Series R Helical-Rotary Liquid Chillers: Model RTWB 207-224
Series R Helical-Rotary Liquid Chillers: Model RTWB 207-224
Helical-Rotary
Liquid Chillers
Model RTWB 207-224
200-700 kW
RLC-PRC002-E4
Introduction
Introduction 2
Features and Benefits 4
Application Considerations 5
Selection Procedure 6
Model Number Description 8
Performance Data 9
General Data 11
Controls 13
Electrical Data and Connections 15
Job Site Connections 16
Dimensions and Weights 19
Mechanical Specifications 21
Options 23
RLC-PRC002-E4 3
Features and Benefits
4 RLC-PRC002-E4
Application Considerations
RLC-PRC002-E4 5
Selection Procedure - RTWB
Performance
The performance examples, on the following pages provide performance
information at various capacities for the most common water temperatures. The
stated cooling capacity is based on a water-temperature difference between the
evaporator inlet and outlet of 5°C and a difference of 5°C between the inlet and
the outlet of the condenser. The capacity ratings are applicable to a temperature
drop within 4 to 8°C except as limited by the minimum or maximum water-flow
rates as indicated by the heat exchanger’s hydraulic resistance table. All
capacities are based on a fouling factors of 0.044 m²K/kW for both evaporator
and condenser-watersides. If a different fouling factor is used, the unit capacity
will vary. For conditions that are not directly tabulated, direct interpolation may
be used. Extrapolation is not permitted.
For determining, the cooling capacity and the power input the following
information is needed:
• the required cooling capacity
• the inlet and outlet evaporator-water temperature
• the inlet and outlet condenser-water temperature
The evaporator-water flow can be determined by using the formula:
Evaporator water flow (liter/second) =
Cooling capacity x 0.239
Evaporator inlet (°C) - Evaporator outlet (°C)
The condenser-water flow can be determined by using the formula:
Condenser-water flow (liter/second) =
(Cooling capacity + Power input) x 0.239
Condenser outlet (°C) - Condenser inlet (°C)
The water pressure-drop tables are available on page 13.
Selection example:
Cooling capacity required: 560 kW
Evaporator temperature: 12/7°C
Condenser temperature: 30/35°C
Fouling factor: 0.044 m²K /kW
By using the selection table it can be determined that the RTWB 220 gives a
cooling capacity of 567 kW and a power input of 151 kW.
Determination of the evaporator flow rate:
27.1 liter/second = 567 x 0.239
12 - 7
Determination of the condenser flow rate:
34.3 liter/second = (567 + 151) x 0.239
35 - 30
After the evaporator and condenser flow rates have been determined, the
hydraulic pressure drop can be determined by using the water pressure-drop
table.
6 RLC-PRC002-E4
Selection Procedure - RTUB
Performance
The performance examples, on the following pages, provide performance
information at various capacities for the most common evaporator water and
saturated condensing temperatures. The stated cooling capacity is based on a
water temperature difference between the evaporator inlet temperature and
outlet of 5°C and a temperature difference of 9.6°C between the saturated
condensing and liquid temperatures (sub-cooling). The capacity ratings are
applicable to a temperature drop within 4 to 8°C except as limited by the
minimum or maximum water flow rate indicated in the heat exchanger
hydraulic resistance table. All capacities are based on a fouling factor of
0.0176 m² K/kW for evaporator water side. If a different sub-cooling or fouling
factor is used, the unit capacity will vary. For conditions that are not directly
tabulated, direct interpolation may be used. Extrapolation is not permitted.
To determine the cooling capacity and the power input, the following
information is needed :
• the required cooling capacity
• the inlet and outlet evaporator temperature
• the saturated condensing temperature
Selection example:
Cooling capacity required: 523 kW
Evaporator temperature: 12/7 °C
Condensing temperature: 45 °C
Fouling factor: 0.0176 m² K/kW
By using the selection table it can be determined that the RTUB 220 gives a
cooling capacity of 530 kW and a power input of 175 kW (with a sub-cooling of
9.6°C).
25.3 liter/second =
530 x 0.239
(12 - 7)
The water pressure drop can be determined by using the water pressure drop
table.
RLC-PRC002-E4 7
Model Number Description
Digit 1-2-3-4-5: Unit model type Digit 27: Condenser tubes Digit 71:Temperature sensors
ERTWB: Epinal RTWB X: Without X: Without
ERTUB: Epinal RTUB 5: GEWA C 1: With
Digit 6-7-8: Unit size S: Special Digit 74: Factory test
207-208-210-211-212-214-216-217-218-220- Digit 28: Condenser pass X: (RTUB)
222-224 X: Without (RTUB) A:A (RTWB)
Digit 11: Approval A: 1 pass B:B (RTWB/UB)
2: Pressure European Directive B: 2 pass right E:E (RTWB)
D: Australia C: 2 pass left S: Special
V: Poland S: Special Digit 75: Other special requirement(s)
Digit 12: Language Digit 31:Operating conditions X: No
C: Spanish A: One only S: Yes
D: German S: Special
E: English Digit 44: Under-over voltage protection
F: French X: Without
H: Dutch 1: With
I: Italian Digit 45: IP 20 protection
M: Swedish X: Without
U: Greek 1: With
V: Portuguese Digit 49: Communication cards
Digit 15: Main power voltage X: Without
C: 380/50/3 1: CSR module
D: 400/50/3 2: 1+ temperature sensor
E: 415/50/3 3: 2+ LWTC control
S: Special Digit 52: Compressor sound attenuating
Digit 17: Electrical codes enclosure
A: IEC X: Without
S: Special 1: With
Digit 18: Compressor starter Digit 53: Pressure gauges
H: Unit-mounted star-delta X: Without
S: Special 1: With
Digit 20: Main electrical disconnect device Digit 56: Compressor isolator valve
X: Without X: Without
B: Fused disconnect switch 1: Discharge (RTWB only)
S: Special Digit 57: Ammeter/voltmeter
Digit 23: Leaving chilled-water X: Without
temperature 1: With
A: -12°C≤T°C<-8°C Digit 61: Safety devices
B: -8°C≤T°C<-4°C X: Standard
C: -4°C≤T°C<+4°C 1: Germany
D: +4°C≤T°C<+10°C 3: Netherlands
E:+10°C≤T°C≤+15°C Digit 64: Packing
S: Special 1: Domestic
Digit 25: Condenser size 2: SEI Class 3
X: Without (RTUB) 3: SEI Class 4a
2: Standard (RTWB) 4: SEI Class 4c
Digit 26: Condenser leaving water S: Special
temperature (RTWB) Digit 65: Isolators
Saturated condenser temperature (RTUB) X: Without
A: 25°C≤T°C<30°C (RTWB) 1: Pads
B: 30°C≤T°C<35°C (RTWB/UB) S: Special
C: 35°C≤T°C<40°C (RTWB/UB) Digit 66: Flow switch
D:40°C≤T°C≤45°C (RTWB/UB) X: Without
E:45°C<T°C≤50°C (RTWB/UB) 1: Quantity 1
F: 50°C≤T°C≤55°C (RTWB/UB) 2: Quantity 2
G: 55°C≤T°C≤60°C (RTWB/UB) Digit 67: Counterflanges
H: 60°C<T°C≤65°C (RTUB) X: Without
S: Special 1: With
8 RLC-PRC002-E4
Performance Data
RLC-PRC002-E4 9
Performance Data
10 RLC-PRC002-E4
General Data
RLC-PRC002-E4 11
General Data
5 10 15 20 25 30 35 40 45
207 1 6 24
208 1 6 24
210 1 57 122
211 1 29 61 104
212 1 29 61 104
214 1 11 24 41 62
216 1 11 24 41 62
217 1 11 24 41 62
218 1 17 29 45 64
220 1 17 29 45 64
222 1 23 35 49 66 85 106
224 1 23 35 49 66 85 106
12 RLC-PRC002-E4
Controls
The RTWB and RTUB water-cooled can be solved. Whenever possible, adjustable), b) a 2-10 Vdc input or, c) a
Series R chillers employ the most the chiller is allowed to perform its 4-20 mA input.
advanced controls on the market function: making chilled-water. In External current limit setpoint
today. The two-line forty-character addition, microcomputer control Allows the external setting
Clear Language Display (CLD) has a provides safety protections such as independent of the front panel point
backlight for a simple readout. under/over voltage (option), phase by one of the following means: a) a
Adaptive Control™ microcomputer reversal, phase loss, phase remote resistor input (fixed or
The microcomputer-based controller imbalance, low voltage and overload adjustable), b) a 2-10 Vdc input or, c) a
optimizes controls around the chiller protection. These safety controls help 4-20 mA input.
application and the specific the chiller to remain in operation and
keep all of the building occupants Remote running and alarm indication
components used in the Series R contacts
chiller. For instance, the compressor comfortable.
The chiller provides three single-pole
protection system is specifically Monitoring and diagnostics double-throw contact closures to
designed for the Series R unit. A Because the microcomputer provides indicate that a failure has occurred if
leaving chilled-water temperature- all control functions, it can easily any compressors are running, or if
control algorithm maintains accurate indicate such parameters as leaving the compressors are running at
temperature control, minimizes the chilled-water temperature. All of the maximum capacity. These contact
drift from the setpoint and provides monitoring and diagnostic closures may be used to trigger job-
better building comfort. The information is displayed directly on a site-supplied alarm lights or bells.
microprocessor control incorporates clear language microcomputer
improved chiller start-up, load display. If a failure does occur, one of Ice-making control
limiting, lead/lag and compressor run- many Clear Language Display Provides an interface with ice-making
time equalization functions into messages will indicate the problem. controls systems.
standard chiller operation. The Chilled-water temperature reset
interface with building automation Standard features Reset can be based on return water
systems remains flexible and easy. External Auto/Stop temperature or outdoor air
Safety controls A job-site-provided contact closure temperature.
A centralized microcomputer provides will turn the chiller on and off. Note: The next version reviews the
a high level of machine protection. do not use the chilled-water pump to recommended interface with the
The safety controls are designed to stop the chiller. following control systems: Integrated
avoid compressor and/or evaporator External interlock Comfort systems interface, non-Trane
operation failures and to minimize A job-site-supplied contact opening building automation systems, stand-
nuisance shutdowns. The Unit Control wired to this input will turn the chiller alone chillers, and ice-making
Module (UCM) directly senses the off and will require a manual reset of systems.
control variables that govern the the chiller microcomputer. This Trane Integrated Comfort system
operation of the chiller: motor current closure is typically triggered by a job- (ICS) interface
draw, evaporator temperature, and site-supplied system such as a fire A single twisted pair of wires ties
condenser temperature. When any alarm. directly between the chiller and a
one of the variables approaches a
Chilled-water pump control Tracer™ system. A Tracer system
limit condition where the chiller may
Unit control provides output to provides elaborate control,
be shutdown to avoid damage, the
control the chilled-water pump(s). monitoring and diagnostic
UCM takes corrective action to avoid
One contact closure to the chiller is all capabilities. When the Series R
shutdown and keep the chiller
that is required to initiate the chilled- chillers are used in conjunction with a
operating. Corrective action is
water system. Trane Tracer system, the chiller can be
accomplished through combined
monitored and controlled from a
actions on the compressor unloader
valve and on the electronic expansion Optional features remote location. The Series R chiller
Communication interface can be controlled to fit into the overall
valve.
Capability for communication with building automation strategy by
Additionally, the UCM optimizes the using time-of-day scheduling, timed
the following control device:
total power consumption of the chiller override, demand limiting and chiller
during normal operating conditions. Trane Tracer building automation sequencing. A building owner can
During abnormal operating systems completely monitor the Series R
conditions, the UCM will continue to External chilled-water setpoint chiller from the Tracer system,
optimize the chiller performances by Allows the external setting because all of the monitoring
taking the necessary corrective action independent of the front panel point information indicated on the
to avoid shutdown. This keeps cooling by one of the following means: a) a microcomputer can be read on the
capacity available until the problem remote resistor input (fixed or Tracer system display. In addition, all
RLC-PRC002-E4 13
Controls
14 RLC-PRC002-E4
Electrical Data and Connections -
RTWB/RTUB
Electrical connection
Model Fuse size (1) Disconnect switch size (1) Minimum connecting wire (1) Maximum connecting wire (1)
RTWB/RTUB (A) (A) (mm²) (mm²)
207 80 315 150 240
208 100 315 150 240
210 125 315 150 240
211 60+125 400 185 240
212 160 400 185 240
214 2 x 160 400 185 240
216 160+200 630 2x150 2x300
217 2 x 200 630 2x150 2x300
218 250+200 630 2x150 2x300
220 2 x 250 630 2x150 2x300
222 2 x 315 800 2x185 2x300
224 2 x 315 800 2x185 2x300
(1) With disconnect switch option only.
RLC-PRC002-E4 15
Job Site Connections
16 RLC-PRC002-E4
Job Site Connections
RLC-PRC002-E4 17
Job Site Connections
RTWB/RTUB
Notes :
• All three-phase motors supplied with the unit are protected under primary
single-phase failure conditions.
• Caution - Do not energize the unit until check-out and start-up procedures
have been completed.
• All customer control-circuit wiring must have a minimum rating of 150V.
• All field wiring must be in accordance with the EN60204-1
101 Auxiliary controls for a customer-specified or installed tripout. The chiller will
run normally when the contact is closed and trip the chiller off on manually
resettable diagnostic when contact opens. Manual reset is accomplished at
the local Clear Language Display.
102 2 wires, 30 volt or less circuit. Do not run in conduit with higher voltage
circuits.
103 3 wires. 115 Vac circuit. Separate 115 Vac power is required. Load not to
exceed 1150 VA inrush.
104 2 wires. 115 Vac circuit, minimum contact rating at 115 Vac : 6.9 VA inrush,
1.3 VA sealed.
105 Shielded twisted pair, 30 volt or less circuit. Maximum length 1500 m. Do
not run in conduit with higher voltage circuits.
106 Customer supplied contacts must be compatible with circuit 12 Vdc, 45 mA
resistive load. Silver- or gold-plated contacts are recommended.
107 Auxiliary controls for a customer-specified or installed remote Auto/Stop
function. The chiller will run normally when the contact is closed and stop
the chiller when the contact is open. Re-closure of the contact will permit the
chiller to automatically return to normal operation. To be in series with water
pump relay. Note: Do not use the chilled-water pump to stop the chiller.
108 Normally-open contacts for remote shutdown or refrigerant circuit
operation. The refrigerant circuit will go through a normal shutdown when
the contacts are closed and will automatically resume normal start and run
modes when contacts are open.
109 Chiller module relay outputs can be programmed to perform alternate
functions.
18 RLC-PRC002-E4
Dimensions and Weights
Dimensions
The dimensional drawings illustrate the overall measurements of the unit. The
recommended service clearances indicate clearances required to easily service
the chiller. All catalog dimensional drawings are subject to change. Current
submittal drawings should be referred to for detailed dimensional information.
Contact the local Trane sales office for submittal information.
RLC-PRC002-E4 19
Dimensions and Weights
RTWB/RTUB 207-224
Evaporator 1 pass
Condenser
(RTWB) 1 pass
6 6
20 RLC-PRC002-E4
Mechanical Specifications
RLC-PRC002-E4 21
Mechanical Specifications
22 RLC-PRC002-E4
Options
RLC-PRC002-E4 23
The manufacturer has a policy of continuous
product improvement, and reserves the right
to alter any details of the products at any time
without notice.