Technical data
All data is supplied subject to change without notice. Specifications
are typical at 24 V, 25°C and 50% RH unless otherwise stated.

Operating voltage 17 V - 28 V dc
(max dc voltage range)
Digital communication XP95, Discovery and
CoreProtocol compatible
Modulation voltage 5 - 9 V peak to peak
Quiescent current 35 µA
Surge current 0 mA
Maximum current drawn 8.5 mA
Maximum line impedance 50 Ω

Product Overview Operating temperature - 30 ºC to +80 ºC


Humidity (no condensing or icing) 10% to 93% RH
Product Isolator
Standards and approvals CPR, LPCB, VdS
Part No. 55000-720
Dimensions 100 mm diameter x 3.5 cm
Product Isolator Base height
Materials White flame-retardant
Part No. 45681-211
polycarbonate
Digital Communication XP95, Discovery and Note:
CoreProtocol® compatible For further details on Short-circuit isolation, please refer to PP2090 -
Short-circuit isolation - available from www.apollo-fire.co.uk
Compliance
EMC Directive 2014/30/EU
The Isolator and Isolator Base comply with the essential
requirements of the EMC Directive 2014/30/EU, provided
that they are used as described in this datasheet.
Note: Part No. 45681-211 has LPCB approval only.
A copy of the Declaration of Conformity is available from the
Product Information Apollo website: www.apollo-fire.co.uk
Conformity of the Isolator and the Isolator Base with the EMC
Isolator Directive, does not confer compliance with the directive on
The Isolator is placed at intervals on the loop and ensures any apparatus or systems connected to them.
that, in the case of a short circuit, only the section between
Construction Products Regulation 305/2011/EU
the isolators will be affected. When the short circuit is
removed, the isolators automatically restore power and The Isolator complies with the essential requirements of the
data to the isolated section. The Isolator can only be used Construction Products Regulation 305/2011/EU.
with an Isolator base and will not fit a standard addressable A copy of the Declaration of Performance is available from
base. the Apollo website: www.apollo-fire.co.uk
• Detects wiring short-circuits using patented technology
• Minimizes disruption from short circuits
• Automatic de-isolation on short-circuit removal

• Up to 20 detectors (or equivalent) may be installed


between isolators

Isolator Base
The Isolator Base is only suitable for use with the Isolator.
All information in this document is given in good faith but Apollo
36 Brookside Road, Havant Tel: +44 (0)23 9249 2412 Email: sales@apollo-fire.com Fire Detectors Ltd cannot be held responsible for any omissions or
Hampshire, PO9 1JR, UK. Fax: +44 (0)23 9249 2754 Web: www.apollo-fire.co.uk errors. The company reserves the right to change the specifications
of products at any time and without prior notice.

MANAGEMENT
SYSTEMS
MANAGEMENT
SYSTEMS
PRODUCT
CERTIFICATION
© Apollo Fire Detectors Ltd 2018
Assessed to ISO 9001:2015 Assessed to ISO 14001:2015 Cert/LPCB ref. 010
Cert/LPCB ref. 010 Cert/LPCB ref. 010 EMS
PP2684/2018/Issue 1
Bases and Accessories Page 2 of 2

This page has intentionally been left blank

You might also like