Professional Documents
Culture Documents
Failure Codes SRX16
Failure Codes SRX16
Failure Codes SRX16
Fault Fault
Fault Name Control Fault Name Control
Code Code
T1 SEAT SW OPEN T T76,P76 MC COIL SHORT T/P
T2,P2 ANALOG INPUT T/P T77 MAINTENANCE HOUR T
T3,P3 COIL SHORT HW KO T/P T78,P78 VACC NOT OK T/P
T4,P4 SAFETY OUTPUT, FAN OUTPUT T/P T79,P79 INCORRECT START T/P
T5,P5 VACC OUT RANGE T/P T80 FORW + BACK T
T7,P7 SLIP_PROFILE T/P T81,P81 SENS MOT TEMP KO T/P
T8,P8 WATCHDOG#1 T/P
T82,P82 ENCODER ERROR T/P
T9,P9 WATCHDOG# T/P
P83 OVERLOAD P
T10 WAITING DISPLAY T
P84 LOAD SENS. ERROR P
T11,P11 AUX DRIV.SHRT. T/P
T85,P85 WAITING FOR NODE T/P
T12,P12 SAFETY INPUT T/P
T86 SEQUENCE FAULT T
T13,P13 EEPROM KO T/P
P90 ACQUIRE LIFT P
T14,P14 TH. PROTECTION T/P
T15,P15 AUX COIL SHORT T/P P91 ACQUIRE TILT P
T16,P16 AUX DRIV.OPEN T/P P92 ACQUIRE S/S P
T17,P17 LOGIC FAILURE #3 T/P P93 ACQUIRE AUX1 P
T18,P18 LOGIC FAILURE #2 T/P P94 MHYRIO IN ALARM P
T19,P19 LOGIC FAILURE #1 T/P P95 LIFT OUT OF RNG. P
T30,P30 VMN LOW T/P P96 TILT OUT OF RNG. P
T31,P31 VMN HIGH T/P P97 AUX OUT OF RNG. P
T33,P33 IDLE TIME T/P P98 S/S OUT OF RNG. P
T37,P37 CONTACTOR CLOSED T/P P99 ACQUIRE REACH P
T38,P38 CONTACTOR OPEN T/P P100 REACH OUT OF RNG P
T39,P39 KEY OFF SHORT T/P T101
CAN BUS KO DISP. T/P
T40,P40 HARDWARE FAULT T/P P101
T43,P43 FLASH CHECKSUM T/P P113 STEERING HAZARD P
T44,P44 WRONG RAM MEMORY T/P P114 HEIGHT ZERO POS. P
T45,P45 SOFTWARE ERROR T/P P115 HEIGHT ENC. LOCK P
T46,P46 CURRENT GAIN T/P P116 LIFT/LOWER LIMIT P
T47,P47 WRONG 0 VOLTAGE T/P P117 REACH IN LIMIT P
T48,P48 PROG VACC NOT OK T/P
T241
T53,P53 STBY I HIGH T/P DATA ACQUISITION T/P
P241
T60,P60 CAPACITOR CHARGE T/P T243
T65,P65 MOTOR TC START T/P NO CAN MSG. T/P
P243
T66,P66 BATTERY LOW T/P T245
WRONG SET BAT. T/P
T71,P71 MOTOR SHUTDOWN T/P P245
T72,P72 MOTOR STALL T/P T249
THERMIC SENS. KO T/P
T74,P74 DRIVER SHORTED T/P P249
T75,P75 CONTACTOR DRIVER T/P
2. EPS(Steering) Controller
Fault Fault
Fault Name Control Fault Name Control
Code Code
E20 EPS NOT ALIGNED EPS E149 WAITING FOR TRAC EPS
E21 MICRO SLAVE #3 EPS E150 DIR. NOT CONIFIG EPS
E22 POSITION ERROR EPS E162 SL CENTERING EPS
E23 SERIAL ERROR #1 EPS E163 MOTOR TEMPERAT EPS
E24 MICRO SLAVE #4 EPS E164 MOTOR LOCKED EPS
E25 SLAVE COM. ERROR EPS E165 STEPPER MOT. MISM EPS
E26 NO SYNC EPS E166 CLOCK PAL NOT OK EPS
E27 CURRENT GAIN EPS E167 MICRO SLAVE #8 EPS
E28 FB SENS LOCKED EPS E168 INPUT ERROR #1 EPS
E29 STEER SENSOR KO EPS E169 CAN BUS KO SL EPS
E120 HIGH CURRENT EPS E170 SL EPS NOT ALL EPS
E121 POWER FAILURE #1 EPS
E122 POWER FAILURE #2 EPS
E123 POWER FAILURE #3 EPS
E124 STBY I HIGH EPS 3. Valve Controller (MHYRIO-CB)
E125 D LINE SENSOR KO EPS
Fault
E126 Q LINE SENSOR KO EPS Fault Name Control
Code
E127 EEPROM KO EPS
M8 WATCHDOG MhyrioCB
E128 VMN NOT OK EPS
M13 EEPROM KO MhyrioCB
E129 HIGH TEMPERATURE EPS
M19 HI SIDEDRIVER KO MhyrioCB
E130 DATA ACQUISITION EPS
M20 EVPG1 DRIVER KO MhyrioCB
E131 LOGIC FAILURE #1 EPS
M21 EVPG2 DRIVER KO MhyrioCB
E132 LOGIC FAILURE #2 EPS
M22 EVPG3 DRIVER KO MhyrioCB
E133 LOGIC FAILURE #3 EPS
M23 EVPG4 DRIVER KO MhyrioCB
E134 LOGIC FAILURE #4 EPS
M24 EVP DRIVER KO MhyrioCB
E135 KS CLOSED EPS
M30 EV DRIVER KO MhyrioCB
E136 KM CLOSED EPS
M31 EVPG1 DRIV SHORT MhyrioCB
E137 KS OPEN EPS
E138 KM OPEN EPS M32 EVPG2 DRIV SHORT MhyrioCB
E139 MICRO SLAVE EPS M33 EVPG3 DRIV SHORT MhyrioCB
E140 JERKING FB EPS M34 EVPG4 DRIV SHORT MhyrioCB
E141 F.B OUT OF RANGE EPS M35 EVP DRIVER SHORT MhyrioCB
E142 MICRO SLAVE KO EPS M36 WAITING FOR PEV MhyrioCB
E143 ENCODER ERROR EPS M39 UNDER VOLTAGE MhyrioCB
E144 BAD ENCODER SIGN EPS M40 FF VALVES MhyrioCB
E145 GAIN EEPROM KO EPS M74 EV DRIVER SHORT MhyrioCB
E146 STEER HAZARD EPS M76 COIL SHORTED MhyrioCB
E147 WAITING DATA EPS M243 CAN BUS KO MhyrioCB
E148 CAN BUS KO EPS M245 WRONG SET BAT. MhyrioCB
Troubleshooting :
T1 SEAT SW OPEN - Controller detects the seat switch is open during operation.
- Check the seat switch wiring and connection.
- Check for inoperative seat switch.
Cause : This alarm occurs when the A/D conversion of the analog inputs gives
frozen value, on all of the converted signals, for more than 400msec. The goal
T2 of this diagnosis is to detect a failure of the A/D converter or a problem in the
ANALOG INPUT code flow that omits the refreshing of the analog signal conversion.
P2
Troubleshooting : If the problem occurs permanently it is necessary to substi-
tute ACE logic board.
Cause : The hardware circuits which manages short circuits protection of LC
T3 and EB/AUX coils has a problem.
COIL SHORT HW KO
P3 Troubleshooting : This type of fault is not related to external components :
replace the ACE logic board.
Cause : The safety out driver is shorted.
T5 Troubleshooting :
VACC OUT RANGE - This fault indicates that the accelerator voltage is 1 volt lower than the maxi-
P5
mum value programmed by PROGRAM VACC function.
- The potentiometer is not correctly calibrated.
- The potentiometer is defective.
Cause : There is an error on the choice of the parameters of the slip profile.
T7
SLIP_PROFILE Troubleshooting :
P7
Check in the hardware setting menu the value of those parameter.
Cause : At start-up the watch dog signal is already active before the software
has generated it. At stby or running condition the watch dog signal is not
T8 active. (in alarm status)
WATCHDOG#1
P8 Troubleshooting : The WD hardware circuit or microcontroller output port
are damaged. In both cases no external component are involved.
Replace the logic board.
T30 Troubleshooting :
VMN LOW If the problem occurs at start up (the LC does not close at all), check.
P30
- Motor internal connections. (ohmic continuity)
- Motor power cables connections.
- Motor leakage to truck frame.
- If the motor connections are OK, the problem is inside the controller, replace it.
If the alarm occurs during motor running, check.
- Motor connections.
- If motor phases windings/cables have leakages towards truck frame.
- That the LC power contact closer properly, with a good contact.
- If no problem are found on the motors, the problem is inside the controller,
replace it.
Cause :
1. Before switching the LC on, the software checks the power bridge: it turns
on alternatingly the Low side Power Mosfets and expects the phases voltage
to decrease down to -BATT. If the phases voltage is higher than 10% of
nominal battery voltage, this alarm occurs.
2. This alarm may occur also when the start up diagnosis is overcome, and so
the LC is closed. In this condition, the phases’ voltages are expected to be
lower than 1/2 Vbatt. If it is higher than that value, fault status is entered.
Troubleshooting :
T31
VMN HIGH If the problem occurs at start up (the LC does not close at all), check.
P31
- Motor internal connections. (ohmic continuity)
- Motor power cables connections.
- If the motor connection are OK, the problem is inside the controller, replace it.
If the problem occurs after closing the LC (the LC closed and then opens back
again), check.
- Motor connections.
- If motor phases windings/cables have leakages towards truck frame.
- If no problem are found on the motors, the problem is inside the controller,
replace it.
Troubleshooting :
- Key input signal down-going pulses (below under voltage threshold) due to
external loads, like DC/DC converters starting-up, relays or contactor
T39
KEY OFF SHORT switching, solenoids energizing / de-energizing.
P39 - Check the connection of power cables to the battery terminal, positive and
negative, to MC and to controller +Batt and –Batt, which must be screwed
with a torque comprised in the range 13Nm÷15Nm.
- If no voltage transient is detected on the supply line and the alarm is present
every time the key is switched ON, the failure is probably in the controller
hardware, so it is necessary to replace the logic board.
Cause :
1) Hardware problem in the logic card circuit for MC driver management.
2) Hardware problem in the logic card circuit for power section management.
T40
HARDWARE FAULT Troubleshooting :
P40 1) This type of fault is not related to external components, so, when it is pres-
ent it is necessary to replace the ACE logic board.
2) This type of fault is not related to external components, so, when it is pres-
ent it is necessary to replace the ACE logic board.
Troubleshooting :
T47
WRONG 0 VOLTAGE It is suggested to check.
P47 - Motor internal connections. (ohmic continuity)
- Motor power cables connections.
- Motor leakage to truck frame.
- If the motor connections are OK, the problem is inside the controller, replace
the logic board.
T48
PROG VACC NOT OK Not used.
P48
Cause : The current transducer or the current feedback circuit is damaged in
T53 the controller.
STBY I HIGH
P53 Troubleshooting : This type of fault is not related to external components so,
when it is present, it is necessary to replace the controller.
Cause : When the key is switched ON, the inverter tries to charge the power
T60 capacitors through a series of a PTC and a power resistance, and check if the
CAPACITOR CHARGE capacitor are charged within a timeout. If the capacitor voltage measured is
P60 less than 20% of the nominal battery voltage, an alarm is signalled; the main
contactor is not closed.
Troubleshooting :
- There is an external load in parallel to capacitor bank, which sinks current
from the controller capacitors pre-charging circuit, thus preventing the caps
from charging. Check if a lamp or a dc/dc converter or an auxiliary load is
placed in parallel to capacitor bank.
- The charging resistance or PTC is opened; insert a power resistance across
line contactor power terminals; if the alarm disappears, it means the control-
ler internal charging resistance is damaged.
- The charging circuit has a failure, inside the controller.
- There is a problem in the controller power section.
Cause : When motor temperature is over than " MOTOR TC START " parameter.
T65
MOTOR TC START
P65 Troubleshooting : To reduce the heat of the motor surface if motor surface is
not heated, must be checked motor thermic sensor.
T66 Cause : When voltage battery is under minimun voltage.
BATTERY LOW
P66 Troubleshooting : Need to charging the battery.
Cause : The traction stopped because of a too high temperature on the motor.
T71
MOTOR SHUTDOWN
P71 Troubleshooting : To reduce the heat of the motor surface if motor surface is
not heated, must be checked motor thermic sensor.
Cause : The controller is trying to move the motor but the motor seems stuck.
There could be also a problem with the encoder.
T72 Troubleshooting :
MOTOR STALL
P72 - Check both electrical and mechanical encoder functionality.
- Check all connections between the controller and the encoder.
- If the problem still present try to replace the encoder.
T74 Troubleshooting :
DRIVER SHORTED - Check if there is a short or a low impedance pull-down between NMC
P74
(CNA#16) and –BATT.
- The driver circuit is damaged in the logic board, which has to be replaced.
Cause : The MC coil driver is not able to drive the load.
The device itself or its driving circuit is damaged.
T75
CONTACTOR DRIVER Troubleshooting :
P75
This type of fault is not related to external components:
replace the ACE2 logic board.
Cause :
This alarm occurs when there is a short circuit of the MC coils connected to
CNA#16 output. After the overload condition has been removed, the alarm
exits automatically by releasing and then enabling a travel demand.
T76 Troubleshooting :
MC COIL SHORT
P76 - The typical root cause for this error code to be displayed is in the harness or
in the load coil. So the very first check to carry out concerns connections
between controller outputs and loads.
- In case no failures/problems have been found externally, the problem is in the
controller, which has to be replaced.
Cause : The truck reached the maintenance working hours.
T77 MAINTENANCE HOUR Troubleshooting : Need to change maintenance reset value form off to on and
key off and on. It will be change on to off automatically after key on.
Cause : The test is made at key-on and immediately after that both the travel
demands have been turned off. This alarm occurs if the ACCELERATOR
reading in the TESTER menu’ is 1,0V higher than PROGRAM VACC min
T78 acquisition when the accelerator is released.
VACC NOT OK
P78 Troubleshooting : Acquire the maximum and minimum potentiometer value
through the PROGRAM VACC function. If the alarm is still present, check the
mechanical calibration and the functionality of the potentiometer. If the alarm
is not disappeared the failure is in the ACE logic board, replace it.
Cause : Wrong traction and pump request sequence.
This fault indicates an incorrect starting sequence.
Troubleshooting :
- If SRO FUNCTION is active, every time work is stopped the operator must
T79 put the truck in neutral.
INCORRECT START (SRO) - If forward, reverse or seat switch is active when key switch is turned on.
P79
- If Acce. pedal, deadman switch or HYD lever is active when key switch is
turned on.
- If Acce. pedal, deadman switch is active before FWD, RVS switch is pressed.
- If forward, reverse closed without seat switch input..
- If the fault persist after checking the wiring.
Troubleshooting :
T80 FORW + BACK - Processor is continuously checking for a request for forward and reverse at
same time.
- Check forward and reverse switch.
T81 Cause : The output of the motor thermal sensor is out of range.
SENS MOT TEMP KO
P81 Troubleshooting : Check the sensor ohmic value and the sensor wiring.
Cause : This fault is signalled in following conditions: the frequency supplied
to the motor is higher than 40 Hz and the signal feedback from the encoder has
a jump higher than 40 Hz in few tens mSec. This condition is related to a mal-
functioning of the encoder.
Troubleshooting :
T82 - Check both the electric and the mechanical encoder functionality, the wires
ENCODER ERROR crimping.
P82
- Check the encoder mechanical installation, if the encoder slips inside its com-
partment raising this alarm condition.
- Also the electromagnetic noise on the sensor bearing can be a cause for the
alarm. In these cases try to replace the encoder.
- If the problem is still present after replacing the encoder, the failure is in the
controller.
Cause : Truck overloaded.
P83 OVERLOAD Troubleshooting :
The controller detects the load is overloaded, check the load & Sensor.
Cause : Load sensor out of range.
P84 LOAD SENS. ERROR
Troubleshooting : Check the load sensor and try to teach the sensor again.
T85 Cause : Truck waiting pump or vice versa.
WAITING FOR NODE
P85 Troubleshooting : Check the load sensor and try to teach the sensor again.
T86 SEQUENCE FAULT Not used.
Cause : MAX/MIN LIFT parameters are not correct.
P90 ACQUIRE LIFT Troubleshooting : Calibrate lift analog sensor.
If after calibration alarm persist, checkt the lift analog sensor.
Cause : MAX/MIN TILT parameters are not correct.
P91 ACQUIRE TILT Troubleshooting : Calibrate tilt analog sensor.
If after calibration alarm persist, checkt the tilt analog sensor.
Cause : MAX/MIN S/S parameters are not correct.
P92 ACQUIRE S/S Troubleshooting : Calibrate S/S analog sensor.
If after calibration alarm persist, checkt the S/S analog sensor.
Cause : MAX/MIN AUX parameters are not correct.
P93 ACQUIRE AUX Troubleshooting : Calibrate AUX analog sensor.
If after calibration alarm persist, checkt the AUX analog sensor.
/)%'0& +",*!"-%1!"#2-3.4""*5,6%7%&'898&0
Group 19, Motor Controls
Troubleshooting :
Check the potentiometer connected to CNB#6 is right working.
If toggle switches are connected to CNA#2 and CNA#3, verify they are right
working and the setting AUX FUNCTION 11 is correct.
Verify also the sensor bearing in the motor (encoder) has not a slip (the sensor
bearing has two rings: one is connected to the rotor shaft; the other is
connected to the motor frame. Check these two rings are strictly connected to
their structure without slip.
Cause : Main uC and Slave uC communicate via a local serial interface.
This alarm occurs when the slave uC does not receive thecommunication from
E23 SERIAL ERROR #1 the main uC through this serial interface.
E135 KS CLOSED Troubleshooting : This alarm occurs if the connection CNA#4 (NK1) is
around a voltage of 12 Vdc when switching on the key. In fact, when the safety
contacts are open, NK1 is expected being connected to a minus battery voltage
(not 12 V). Search for a harness problem or replace the controller.
Cause : This alarm occurs at key on if the slave uC detects the safety contact,
of the main uC, closed prior to be commanded.
E136 KM CLOSED Troubleshooting : This alarm occurs if the connection CNA#5 (K1) is around
a voltage of 12 Vdc when switching on the key. In fact, when the safety
contacts are open, K1 is expected being connected to a battery voltage (not 12
V). Search for a harness problem or replace the controller.
Cause : This alarm occurs if the main uC detects the safety contact, of the
E137 KS OPEN slave uC, open when expected being closed.
Troubleshooting :
E168 INPUT ERROR #1 When the safety contacts are open, the voltage on CNA#4 is expected to be
close to 0 Vdc and this is independent from whether the safety contacts are
connected to a plus battery or to a minus battery (see 7.6).
In the first case (safety contacts connected to a plus battery), when the safety
contacts are open, CNA#4 is connected to a minus battery through a load.
Only a harness mistake may connect NK1 to a higher than 12 V voltage.
Cause : Alarm can bus slave.
E169 CAN BUS KO SL
Troubleshooting : Internal CAN BUS fault.
Cause : Slave not aligned.
E170 SL EPS NOT ALL
Troubleshooting : Internal fault.