22.

60
( DIVERSIFIED LOAD SUMMARY ) ( MAIN SWITCH BOARD )
5.53 17.06
SI TOTAL
A/C (KW) W/H(KW) COOKER(KW) GENERAL(KW) OTHER(KW) LOAD(KW)
NO
Ø100mm PVC DUCT Ø100mm PVC DUCT
1 SUB TOTAL(KW) 32.57 10.00 4.00 19.87 4.00 70.44 KW
600 mmBELOW G.Lvl 600 mmBELOW G.Lvl
2 DIVERSITY 90% 30% 40% 60% 50% -

3 DIVERSIFIED 29.31 48.33 KW


LOAD 3.00 1.60 11.92 2.50
- Cable routing is not acceptable
TOTAL CONNECTED LOAD = 70.44 KW
- Avoid Lift shaft and kitchen MAXIMUM DEMAND LOAD = 48.33 KW

3.35
OOREDOO GENERAL NOTES
S.P. 1 All Civil works to be executed by customer / contractor under Ooredoo supervision.
2 Civil materials to be purchased from Ooredoo with supervision

 3 MDF to be purchased from Ooredoo and installed by certified contractor
W6

MSB
DB-1
4 Block wiring to be executed by certified Ooredoo contractor.
UP D3 1 5 Cable works to be laid by Ooredoo free of charge up to main telecom room and
ARCH
UP ELEC. on rechargeable basis for sub telecom rooms.
UP  CABINET D3
KITCHEN
2 6 Cable trays width should be between 30 cm to 60 cm.
7 For Internal Connections (block wiring). Refer to (Ooredoo web site)
+0.30 3 - Internal cabling guidelines.
- Telecom Equipment room guidelines.
F.F.L
4 8 All telecom jobs to be executed as per Ooredoo standards & regulations.
BOUNDARY

TV
WOMEN MAJLIS 9 Telecom Room size ......... m x.........m.
FIRE & WATER 
W3
PROOF ENCLOSURE W6 W3 5 10 Ooredoo approval provided for external telecom. network only.

WALL

REF 11 All internal infrastructure inside the building is under consultants /


 6 contractors responsibilities.
 STORE 12 Consultant to contact GSM departments for their requirements.
 7 13 Conctractor should contact Ooredoo plant protecting officer PPo. On
Tel 44400500/44600700 prior to excavation.


32 mm Ø PVC RISER 8
LIFT
 400X400X100 MTJB

D2 D2 Design and Construction of building shall comply with the provisions of the following
D2
 INTERCOM PANEL
 1) Regulation for the installation of electrical wiring, electrical equipment and air

ARCH
conditioning equipment December 2010 edition.
D4 UP 
UP
D1A ENTRY All possible energy saving measures adopted in lighting sector.
D2 Energy saving lamps is proposed wherever applicable.

19.08
19.20

TV
D2 Control Systems are provided for lighting and A/C as pplicable.
Timer and/or photocell control is ensured for the external lighting.

TV D2
Neccessary provisions are included in design/construction to reduce the cooling load and
W6 corresponding electrical demands by property selecting building materials, insulation to
walls and roof and energy efficient windows as applicable.
15.85

DINING SITTING All air conditioning equipments are sized and selected as per cooling load calculations.
S.P. +0.45 Energy efficiency and conservaion measures area considered while selecting HVAC

TV
F.F.L MEN MAJLIS
Note for ami provisioning:
All required provisioning for AMI shall be implemented as per
amendment to the regulation titled
ADVANCED METERING INFRASTRUCTURE CODE 2016

D1 KAHRAMAA INSTALLATION DEPARTMENT NOTES:


THERMAL INSULATION SPECIFICATION ARE AS PER 2 "MINISTERIAL
Manhole should be provided to avoid elevator shaft W1 W1
Contractor to avoid the overlapping
UP between Electrical and Mechanical
± 0.00
MAIN ENTRY Services
Ø100mm PVC DUCT
600 mmBELOW G.Lvl

50mm DIA PVC DUCT


600 mmBELOW G.Lvl
INTERCOM PANEL
RS +1
+1
7.3 CLIENT:
8 7.1
CAR ENTRANCE BOUNDARY 9 BOUNDARY ELECTRICAL
WALL ENTRANCE WALL
+ 17.19 SERVICE CABINET

1.00 5.00 3.70 1.60 11.49

22.79
FROM OOREDOO
CABLE General Directorate Of Endowments

- - - - ROAD - - - - FROM QGEWC CONSULTANT:

SITE PLAN ELECTRICAL LAYOUT James Cubitt & Partners


Engineering Consultancy
SCALE 1/100 TEL: 44665216 - FAX: 44665250 - P.O.BOX 24436 - DOHA - QATAR

MAIN CONTRACTOR

CABLE REFERENCE
VILLA
GR. FLOOR
VILLA
F. FLOOR
VILLA
P/HOUSE 40A, TPN ISO. KIT. BLOCK
RIVERA TRADING & CONT.CO.
DB-1 DB-2 DB-3 FOR LIFT DB-K Tel.:4684453 / 4684454 Fax.: 4684453
1 - 4C-16 sqmm PVC + 1C-16 sqmm PVC/ECC
19.20 KW 16.35 KW 21.43 KW 4.00 KW 9.46 KW C.R. No.: 9429 - C. Cont.: 746
2 - 4C-16 sqmm PVC/PVC + 1C-16 sqmm PVC/ECC
SPARE P.O. Box 4258 Doha, Qatar
3 - 4C-16 sqmm PVC/PVC + 1C-16 sqmm PVC/ECC

4 - 4C-16 Sq mm PVC/PVC + 1C-16 Sq mm PVC/ECC.


5 - 4C-16 sqmm PVC/SWA/PVC + 1C-16 sqmm PVC/ECC
1 2 3 4 5 MEP CONTRACTOR
1(RYB)

3(RYB)

4(RYB)

5(RYB)

6(RYB)
2(RYB)

600
40A 40A 40A 40A 40A 40A
TP TP TP TP TP TP
SERVICE CABINET MCCB MCCB MCCB MCCB MCCB MCCB
AT B/WALL
COPPER BUSBAR 100A
150 AMPS 4 POLE+E TP 6 WAY'S 150A TP MAIN SWITCH
kW/HR METER BOARD (MCCB PANEL)
MCCB

TOTAL CONNECTED LOAD = 70.44 KW


2200(MAX)
830

MAXIMUM DEMAND LOAD = 48.33 KW


PROJECT
QGEWC CUTOUT
VILLA ( G+ 1 + P.H ) + KITCHEN BLOCK
4C-70 Sq mm XLPE/SWA/PVC+
1C-35 Sq mm PVC/ECC.
LOCATION:
MADINET KHALIFA NORTH
800

GR. FFL
DATE:
30 / 04 / 2022
GR. LVL.

TITLE: SHOP DRAWING SITE PLAN


ELECTRICAL LAYOUT
600(NTS) 600 DRAWING NO.: SCALE:
150mm PVC DUCT EL-RIV-271-SD-016 1:100 @ A2
WITH SLOW BEND

FROM QGEWC REV: DRAWN BY:


ELEC. SUPPLY 150mm PVC DUCT WITH SLOW BEND 0 SC
SCHEMATIC DIAGRAM OF MAIN SWITCH BOARD (M.S.B) CAD FILE :