A) This is for information:-

<>This is the 1st resubmission submitted by SPCL for review purpose received to TCE.
<>But it is observed that some of TCE comments are not yet incorporated in this resubmission and drawing is not up to the mark.
<>However for the timeline interest of the project, TCE herewith approving this drawing with comments.
<>SPCL to submit the correct record purpose drawings after incorporating all our comments.
C10

C7 KEY PLAN:
KMP HIGHWAY

60m wide road


GATE GATE GATE GATE GATE GATE GATE

Sheeting
LAGOON

GATE
GATE
CANAL
WATER
TANK

Dim.,?? C9

GATE
60m wide road
C11

45m wide road


FINISHED CAR PARKING AREA

Dim.,??

GATE
LAGOON

C6 (Typical) Dim? GATE GATE GATE GATE GATE


60m wide road
GATE
LAGOON

GATE GATE

DN

C5 (Typical)

C8

Rohit Digitally signed


by Rohit Bhagat

Bhagat 20:35:09 +05'30'


Date: 2023.01.31

TCE.12648C-3010-SPCL-PRS-159

FOR REFERENCE

Dim?? FOR ESTIMATION

C) MISSING DETAILS NOT YET RECEIVED IN DRAWING- FOR APPROVAL


> Refer mail dated 14-01-2023, sent to SPCL about missing details in drawings. B) COMMENTS NOT
> ANCHOR BOLT design and detail drawings from Grid 14 to 2a. INCORPORATED IN THE
> Grid 13 to 2a Connection design calculations & details of same in drawing are not yet DRAWING:- CONTRACT
submitted. C5-Specify roof monitor out to
> Missing Levels & Dimensions. (Like clear height/dimension & Top of structure). out width.
> Purlin Layout & all Girt elevations (Side wall and gable end framing) with sag rod layout not C6-2m wide canopy (Typical). FOR TENDER
C7-Show center to sheeting out. Rohit Digitally signed

shown in drawings.
by Rohit Bhagat

Bhagat
Date: 2023.01.31

(Typical)
19:26:02 +05'30'

> Staircase design calculations & details of same in drawing are not yet submitted. FOR CONSTRUCTION
> Deck slab, Deck sheet design calculations & details of same in drawing are not yet submitted. C8-Show Skylight & Air washer,
> Roof plan showing gutter and downtake location. exact location shall be as per
> Sheeting drawings showing Sheeting lines, levels, height, Sheet lapping, flashing, trim, soffit, Latest architectural drawing and
add arrangement detail for AS-BUILT
framed openings, connection bolts and screw details, etc shall be submitted.
review.
C9-Show Toilet Block, location
shall be as per Architectural
MSIL NEW FACTORY PROJECT
drawing R0.
C10-Show sheeting out to out SONIPAT (PACKAGE-01)
dimension (Typical).
C11-Check Gutter slope and
<>Refer mail Dated -18-12-2022 for changes in arrow direction. (Typical)
roof monitor. MARUTI SUZUKI INDIA LTD.

<>Extend the roof monitor as shown, 3500 mm


from the end of the roof monitor to the sheeting CONSULTING ENGINEERS LIMITED
out. (Typical) PUNE

ROOF PLAN

DEL-1664-001-C-SL-005

N
W
DN

E
2m wide Canopy

LEGEND:-
dim.,?? dim.,?? SHAPOORJI PALLONJI & CO. PVT. LTD.
7TH FLOOR, KANCHANJUNGA BUILDING,
Update detail as per Architectural BARAKHAMBA ROAD, CON NAUGHT PLACE,
drawing (R0). NEW DELHl-110001

MSIL-KH-SPCL-PRESS (A+B)-ROOF-PLAN-159