Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

AL-SECURE CU/XL-HFFR AS PER BS EN

50525-3-41
1x4

Nexans Ref.: 21004PHZOU000ADY

450/750 V STRANDED COPPER ,XL-HFFR INSULATED ,NON SHEATHED CABLES


CONFORMING TO BS EN 50525-3-41

DESCRIPTION
Application

These cables are intended for fixed wiring applications ,Used in energy networks in
refineries,mines,hotels,schools ,tunnels ,hgh constructions ,hospitals ,power plants
,data processing centres where there is a risk of fire with voltage upto and including
450/750 V

1. Conductor : Stranded bare copper class 2 to BS EN 60228.


2. Insulation: Cross linked Halogen free (XL-HFFR)
3. Colours: Available in Standard colours of G/Y ,Green ,Yellow,Brown ,White STANDARDS
,Black ,Blue or as required by customer .
International EN 50525-3-41

Packing

For Cable sizes less than 35 Sq.mm can be supplied in coils of 100 yards (91.44 mtrs)

For Cable sizes >= 50 Sq.mm shall be supplied in drums . Length as per the
requirement of customer .

Marking

450/750 V Cu / XL-HFFR 1 x 4mm2 H07Z-R 90 ˚C EN 50525-3-41 BASEC Made In


QATAR QICC - Nexans Year Meters

Certification :

BASEC (British approval services of cables)

Conductor flexibility Rated Voltage Uo/U (Um) Mechanical resistance to impacts Flame retardant Bending factor when laying Max.conductor temp.in service
Stranded class 2 450 / 750 V Good Yes 8 (xD) 90 °C

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/29/22 www.nexans.qa Page 1 / 2
AL-SECURE CU/XL-HFFR AS PER BS EN
50525-3-41
1x4

CHARACTERISTICS
Construction characteristics
Conductor flexibility Stranded class 2
Conductor material Bare copper
Insulation XL-HFFR
Dimensional characteristics
Approximate weight 48.42 kg/km
Conductor cross-section 4 mm²
Nominal outer diameter 4.12 mm
Number of cores 1
Electrical characteristics
Rated Voltage Uo/U (Um) 450 / 750 V
Max. DC resistance of the conductor at 20°C 4.61 Ohm/km
Rated current 40 A
Mechanical characteristics
Mechanical resistance to impacts Good
Usage characteristics
Flame retardant Yes
Bending factor when laying 8 (xD)
Max. conductor temperature in service 90 °C
Packaging Available in Coils/Drum
Short-circuit max. conductor temperature 250 °C

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/29/22 www.nexans.qa Page 2 / 2