT PCKT-06 1 220 6,000 27.273 30 Amp. 50 8.00 mm² 19mmØ x 3m PVC PIPE
TO BE USED SHALL BE 3.5mm², THHN AND 15mm NOMINAL DIAMETER RESPECTIVELY. LIKEWISE ALL
Sab SINGLE POLE, SUBSCRIPT LETTER
INDICATES CONTROLLED LIGHTS SPARE 230 1,000 4.347 20 Amp. 50 3.50 mm² 19mmØ x 3m PVC PIPE
ELECTRICAL WIRES SHALL BE COLOR-CODED.
SPARE 230 1,000 4.347 20 Amp. 50 3.50 mm² 19mmØ x 3m PVC PIPE
5. ALL LIGHTING HOMERUNS AND CONVENIENCE OUTLETS SHALL BE WIRED NOT LESS THAN 3.5mm² IN SINGLE GANG 15A SWITCH, 250 VOLTS,
SIZE. SINGLE POLE, SUBSCRIPT LETTER 12,200 54.603
Se
6. WHEREVER REQUIRED AND NECESSARY, PULL OR JUNCTION BOXES SHALL BE INSTALLED AT INDICATES CONTROLLED LIGHTS
CONVENIENT AND INCONSPICUOUS LOCATION, ALTHOUGH SUCH BOXES ARE NOT SHOWN ON THE PLAN
NOR MENTIONED IN THE SPECIFICATIONS. DUPLEX CONVENIENCE OUTLET, 20 Amps, 7 LOADS SCHEDULE AND COMPUTATIONS
7. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE PROPERLY 250 VOLTS WALL MOUNTED
GROUNDED IN ACCORDANCE WITH THE PROVISIONS IN ARTICLE 2.50 "GROUNDING " PHILIPPINE
ELECTRICAL CODE, VOLUME 1, 2000 EDITION.
E 1 SCALE NTS

RANGE SINGLE RECEPTACLE OUTLET,


8. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR LOCATION AND 20 Amps, 250 VOLTS WALL MOUNTED
SERVICE ENTRANCE: 2 WIRES,
PURPOSE. R MAIN CIRCUIT
BREAKER 230 VOLTS,SINGLE PHASE, 60 Hz
9. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER APPURTINANCES USE 60 Amps.
FOR THE ENTIRE ELECTRICAL INSTALLATION SHALL BE USED. EMERGENCY LIGHT SINGLE RECEPTACLE
OUTLET, 20 Amps, 250 VOLTS WALL MOUNTED USE 8.00 mm² THHN COPPER
ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE THE FINISHED FLOOR EL ENTRANCE SRVICE WIRES
LEVEL UNLESS NOTED IN THE PLANS;
LCKT-01 15 AT 20 AT PCKT-05
R

a) WALL SWITCHES @ 1200mm


FLOOR OUTLET BOX
b) WALL CONVENIENCE OUTLETS @ 300mm ABOVE FINISHED FLOOR.
E

R
PCKT-04 PCKT-05
10. ALL ELECTRICAL EQUIPMENT AND MATERIALS SHALL CONFORM TO THE APPLICABLE REQUIREMENTS, MAIN CIRCUIT
V

E
UNDERWRITER'S LABORATORY (UL), NATIONAL FIRE FIRE PROTECTION (NTFA), NATIONAL ELECTRICAL LCKT-02 15 AT 30 AT PCKT-06 BREAKER PCKT-03 PCKT-06
PANEL BOX
I

V
MANUFACURER'S ASSOCIATION (NEMA) AND OTHER RELATED PUBLICATIONS.
R

I
11. WORKMANSHIP SHALL BE EQUAL TO THE BEST STANDARD PRACTICE RECOGNIZED AND ADOPTED FOR CIRCUIT RUN ON CEILING OR WALLS (PVC PIPE) LCKT-02 SPARE
THIS TRADE. R PCKT-03 20 AT 20AT SPARE
O

LIGHTING CIRCUIT HOME RUN, LETTERS AND USE 60 Amps.


1 ELECTRICAL GENERAL NOTES LCKT- 1 LCKT-01 SPARE
C

NUMBERS REPRESENT PANEL BOX DESIGNATION


N

AND CIRCUIT NUMBER RESPECTIVELY.


E 1 SCALE NTS
I

PCKT-04 20 AT 20 AT SPARE PANEL BOX


A

PCKT- 1 POWER CIRCUIT HOME RUN, LETTERS AND NUMBERS


H

C2
D

LICUTAN REPRESENT PANEL BOX DESIGNATION A


C

USE 5.5 mm² TW COPPER


DALKINSON TANGILIG ND CIRCUIT NUMBER RESPECTIVELY.
U

AWINGAN GROUND WIRE


MABACA USE 5.0 mm² TW COPPER
N

LOWER MANGALI
MALLANGO
UPPER 4 L E G E N D GROUND WIRE
A

ANGGACAN GUIMMA
BANGAD
E 1 SCALE NTS
T

MANGALI CENTRO ANGGACAN SUR 8 PANEL DIAGRAM 9 RISER DIAGRAM


BANGAD
CENTRO POBLACION
E 1 SCALE NTS
E 1 SCALE NTS

BABBANOY
AMBATO UPPER LUBO LOWER LUBO
A B C A B C
TINGLAYAN
PROPER TANUDAN
R

4000 4000
4000 4000
E
V

LUPLUPA
I

2300 2300 3400 1000


R

GA-ANG 2300 2300 3400 1000


O

SITE 1000
C

1000
I

ANGGACAN, TANUDAN, KALINGA


H

COORDINATE,17.33835,121.22709 DACALAN
C

2 LOCATION MAP 1 1 RG D
a b
E 1 SCALE NTS
LCKT-01
a

PCKT-05
3125
3125

ABBREVIATIONS:

PCKT-06
Sa a a b
A A, AMP AMPERE
AF AMPERE FRAME
2 2
AT AMPERE TRIP PB MPVS
b
C C CONDUIT Sb
CB CIRCUIT BREAKER

3125

PCKT-03

PCKT-04
c d
3125

CKT CURCUIT CRM


b
D Ø/DIA. DIAMETER Sc

H HZ HERTZ Sd,c
3 3 CBS

1000
P P POLE c c
1000

LCKT-02
PVC POLYVINYL CHLORIDE

T THWN MOISTURE & HEAT RESISTANT THERMOPLASTIC NYLON

V V VOLT

Ø PHASE, DIA.

3 A B B R E V I A T I O N S 5 LIGHTING LAYOUT PLAN 6 POWER LAYOUT PLAN


E 1 SCALE NTS
E 1 SCALE 1:80m
E 1 SCALE 1:80m

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:

REPUBLIC OF THE PHILIPPINES CONSTRUCTION OF ONE-STOREY SEPTIC TANK VOLUME


DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE COMPUTATION
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER DETAILS 1 18
DELFIN F. MADDARA BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
PROFESSIONAL ELECTRICAL ENGINEER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR E-1 20
PRC. NO: 3202 TIN. NO:140195328
PTR. NO:7248125 PRC VALIDITY:11/22/21
PLUMBING GENERAL NOTES:

1. ALL WORKS SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL


PLUMBING CODE AND LOCAL CODE REQUIREMENTS AND SUBDIVISION
REQUIREMENTS.
2. THE PLUMBING LAYOUT IS ONLY DIAGRAMATIC PIPES, CLEANOUTS, AND
4100
CHECK VALVES SHALL BE CONCEALED AS POSSIBLE.
3. ALL PLUMBING SHALLBNOT BE EMBEDDED ON STRUCUTRAL PARTS UNLESS
OTHERWISE SPECIFIED.
10.

4. MINIMUM SLOPE FOR SEWERAGE SHALL BE 2% AND DRAIN 1%. 1300 1500 1300
5. ALL CO'S SHALL BE FLUSHED MOUNTED TO WALL AND PROVIDE WITH 1
2" Ø PVC PIPE
POLISHED COVER CAPS. DO NOT INSTALL CLEAN OUTS EXCEPT AT LINE 4100
ON GRADE AND SERVICE NOT SUBJECTED TO TRAFFIC FLOWS.
6. ALL UNDERGROUND G.I. PIPES IN DIRECT CONTAT WITH THE SOIL SHALL BE
PROVIDED WITH TWO COATS OF PROTECTIVE TAR COVERED AND

3/4" Ø PVC PIPE


LAV 3000 1300 1500 1300
WRAPPED WITH JUTE CLOTHES THOROUGHLY SOAKED WITH TAR. LAV
WC
7. PROVIDE VENTILATION STACK THROUGH ROOF OF PVC AS RERQUIRED
CO
AND SHOWN IN TYHE PLANS.
4"Ø uPVC PIPE -SP
8. PROVIDE GATE VALVES TO ALLOW AND CONTROL WATER FROM WATER
LAV
SOURCE. LAV

2000
9. PROVIDE WATER PRESSURIZED TANK TO MEET THE WATER DEMAND FROM
11. ALL ELECTRICAL WORKS SHALL BE DONE
UNDER THE DIRECT AND IMMEDIATE
SUPERVISION OF A DULY REGISTERED
ELECTRICAL ENGINEER.

WC

2000
1ST TO 3RD FLOOR. FD
10. ALL PLUMBING WORKS SHALL BE UNDER THE DIRECT SUPERVISION OF A
R

R
F
DULY LICENCED SANITARY ENGINEER OR A MASTER PLUMBER. SEPTIC TANK
E

E
WATER SUPPLY
V

V
I

1 PLUMBING GENERAL NOTES


I
R

500
R

P 1 SCALE NTS
ANGGACAN, TANUDAN, KALINGA
O

COORDINATE,17.33835, 121.22709
N
C

UPPER DALNACAN
MABONGTOT
A
I

TALOCTOC

500
MANANGOL
H

LICUTAN
C2 SITE MATTELED
C

DALKINSON TANGILIG AWINGAN MABACA SE-ET


N

MALLANGO LOWER MANGALI


A

UPPER ANGGACAN GUIMMA


BANGAD
T

GUMBOWOY
MANGALI CENTRO ANGGACAN SUR

BANGAD BAKKUNG
4 WATER LINE LAYOUT PLAN 5 SEWERAGE LAYOUT PLAN
CABUGAO
CENTRO POBLACION
P 1 SCALE 1:25m
P 1 SCALE 1:50m

BABBANOY
AMBATO UPPER LUBO LOWER LUBO

TINGLAYAN
PROPER TANUDAN
LUPLUPA

GA-ANG

DACALAN

2 LOCATION MAP LA
V

P 1 SCALE NTS
CO

V
V LA
LA WC FD
BRANCH/SUPPLY SIZE
ABBREVIATION SYMBOLS DESCRIPTION
SP WP DP CWL
SP
CB CATCH BASIN E-
PIP
CO CLEAN OUT 100mmØ 50mmØ AV VC
L uP
3 1 F mØ
CWL COLD WATER LINE (PVC) 4"Ø, 2"Ø
WC 10
0m
DP DRAINAGE PIPE (uPVC) 100mmØ
IPE 2 "1Ø
DS DOWN SPOUT (uPVC) 75mmØ CP PV
C
PV PIP
FD FLOOR DRAIN 50mmØ 1 2"Ø E
3
GV GATE VALVE 4"Ø
3
KS KITCHEN SINK 4"Ø
4 "3Ø
1 PV
LAV LAVATORY 50mmØ 2"Ø C
3 1 PIP
PVC POLYVINYL CHLORIDE 4"Ø, 2"Ø E
SDP STORM DRAIN PIPE(uPVC) 100mmØ
SP SOIL PIPE (uPVC) 100mmØ
LY
PP
uPVC UNPLASTICIZED POLYVINYL CHLORIDE 100mmØ 50mmØ SU
TE
R NK
VP VENT PIPE 50mmØ WA TA
IC
WC WATER CLOSET 100mmØ 3
4"Ø
PT
SE
WP WASTE PIPE 50mmØ

3 A B B R E V I A T I O N S 6 WATER LINE PLUMBING ISOMETRY 7 PLUMBING-SEWERAGE ISOMETRY


P 1 SCALE NTS
P 1 SCALE 1:30m
P 1 SCALE 1:50m

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:
CONSTRUCTION OF ONE-STOREY SEPTIC TANK VOLUME
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE COMPUTATION
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER DETAILS 1 19
DIWAY KATE. M PASIKAN
BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
PLUMBING DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR P-2 20
PRC. NO: 0012881 TIN. NO:718-859-118-000
PTR. NO:2854571 PRC VALIDITY: 05/25/2022
QUANTITY FIXTURE DFU 18 DFU = 1000 GALLONS / 3785 LITERS=3. 785 cu.m. VOLUME
(min.) OF THE SEPTIC TANK CLEAN OUT REMOVABLE BRASS STRAINER
2 WATER CLOSET 12
V= W x L x H
SIZE OF SEPTIC TANK: DIGESTIVE CHAMBER: LEACHING CHAMBER 2: STRAINER BODY
2 LAVATORY 2 COUPLING
WIDTH= 1000 mm LENGTH= 1577 mm LENGTH= 788.5 mm
1 KITCHEN SINK 2 LENGTH= 3154 mm FINISHED FLOOR LINE
LEACHING CHAMBER 1:
HEIGHT= 1200 mm
LENGTH= 788.5 mm CONCRETE SLAB SLOPE SLOPE
1 FLOOR DRAIN 2

T O T A L 18 uPVC PIPE SEWERAGE LINE SLOPED AT 2°

PVC P-TRAP

1 SEPTIC TANK VOLUME COMPUTATION


P 2 SCALE NTS
SANITARY WYE 2°
100mm THK. REINFORCED SLAB W/ 10mm Ø REBARS
SPACED @ 150mm O.C.B.W., ADDITIONAL 2-12mm Ø
DIAGONAL BARS AT ALL CORNER OF MANHOLE
CLEANING EYE
CONCRETE MANHOLE COVER WITH 8-10mmØ
REBARS EQUALLY SPACED BOTHWAYS
PROVIDED WITH 12mmØ LIFT BAR CONNECTOR SUITE DRAIN AND P-TRAP

3 F L O O R C L E A N-O U T D E T A I L 4 FLOOR DRAIN DETAIL 5 SEWERAGE BRANCH DETAIL


3754

150 1577 150 788 150 788 150


P 2 SCALE 1:10m
P 2 SCALE 1:10m
P 2 SCALE 1:10m

510 533 139 510 139 510


ANGLE VALVE
150

CO CO CO CO ANGLE VALVE P-TRAP


395

MANHOLE MANHOLE MANHOLE


1300

1000

510

800

510
395

CO
150

130
PLAN FINISHED FLOOR LINE FINISHED FLOOR LINE
CONCRETE MANHOLE COVER WITH 8-10mmØ
REBARS EQUALLY SPACED BOTHWAYS
PROVIDED WITH 12mmØ LIFT BAR

150mm THK. PLASTERED 100mm CHB WALL W/ 6 TOILET FIXTURE MOUNTING DETAILS
10mmØ VERTICAL REBARS SPACED @ 600mm O.C.,
560 560 560 10mmØ HORIZONTAL REBARS SPACED @ EVERY 3 LAYERS OF CHB P 2 SCALE 10:m
PIPE CAP
510 510 510
4"Ø SANITARY TEE
AIR SPACE

400 12mmØ LIFT BAR


100

MANHOLE CO MANHOLE CO MANHOLE CO 200


3"Ø PVC PIPE DOWNSPOUT 1"Ø PVC PIPE NIPLE-AIR CHAMBER
3"Ø uPVC PIPE DOWNSPOUT

300
300

NATURAL GRADE LINE 75mm THK. CONC. SLAB W/ 10mmØ


50

4"Ø uPVC INLET 4" Ø PVC PIPE DRAINAGE LINE BARS AT 300mm O.C.B.W.
50

INCREASER

4"Ø uPVC OUTLET 4" Ø PVC PIPE DRAINAGE LINE

75
INLET
50

3
4"Ø PVC PIPE NIPPLE

100
1800

DIGESTIVE CHAMBER LEACHING LEACHING


1200

OUTLET

500
CHAMBER 1 CHAMBER 2
400

200

OUTLET OUTLET
12mmØ REBARS SPACED
OUTLET
@ 200mm O.C.B.W. 1
2"Ø PVC SUPPLY PIPE

75
1:10 slope 1:10 slope TEE
1:10 slope
200

MANHOLE

SECTION
7 CATCH BASIN DETAILS 8 AIR CHAMBER DETAIL
2 SEPTIC TANK DETAILS P 2 SCALE 1:10m
P 2 SCALE 1:10m

P 2 SCALE NTS

PEOPLES ORGANIZATION BENEFICIARY: SET SHEET


DESIGNED: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: PROJECT TITLE / LOCATION: SHEET AND CONTENTS:
NO: NO:
CONSTRUCTION OF ONE-STOREY SEPTIC TANK VOLUME
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF TRADE AND INDUSTRY WITH ROOFDECK RICE COMPUTATION
CORDILLERA ADMINISTRATIVE REGION PROCESSING CENTER DETAILS 2 20
DIWAY KATE. M PASIKAN
BOB JOHN A. BONGNGAT ANTONIO CALADING LINO D. CUNGIHAN MYRNA P. PABLO ANGGACAN, TANUDAN, KALINGA
PLUMBING DESIGNER
MANAGER, ROCKWELL BUILDERS
RIZAL PARK, SALVOSA DRIVE, BAGUIO CITY 2600
PO PRESIDENT/REPRESENTATIVE PROVINCIAL DIRECTOR, DTI KALINGA REGIONAL DIRECTOR, DTI CAR P-2 20
PRC. NO: 0012881 TIN. NO:718-859-118-000
PTR. NO:2854571 PRC VALIDITY: 05/25/2022