Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

“PREMIER”

NON-PERCOLATING FLEXIBLE FIRE FIGHTING


DELIVERY HOSE

TECHNICAL DATA

Manufacturer NewAge Fire Fighting Co. Ltd.

Approval BIS Approved

1. IS 636 : 2018 For Fire Hose


Reference Standard
2. IS 903 : 1993 For Coupling

Type of Hose Type 1 (Uncoated)

Internal Diameter 63 mm

Length 15 meter

Mass Max. 450 g/m

Coil Diameter Max 45 cm (For 30 Meter


length hose without coupling)

Hydrostatic Proof Pressure 23 kgf/cm2

GENERAL DESCRIPTION Hydrostatic Burst Pressure Min. 38 kgf/cm2

Kink Test 23 kgf/cm2


NewAge make Premier Hose is a high quality layflat
hose for all fire-fighting operation. Circular woven
Pressure Loss Max. 0.50 Bar
Reinforcement is made of 100% High Tenacity Polyester
yarn with an inner lining made up of specially Each Hose shall be clearly
compounded EPDM Rubber compound. and permanently marked with
Ÿ Type of hose
ADVANTAGES Ÿ Size of the hose
Marking Ÿ Length of the hose
Ÿ Manufacturer’s Name or
Ÿ Light weight lay flat hose
Trade-mark or Both
Ÿ Very flexible
Ÿ Month and Year of
Ÿ Weather Proof
Manufacture
Ÿ Ageing & Ozone Resistant
Ÿ IS Mark
Ÿ Low Friction Loss
Ÿ Cold Resistance up to - 40 oC
Ÿ Heat Resistance up to + 100 oC End Connection
Ÿ Easy to operate & maintain
Instantaneous pair of male &
Type of Coupling
female parts
APPLICATIONS
Ÿ SS 304 (IS 3444 Gr. 1)
Material of Construction
Ÿ Construction Sites Ÿ Gunmetal (IS 318 LTB 2)
Ÿ Residential Buildings Ÿ Aluminum Alloy
Ÿ Commercial Buildings
Ÿ Agriculture Size 63 mm X 63 mm
Ÿ Municipal Corporations
Binding Wire SS Wire

Page 1 of 2 Rev.0 DS-FDH-001


Internal Maximum Hydostatic Minimum Maximum
Diameter Weight Proof Pressure Hydrostatic Pressure loss/23m
(mm) (g/m) (Kgf/cm²) Burst Pressure (bar)
(Kgf/cm²)

38 300 23 38 0.75

50 375 23 38 0.40

63 450 23 38 0.50

70 500 23 38 0.40

HOSE CARE & MAINTENANCE

Ÿ Hose Should be stored in cool, dry, clean and well ventilated storage area.

Ÿ Once the hose is used, it must be dried completely. It must also be checked for any cuts on the external surface.

Ÿ In case the hose has got in contact with oil or chemical, it must be washed thoroughly with detergent soap and them
dried completely before storing.

Ÿ Hose must be tested at a pressure of 50% in excess of the intended working pressure or at 10.5kg/cm2, whichever is
greater. The test must be conducted at least once in six months. Hose with small leaks should be repaired, wherever
possible. Hose with excessive leaks should be removedfrom service.

Ÿ While in use, avoid dragging hose over sharp objects or abrasive surfaces.

Ÿ Avoid hose kinks as much as possible.

Ÿ During operation, all necessary precautions must be taken to make sure that the hose does not get in direct contact
with hot surface or flame.

Ÿ While in operation, hose ramps should be used to avoid vehicles running over the hose.

Ÿ Hose should be coiled loosely enough to avoid any cracking on the edge of the hose.

NOTICE
* Inline with NEWAGE policy for continuous development, NEWAGE reserves the right to change specifications without prior notice
* All picture shown are for illustration purpose only. Actual product may very in appearance

Ambawadi Industrial Estate, Surendranagar - 363001 Gujarat, India


Phone: +91 2752 288000 I Fax: +91 11 6617 3355 I info@newage-india.in I www.newage-india.in

Page 2 of 2 Rev.0 DS-FDH-001

You might also like