Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 10

COOLING TOWERS

Equipment Code COT 01


Date of Commissioning Aug-06
Make Advance 2020
Type TM Series Multi cell counter flow FRP
CT
Model A 73
Capacity 300TR Each
Water entering temp 36.4deg C
Water outlet temp 32 Deg C
Water flow 272.52m3/hr
Air flow 106000m3/hr
Fan dia 2000mm
Fan type Axial flow
Material of the fan FRP
No of fan blades 3
Speed of the fan 560 rpm
Belt Size 70x3440mm endless nylon flat
Drift loss 0.00005%
Draft Motor KW 7.5KW
Voltage 415 V
Make Hindustan
Frame 132M
Current 14.5A
Efficiency 80
Duty S1
IP 55
Water quality for CT
Test Items Limits
PH 7.2-8.5
TH CaCo3 PPM <200
Total Alkality CACo3 PPM <100
Chloride Ion PPM <200
Total Iron Fe PPM <1
Silica Sio2 PPM <50
Ammonium Ion PPM <1
TDS PPM MAX 1500
Cooling tower sump capacity
Parameter Mts
Length 6.5
width 5.47
height 0.85
Volume in m3 30.22175

1 4.4 272
2 4.4 272
3 4 201
4 4 201
5 5 198
6 5 198
COOLING TOWERS
Equipment Code COT 02
Date of Commissioning Aug-06
Make Advance 2020
Type TM Series Multi cell counter flow FRP CT
Model A 73
Capacity 300TR Each
Water entering temp 36.4deg C
Water outlet temp 32 Deg C
Water flow 272.52m3/hr
Air flow 106000m3/hr
Fan dia 2000mm
Fan type Axial flow
Material of the fan FRP
No of fan blades 3
Speed of the fan 560 rpm
Belt Size 70x3440mm endless nylon flat
Drift loss 0.00005%
Draft Motor KW 7.5KW
Voltage 415 V
Make Hindustan
Frame 132M
Current 14.5A
Efficiency 80
Duty S1
IP 55
Water quality for CT
Test Items Limits
PH 7.2-8.5
TH CaCo3 PPM <200
Total Alkality CACo3 PPM <100
Chloride Ion PPM <200
Total Iron Fe PPM <1
Silica Sio2 PPM <50
Ammonium Ion PPM <1
TDS PPM MAX 1500
Cooling tower sump capacity
Parameter Mts
Length 6.5
width 5.47
height 0.85
Volume in m3 30.22175

394.944 315.9552
394.944 315.9552
265.32 212.256
265.32 212.256
326.7 261.36
326.7 261.36
1973.928 1579.1424
1539.66384
COOLING TOWERS
Equipment Code COT 03
Date of Commissioning
Make Advance 2020
Type
Model A 64
Capacity 300TR
Water entering temp 36deg C
Water outlet temp 32 Deg C
Water flow 201.60m3/hr
Air flow
Fan dia 1800mm
Fan type Axial flow
Material of the fan FRP
No of fan blades 3
Speed of the fan 560rpm
Belt Size
Drift loss
Draft Motor KW 7.5KW
Voltage 415 V
Make
Frame
Current
Efficiency
Duty
IP 55
Water quality for CT
Test Items
PH 7.2-8.5
TH CaCo3 PPM <200
Total Alkality CACo3 PPM <100
Chloride Ion PPM <200
Total Iron Fe PPM <1
Silica Sio2 PPM <50
Ammonium Ion PPM <1
TDS PPM MAX 1500
Cooling tower sump capacity
Parameter
Length
width
height
Volume in m3
COOLING TOWERS
Equipment Code COT 04
Date of Commissioning
Make Advance 2020
Type
Model A 64
Capacity 300TR
Water entering temp 36deg C
Water outlet temp 32 Deg C
Water flow 201.60m3/hr
Air flow
Fan dia 1800mm
Fan type Axial flow
Material of the fan FRP
No of fan blades 3
Speed of the fan 560rpm
Belt Size
Drift loss
Draft Motor KW 7.5KW
Voltage 415 V
Make
Frame
Current
Efficiency
Duty
IP 55
Water quality for CT
Test Items
PH 7.2-8.5
TH CaCo3 PPM <200
Total Alkality CACo3 PPM <100
Chloride Ion PPM <200
Total Iron Fe PPM <1
Silica Sio2 PPM <50
Ammonium Ion PPM <1
TDS PPM MAX 1500
Cooling tower sump capacity
Parameter
Length
width
height
Volume in m3
COOLING TOWERS
Equipment Code COT 05
Date of Commissioning
Make Advance 2020
Type
Model A 91
Capacity 325TR
Water entering temp 37*C
Water outlet temp 32*C
Water flow 198m3/hr
Air flow 157366 m3/hr
Fan dia 2400mm
Fan type Axial flow
Material of the fan FRP
No of fan blades 3
Speed of the fan 1440rpm
Belt Size
Drift loss
Draft Motor KW
Voltage
Make
Frame
Current
Efficiency
Duty
IP 55
Water quality for CT
Test Items
PH 7.2-8.5
TH CaCo3 PPM <200
Total Alkality CACo3 PPM <100
Chloride Ion PPM <200
Total Iron Fe PPM <1
Silica Sio2 PPM <50
Ammonium Ion PPM <1
TDS PPM MAX 1500
Cooling tower sump capacity
Parameter
Length
width
height
Volume in m3
COOLING TOWERS
Equipment Code COT 06
Date of Commissioning
Make Advance 2020
Type
Model A 91
Capacity 325TR
Water entering temp 37*C
Water outlet temp 32*C
Water flow 198m3/hr
Air flow 157366 m3/hr
Fan dia 2400mm
Fan type Axial flow
Material of the fan FRP
No of fan blades 3
Speed of the fan 1440rpm
Belt Size
Drift loss
Draft Motor KW
Voltage
Make
Frame
Current
Efficiency
Duty
IP 55
Water quality for CT
Test Items
PH 7.2-8.5
TH CaCo3 PPM <200
Total Alkality CACo3 PPM <100
Chloride Ion PPM <200
Total Iron Fe PPM <1
Silica Sio2 PPM <50
Ammonium Ion PPM <1
TDS PPM MAX 1500
Cooling tower sump capacity
Parameter
Length
width
height
Volume in m3
Cooling Tower Performance Summary
Design
Flow Capacity Air Flow Motor
CTN Range Approach L/G Ratio Range
(CMH) (TR) (CFM) (kW)
1 4.4 Not Available 272.0 394.9 7.5
124656 2.09 3.8
2 4.4 Not Available 272.0 394.9 7.5
3 4 3.3 201.0 265.3 7.5
100000 1.93 4.0
4 4 3.3 201.0 265.3 7.5
5 5 3.7 198.0 326.7 11.0
185062 1.03 5.3
6 5 3.7 198.0 326.7 11.0
nce Summary
Tested
Flow Air Flow Motor
Approach L/G Ratio Shaft Power
(CMH) (CFM) (kW)
Not Detectd 6.0 5.19
3.8 88740
Not Detectd 6.5 5.63
Not Detectd 7.7 6.46
3.5 72000
Not Detectd 6.8 5.83
170.5 9.3 7.96
2.2 121002 1.26
147.7 8.8 7.53