This document outlines filter efficiency requirements for central ventilation and air conditioning systems in skilled nursing facilities, intermediate care facilities, and correctional treatment centers. It specifies minimum filter efficiencies of 30% for the first filter bank and 80% for the second filter bank in areas for patient care, treatment, and diagnosis. Administrative, storage, soiled, laundry, and food preparation areas require a single filter bank with a minimum 30% efficiency. Filter efficiencies are based on ASHRAE standards and represented by minimum efficiency reporting value (MERV) ratings.
This document outlines filter efficiency requirements for central ventilation and air conditioning systems in skilled nursing facilities, intermediate care facilities, and correctional treatment centers. It specifies minimum filter efficiencies of 30% for the first filter bank and 80% for the second filter bank in areas for patient care, treatment, and diagnosis. Administrative, storage, soiled, laundry, and food preparation areas require a single filter bank with a minimum 30% efficiency. Filter efficiencies are based on ASHRAE standards and represented by minimum efficiency reporting value (MERV) ratings.
This document outlines filter efficiency requirements for central ventilation and air conditioning systems in skilled nursing facilities, intermediate care facilities, and correctional treatment centers. It specifies minimum filter efficiencies of 30% for the first filter bank and 80% for the second filter bank in areas for patient care, treatment, and diagnosis. Administrative, storage, soiled, laundry, and food preparation areas require a single filter bank with a minimum 30% efficiency. Filter efficiencies are based on ASHRAE standards and represented by minimum efficiency reporting value (MERV) ratings.
TABLE 4-7 -Filler Efficiencies for Central Ventilation and Air-Gonditioning Systems in Skilled Nursins
- Facilities and lntermediate Gare Facilities and Gorrectional Treatment Genters.t
Filter Efficiency % Filter Bank
(Minimum efficiency reporting
value MERV)s
Area Designation Minimum Number of Filter Banks No. 1 No.2''
All areas for inpatient care, treatment and/or 2 30% 80%
diagnosis, and those areas providing direct service or cleaning supplies (13) (8) Administrative, bulk storage, soiled holding, 1 3Oo/o' laundries and food DreD areas /8)
1 Based on ASHRAE Standard 52.'l-1992 or ASHRAE Standard 52.2-1999.
2 Filters are not required for evaporative coolers serving laundries and food preparation areas. 3 The numbers in parentheses represent MERV rating based on ASHRAE 52.2-1999.