Professional Documents
Culture Documents
Transmission Line Distance Protection Under Current Transformer Saturation
Transmission Line Distance Protection Under Current Transformer Saturation
Transmission Line Distance Protection Under Current Transformer Saturation
1, January 2021
Abstract—
—Conventional transmission line distance protection categories: dependability loss and security loss. A dependabili‐
approaches are subject to malfunction under reverse fault-in‐ ty loss corresponds to a saturation-induced decrease in the cur‐
duced current transformer (CT) saturation for the typically em‐ rent amplitude and a phase shift, which reduces the actuation
ployed breaker-and-a-half configuration. This paper addresses
this issue by proposing a new distance protection approach that range and increases the actuation time of distance protection.
combines the blocking and unblocking criteria of distance pro‐ A security loss corresponds to a distance protection malfunc‐
tection based on the values of incomplete differential current, tion that arises from a saturation-induced reverse current. Gen‐
operation voltage, and current harmonic content. The proposed erally, in the case of a single CT connected to protection, dis‐
approach is verified by theoretical analysis, dynamic simulation tance protection will lose dependability with reduced possibili‐
testing, and field operation to ensure that the obtained distance
ty of malfunction owing to a decrease in the secondary cur‐
protection is reliable and refrains from operating unnecessarily
under reverse fault-induced CT saturation in the breaker-and-a- rent after CT saturation. Similar conclusions have been drawn
half configuration. Meanwhile, the proposed approach is demon‐ in the literature [4], [5].
strated can operate reliably when forward faults occur or vari‐ However, according to the IEEE Std C37.110 [6], in a ring
ous reverse faults are converted to forward faults. or breaker-and-a-half configuration, the current used for line
Index Terms— —Breaker-and-a-half configuration, current protection is the sum of the currents of two CTs. When the
transformer (CT) saturation, distance protection, power fre‐ bus fails, a large ride-through current may flow through the
quency variation, operation voltage. CT. If the CT is saturated, the total current may present a
large reverse current, and the distance protection will be at the
risk of malfunction.
I. INTRODUCTION The problems associated with distance protection under CT
reverse fault-induced CT saturation events is high. According‐ where İ m′ 1 and İ m′ 2 are the secondary currents from CT1 and
ly, it is essential to analyze the causes of malfunctions in dis‐ CT2, respectively; and k̇ 1 = Aeϕ. A and ϕ are the changes in the
tance protection during CT saturation for developing reliable amplitude and angular difference generated during transmis‐
preventative approaches. sion, respectively. The definition of k̇ 2 is similar. A virtual CT
Herein, the mechanism of distance protection malfunction that outputs the secondary total current can be constructed,
during reverse fault-induced CT saturation is analyzed for the and according to (2) and (3), the transmission characteristic of
breaker-and-a-half configuration as an example. Accordingly, CT can be expressed as:
a new distance protection approach is proposed that combines
İ ′ İ ′ + İ ′ k̇ 1 İ m1 + k̇ 2 İ m2
the blocking and unblocking criteria of distance protection k̇ = sum = m1 m2 = (4)
based on the criteria of incomplete differential current, opera‐ İ l İ m1 + İ m2 İ m1 + İ m2
tion voltage, and current harmonic content. The proposed ap‐ where İ l is the primary current flowing through the line; and
proach is validated by theoretical analysis, dynamic simula‐ İ s′um is the total current flowing to the protection device. For
tion testing, and field operation to ensure that the obtained dis‐ simplicity, the CT1 and CT2 ratios are assumed to be 1. There‐
tance protection is reliable and can be implemented appropri‐ fore, k̇ 1 = k̇ 2 = 1 during a normal CT transmission.
ately during reverse fault-induced CT saturation in the ring or The equivalent system obtained when a fault occurs at
breaker-and-a-half configuration. Meanwhile, the proposed ap‐
point F of line L2 in Fig. 1 is shown in Fig. 2, where Ė S is the
proach is demonstrated can operate reliably when forward
sending-end electromotive force; Ė R is the receiving-end elec‐
faults occur or various reverse faults are converted to forward
tromotive force; İ F is the fault current flowing from point F to
faults owing to the subsidence of CT saturation.
point K; Z K is the equivalent impedance from point M to point
K; and Z R is the equivalent impedance of the protection for‐
II. ANALYSIS OF DISTANCE PROTECTION MALFUNCTION
ward direction.
The mho characteristic is one of the most typically used
. M . N .
characteristics in distance protection [3]. In this study, we per‐ ES P Im ER
F
form an analysis based on an example of mho distance protec‐ Z set
tion [19] of positive-sequence voltage polarization. Based on .
IF
the phase-comparison principle, the operation equation is ex‐ ZK ZR
.
pressed as: K
Um
90° < arg(U̇ OP /U̇ P )< 270° (1) Fig. 2. Equivalent system with reverse fault at point F in Fig. 1.
where U̇ OP = U̇ m - İ m Z set is the operation voltage, and Z set is the
setting value of distance protection, U̇ m and İ m are the respec‐ The parameters in Fig. 2 are used to express the operation
tive voltage and current obtained by the protection device, re‐ voltage U̇ OP and polarization voltage U̇ P as:
spectively; and U̇ P = U̇ m1 is the polarization voltage, and U̇ m1 U̇ OP = U̇ m - İ l′ Z set = İ l Z m - k̇ İ l Z set = İ l (Z m - k̇ Z set ) (5)
is the positive-sequence voltage component at the protection
device. U̇ P = U̇ m1 = Ė R + İ l1 Z R = -İ l (Z R - Z m ) + İ l1 Z R =
According to an example of a substation system shown in İ l [Z m - Z R (1- İ l1 /İ l )]= İ l (Z m - k ′ Z R ) (6)
Fig. 1, the current İ ml on the protected line L1 is the sum of the where Z m is the resistance between the protection device and
primary currents İ m1 from CT1 and İ m2 from CT2. the short-circuit point; İ l1 is the positive-sequence component
. * M of İ l; and k ′ = 1- İ l1 /İ l, which is related to the fault type and
I m1 CT1 system parameter. For example, with a single-phase earth
. N
BRK1 I ml
BRK 4 fault, k ′ = 0.75- 0.87; with a phase-phase fault, k ′ = 0.5; and
L1
with a three-phase fault, k ′ = 0.
BRK 2 Substituting (5) and (6) into (1) yields
*
. CT2 Z m - k̇ Z set
I m2
L2 BRK5 90° < arg < 270° (7)
Z m - k′ Z R
F
BRK 3
P The operation characteristic corresponding to (7) is a circle
with end points of k̇ Z set and k ′ Z R as the diameter. During the
normal transmission of CT1 and CT2, k̇ = 1. This condition is
* Circuit breaker (closed)
Fig. 1. An example of a substation system with breaker-and-a-half configu‐ illustrated in Fig. 3(a), where the action circle is removed
ration. from the origin toward quadrant I. The reverse fault measure‐
ment impedance -Z k generally falls in quadrant III, and hence
According to the characteristics of CT transmission, İ m1 and the relay exhibits good directionality. By contrast, when CT1
̇I m2 can be expressed as [3]: is under normal transmission and CT2 is under severe satura‐
tion, k̇ 1 = 1, whereas the amplitude of k̇ 2 is reduced and be‐
İ m′ 1 = k̇ 1 İ m1 (2)
comes zero [6]. This condition is illustrated in Fig. 3(b),
İ m′ 2 = k̇ 2 İ m2 (3) where k̇ = İ m′ 1 /İ l owing to the opposite directions of İ m′ 1 and İ l,
70 JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, VOL. 9, NO. 1, January 2021
and the action circle corresponding to (7) shifts to quadrant and (b), which represent a fault at the near-end point Fa along
III. Therefore, distance protection may malfunction when a the forward direction of the line and a fault at point Fb on the
short-circuit fault occurs at the far-end point or the opposite reverse bus, respectively. Figure 5(a) shows that, when the
bus. fault occurs at point Fa, variations Dİ m1 and Dİ m2 of the current
jX
flowing through CT1 and CT2 are reversed, i. e., they are in
k′ZR the same direction. Figure 5(b) shows that when the fault oc‐
jX . curs at point Fb, Dİ m1 is forward and Dİ m2 is reverse, i. e., the
kZset
two are in opposite directions. These two short-circuit states
are analyzed in much greater detail in the following section.
However, the fault at point Fb shown in Fig. 5(b) is similar to
the fault illustrated in Fig. 1 and that analyzed previously.
. R
kZset −Z k M
. *
k′ZR ∆ I m1
N
BRK1 Fa
R L1 BRK 4
−Z k
.
(a) (b) BRK 2 ∆Uf
. *
Fig. 3. Mho action circle with positive-sequence voltage polarization. (a)
∆ I m2
Transmission of both CT1 and CT2 is normal. (b) CT2 is saturated. L2 BRK5
BRK 3
The system illustrated in Fig. 1 presents a special operation P
condition, denoted as operation condition 1, when BRK4 is * Circuit breaker (closed)
disconnected with a reverse fault at point F so that the same (a)
current flows through CT1 and CT2, and İ l is zero. The condi‐ Fb
tion where CT2 is severely saturated is illustrated in Fig. 4, M
where the total current İ s′um from the CT output presents a con‐ .
∆ I m1
* .
∆Uf
sistent positive-direction characteristic with respect to İ m′ 1. Sub‐ N
BRK1
sequently, k̇ is in quadrant III, and the amplitude approaches L1 BRK 4
infinity. Herein, the action circle corresponding to (7) extends BRK 2
infinitely to quadrant III, and the possibility of a reverse-fault- *
.
induced malfunction arises. ∆ I m2
L2 BRK5
20
′ (A)
10 BRK 3
0
Isum
P
-10
20 * Circuit breaker (closed)
Im′ 1 (A)
10 (b)
0
-10 Fig. 5. Schematic diagrams for illustrating additional short-circuit states of
10 substation system with breaker-and-a-half configuration shown in Fig. 1. (a)
Im′ 2 (A)
{DI cd £ k res DI zd
DI zd > I setzd
(8)
tection device, respectively. This can be defined in cases of
forward and reverse faults as follows.
For the forward fault,
BRK 2
(a)
. *
∆ I m2 ZF Z set
L2 BRK5 .
M Δ Im N R
F
BRK 3 .
ΔUop
.
Circuit breaker (closed) . ΔUm
* Circuit breaker (open) ΔUf
verse faults, which are expressed as (17) and (18), respectively. During the forward fault, | DU̇ op | is significantly greater than
| DU̇ | > U
m setdif
m
(17)
| DU̇ m |; hence, the value of k cannot impair the judgment of
the unblocking criterion. Under this operation condition, the
incomplete differential blocking criterion operates correctly
{| DU̇ | < k | DU̇ | and exhibits greater sensitivity than the operation voltage
op m
(18) blocking criterion.
| DU̇ | > U
m setdif Under operation condition 2, the incomplete differential cri‐
terion is invalid during a fault at the remote end of the line.
where U setdif is the voltage threshold value; and k is the re‐
However, the operation voltage unblocking criterion operates
straint coefficient, which is generally set as 1.1, and ensures
correctly and exhibits greater sensitivity than the incomplete
that the blocking criterion is reliable. Similar to (8), the thresh‐
differential unblocking criterion.
old value U setdif is also set to reduce the effect of disturbance
The above analysis demonstrates the necessity of utilizing
in the system on the criterion. The values of DU̇ m and Dİ m are both the incomplete differential and operation voltage criteria
obtained using the short data window algorithm [20], [21]. to address special conditions where a single set of criteria is
Under normal operation conditions, the criteria can identify not applicable.
the fault direction during CT saturation [3] and then imple‐
ment distance protection for a forward fault while blocking C. Logic Coordination Between Incomplete Differential and
distance protection for a reverse fault. Details regarding the Operation Voltage Criteria
application of the operation voltage criteria under the two op‐ The action conditions of the incomplete differential and
eration conditions are provided as follows. operation voltage criteria at various fault points under differ‐
Under operation condition 1, the total current obtained by ent system conditions are shown in Table I, where P1, P2,
the protection is zero during a reverse bus fault. At this time, and P3 denote the fault points at the near-end line, far-end
| DU̇ op | = | DU̇ m |, and the blocking criterion of (18) is invalid. line, and opposite bus, respectively.
TABLE I
ACTION CONDITION OF INCOMPLETE DIFFERENTIAL AND OPERATION VOLTAGE CRITERIA
The following conclusions can be obtained from Table I. the incomplete differential unblocking and operation voltage
1) Under operation condition 1, the operation voltage block‐ unblocking. Hence, the criteria provide a strict account of the
ing criterion is always activated regardless of the fault type, fault direction under all operation conditions. The criteria are
whereas the operation voltage unblocking criterion is never ac‐ activated according to the characteristics of the linear trans‐
tivated, and the incomplete differential action criteria are acti‐ mission area of the CT prior to its saturation. Consequently, a
vated normally. logical interlock between the blocking and unblocking criteria
2) Under operation condition 2, the incomplete differential is used to avoid the effect of current distortion on criteria deci‐
blocking criterion is activated in the fault at P3, whereas the sions after CT saturation, as shown in Fig. 8, and the continu‐
incomplete differential unblocking criterion is not activated, ity of the criteria can be maintained during CT saturation.
and the operation voltage criteria are activated normally.
3) Under general operation conditions, both the incomplete D. Criteria for Current Harmonic Content Unblocking
differential and operation voltage criteria are activated normally. When a reverse fault is converted to a forward fault, the dis‐
Accordingly, valid distance protection blocking actions are tance protection blocking criteria act first and maintain the ac‐
assured by applying an “and” logic to the criteria of the in‐ tion, resulting in a failure to unblock distance protection after
complete differential blocking and the operation voltage conversion to the forward fault. This problem is addressed in
blocking, whereas valid distance protection unblocking ac‐ the present study by establishing unblocking criteria based on
tions are assured by applying an “or” logic to the criteria of the current harmonic content.
ZHENG et al.: TRANSMISSION LINE DISTANCE PROTECTION UNDER CURRENT TRANSFORMER SATURATION 73
Incomplete differential F4
unblocking criteria ≥1 M
& Distance protection *
Operation voltage unblocking criteria N
unblocking criteria F1 F2 F3
BRK1 BRK 4
L1
. .
Incomplete differential ES ER
& & BRK 2
blocking criteria Distance protection
*
blocking criteria F5
Operation voltage
L2 BRK5
blocking criteria
Fig. 8. Logic diagram for applying distance protection blocking and un‐ BRK 3
blocking criteria.
* Circuit breaker (closed)
The high second harmonic content of the output current is Fig. 9. RTDS simulation model.
the key feature of CT saturation [19], [22], [23]. Accordingly,
CT saturation can be assumed to be relieved when the second TABLE II
harmonic content of the output current is less than a threshold SYSTEM IMPEDANCE AND LINE PARAMETERS OF RTDS SIMULATION MODEL
value, enabling distance protection to be unblocked. The pro‐
posed current harmonic content unblocking criteria are ex‐ Parameter Value
pressed as: Positive-sequence resistance (Ω/km) 0.028
ìI mh2 < k H I m Positive-sequence inductive reactance (Ω/km) 0.275
ï Positive-sequence capacitive reactance in parallel (Ω·km) 0.225
íI m1h2 < k H I m1 (19)
ï Zero-sequence resistance (Ω/km) 0.094
I < k
î m2h2 H m2 I
Zero-sequence inductive reactance (Ω/km) 0.674
where I mh2, I m1h2, and I m2h2 are the secondary harmonic con‐ Positive-sequence capacitive reactance in parallel (Ω·km) 0.313
tents of the total current, side circuit breaker current, and mid‐ Line length (km) 100
dle circuit breaker current, respectively; I m, I m1, and I m2 are the System equivalent impedance at bus M (Ω) 10∠85°
total current, side circuit breaker current, and middle circuit System equivalent impedance at bus N (Ω) 20∠85°
breaker current, respectively; and k H is the harmonic content
ratio coefficient, which is set as 0.15 based on the literature
[22]-[24] and a large number of simulation tests. Two protection devices, denoted as A and B, are employed
During a reverse fault, distance protection is blocked, and in the simulations at the M side of line L1. Device A is devel‐
the output current is monitored according to the criteria in oped based on the proposed method, and device B is devel‐
(19) simultaneously. If CT saturation is relieved and the re‐ oped using the conventional distance protection strategy. De‐
verse fault is converted to a forward fault, the harmonic con‐ vice A measures the respective output currents of CT1 and
tents will be less than the threshold values, and distance pro‐ CT2, whereas device B measures the total current. Both devic‐
tection will be unblocked. During forward-fault-induced CT es comprise two-stage distance protections based on the mho
saturation, the action characteristics of distance protection are relay, which is defined in (1). The value of Z set of distance relay
affected by distortions in the current, and the protection trip zone I is 22.11 Ω, whereas it is set to be 33.16 Ω for the distance
time will be extended or the protection range will be reduced relay zone II, and the time delay is set to be 0.5 s.
[4]. Meanwhile, the action characteristics cannot be restored B. Simulation Result
until CT saturation has subsided to a certain extent or com‐ Dynamic simulations are conducted to verify the perfor‐
pletely relieved. Therefore, the full-cycle Fourier algorithm is mance of the protection devices with forward and reverse me‐
used to implement a criterion that has a short time delay, and the tallic faults and different operation modes. The simulation re‐
criterion can be unblocked in time with limited effect on the ac‐ sults are listed in Table III. The results indicate that both de‐
tion characteristics of the distance protection. vices A and B provide consistent operation characteristics of
distance protection under general operation conditions as well
IV. SIMULATION ANALYSIS as forward and reverse faults. Hence, the proposed approach
does not affect the original operation characteristics of dis‐
A. Simulation System Parameter tance protection.
Figure 9 presents the dual-circuit simulation model built in The fault recording results of device A in a fault at F1 are
the Real Time Digital Simulator (RTDS) and employed for shown in Fig. 10(a) to illustrate the criterion features obtained
analysis. It is a typical model operating at 500 kV, where the during a forward fault. After the fault occurs, the criteria of
same tower adopts the breaker-and-a-half configuration at one the incomplete differential unblocking and operation voltage
side and the dual-bus configuration at the other side. Internal unblocking are satisfied rapidly, and distance protection is un‐
fault points F1-F3 and external fault points F4 and F5 are estab‐ blocked. Similarly, the fault recording results of device A in a
lished in the model to simulate various fault types. The system fault at F5 are shown in Fig. 10(b) to illustrate the criterion
impedance and line parameters are listed in Table II. features obtained during a reverse fault. After the fault occurs,
74 JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, VOL. 9, NO. 1, January 2021
the criteria of the incomplete differential blocking and opera‐ The dynamic simulation results obtained in transfer faults
tion voltage blocking are satisfied rapidly, and distance protec‐ are listed in Table IV. The results indicate that both devices A
tion is blocked. and B provide consistent operation characteristics of distance
protection. Furthermore, the results verify the feasibility of
TABLE III the current harmonic content unblocking criteria, which exhib‐
PERFORMANCE OF PROTECTION DEVICE UNDER DIFFERENT OPERATION
it action features similar to those of the conventional method.
MODES AND FAULTS
TABLE IV
Mode Fault point Device A Device B ACTION OF PROTECTION DEVICE IN TRANSFER FAULT
Distance relay Distance relay
Both strong F1
zone I (12 ms) zone I (12 ms) Convert
Fault Device A Device B
Distance relay Distance relay time (ms)
Both strong F2
zone I (21 ms) zone I (21 ms) F1 A-phase, F4 Distance relay zone I Distance relay zone I
10
Both strong F4 No action No action B-phase (12 ms), A-phase trip (12 ms), A-phase trip
Distance relay Distance relay F1 A-phase, F4 Distance relay zone I Distance relay zone I
ES strong, ER weak F1 10
zone I (10 ms) zone I (10 ms) A-phase (12 ms), A-phase trip (12 ms), A-phase trip
Distance relay Distance relay F4 A-phase, F1 Distance relay zone I Distance relay zone I
ES strong, ER weak F3 10
zone II (521 ms) zone II (521 ms) B-phase (22 ms), B-phase trip (22 ms), B-phase trip
ES strong, ER weak F5 No action No action F4 A-phase, F1 Distance relay zone I Distance relay zone I
10
A-phase (22 ms), A-phase trip (22 ms), A-phase trip
60 . F4 A-phase,
Im′ 1 Distance relay zone I Distance relay zone I
. CT1 saturation, 10
Im′ 2 (25 ms), A-phase trip (22 ms), A-phase trip
Current (A)
40 F1 A-phase
.
′
Isum
20
0 Dynamic simulations are conducted for reverse single-
-20 . phase metallic ground faults and a fault through transition re‐
300
∆Uop
. sistance at F4 under different saturation degrees of CT1 and
∆Um CT2. The respective actions of protection devices A and B are
Voltage (V)
200 Threshold
listed in Table V. The results indicate that device A can reli‐
100 ably block distance protection under the reverse fault-induced
CT saturation when the saturation time is greater than or
0
60
equal to 2 ms. By contrast, device B is subject to malfunction.
∆ Icd
Moreover, the blocking criteria of device A still have a greater
Current (A)
∆ Izd
40
Threshold sensitivity compared with the single blocking criterion of de‐
20 vice B in the case of involving a fault through transition resis‐
tance. Additionally, the criteria provide a smaller fault current
0 5 10 15 20 25 30 35 40 45 as well as reliable distance protection blocking.
t (ms)
(a) TABLE V
. PROTECTION ACTION OF REVERSE FAULT AT F4
15 Im′ 1
.
10 Im′ 2 Saturated Saturation
Current (A)
∆Um
40 CT2 2.0 No action No action
Threshold
CT2 5.0 No action No action
20
CT1 1.5 Action Action
0 CT1 2.0 No action Action
15 ∆ Icd Through transition resistance CT1 2.5 No action Action
Current (A)
0 5 10 15 20 25 30 35 40 45
The fault recording results of device A in a fault at F4 when
t (ms) CT1 is saturated are shown in Fig. 11. Therefore, the criteria
(b) of the incomplete differential blocking and operation voltage
Fig. 10. Criterion features during forward and reverse faults. (a) Forward blocking are satisfied rapidly in the CT linear transmission re‐
fault. (b) Reverse fault. gion after the fault, and the distance protection is blocked.
ZHENG et al.: TRANSMISSION LINE DISTANCE PROTECTION UNDER CURRENT TRANSFORMER SATURATION 75
.
′
Isum
5
0
Over 10000 protection devices based on the proposed ap‐
-5 proach have been used in power grids of various voltage lev‐
-10 els in China, and all of the field protection devices are operat‐
.
100 ∆Uop ing as intended.
.
Voltage (V)
80
∆Um
60
40
Threshold V. CONCLUSION
20 This paper addresses the tendency of conventional transmis‐
0 sion line distance protection approaches to malfunction under
8
∆ Icd reverse fault-induced CT saturation by proposing a new dis‐
Current (A)
Advances in Intelligent Systems and Computing, Singapore: Springer for calculating fundamental component from fault transient signalsin
Nature, 2018, pp. 287-297. power systems,”Automation of Electric Power Systems, vol. 24, no. 1,
[8] Q. Chen, H. Hou, D. You et al., “Research on improvements of using pp. 30-33, Jan. 2000.
electronic current transformer on distance protection,” in Proceedings [22] W. Liu, Y. Pan, Y. Wang et al., “Effect of CT transient characteristics
of 42nd International University Power Engineering Conference, on transfer of inrush,” The Journal of Engineering, vol. 2019, no. 16,
Brighton, UK, Oct. 2007, pp. 267-272. pp. 3062-3066, Apr. 2019.
[9] Y.-C. Kang, S.-H. Ok, and S.-H. Kang, “A CT saturation detection al‐ [23] N. Farshid, K. Zahra, F. Ebrahim et al., “Fast detection and compensa‐
gorithm,” IEEE Transactions on Power Delivery, vol. 19, no. 1, pp. tion of current transformer saturation using extended Kalman filter,”
78-85, Jan. 2004. IEEE Transactions on Power Delivery, vol. 34, no. 3, pp. 1087-1097,
[10] S.-H. Kang, M.-S. Kim, S.-R. Nam et al., “A CT saturation detection Jun. 2019.
algorithm based on wavelet transformation,” in Proceedings of 12th [24] A. Hooshyar and M. Sanaye-Pasand, “Accurate measurement of fault
IET International Conference on Developments in Power System Pro‐ currents contaminated with decaying DC offset and CT saturation,”
tection, Copenhagen, Denmark, Mar.-Apr. 2014, pp. 1-7. IEEE Transactions on Power Delivery, vol. 27, no. 2, pp. 773-783,
[11] J. Ma, X. Gao, Z. Wang et al., “A new adaptive method to identify Apr. 2012.
TA saturation using grille fractal,” Canadian Journal of Electrical and
Computer Engineering, vol. 36, no. 4, pp. 152-157, Aug. 2013.
[12] S. Biswal and M. Biswal, “Algorithm for CT saturation detection with Yuping Zheng received the B.Sc. degree from Hefei University of Technol‐
the presence of noise,” in Proceedings of 4th International Conference ogy, Hefei, Anhui, in 1983. He received the M.Sc. degree from Nanjing Au‐
on Electrical Energy Systems (ICEES), Chennai, India, Feb. 2018, pp. tomation Research Institute, Nanjing, China, in 1986, and the Ph.D. degree
248-251. from Wuhan University, Wuhan, Hubei, in 2004. His research interests in‐
[13] A. Hooshyar, M. Sanaye-Pasand, and E. F. El-Saadany, “CT saturation clude relay protection and control of AC/DC hybrid power system.
detection based on waveshape properties of current difference func‐
tions,” IEEE Transactions on Power Delivery, vol. 28, no. 4, pp. 2254- Tonghua Wu received the B.Sc. degree from Hefei University of Technolo‐
2263, Oct. 2013. gy, Hefei, China, in 1999, the M.Sc. degree from State Grid Electric Power
[14] T. Ji, Q. Wu, W. Tang et al., “A morphological scheme for the correc‐ Research Institute, Nanjing, China, in 2005. He is currently pursuing the
tion of CT saturation waveforms,” in Proceedings of 2011 IEEE PES Ph. D. degree of automation of electric power systems at Hohai University,
General Meeting, Detroit, USA, Jul. 2011, pp. 1-7. Nanjing, China. His research interests include relay protection and control
[15] S. R. Mohantya, V. R. Pandi, B. K. Panigrahi et al., “Performance of AC/DC hybrid power system.
evaluation of distance relay with CT saturation,” Applied Soft Comput‐
ing, vol. 11, no. 8, pp. 4789-4797, Dec. 2011.
[16] E. M. Esmail, N. I. Elkalashy, T. A. Kawady et al., “Detection of par‐ Feng Hong received the B. Sc. and M. Sc. degrees from Hohai University,
tial saturation and waveform compensation of current transformers,” Nanjing, China, in 2005 and 2011, respectively. His research interests in‐
IEEE Transactions on Power Delivery, vol. 30, no. 3, pp. 1620-1622, clude relay protection and control of AC/DC hybrid power system.
Jun. 2015.
[17] A. Bagheri, M. Allahbakhshi, D. Behi et al., “Utilizing Rogowski coil Gang Yao received the B. Sc. degree from Southeast University, Nanjing,
for saturation detection and compensation in iron core current trans‐ China, in 2007, the master degree from State Grid Electric Power Research
former,” in Proceedings of 25th Iranian Conference on Electrical En‐ Institute, Nanjing, China, in 2010. His research interests include relay pro‐
gineering (ICEE), Tehran, Iran, May 2017, pp. 1066-1071. tection and control of AC/DC hybrid power system.
[18] B. Kasztenny and I. Voloh, “Application of distance and line current
differential relays in breaker-and-a-half configurations,” in Proceed‐ Jimin Chai received the B. Sc. degree from Xi’an Jiaotong University,
ings of IEEE/PES Transmission and Distribution Conference and Exhi‐ Xi’an, China, in 2004. He is currently pursuing the Ph.D. degree of automa‐
bition, Dallas, USA, May 2006, pp. 1-8. tion of electric power systems at Hohai University, Nanjing, China. His re‐
[19] ABB. (2011, Feb.). Line distance protection REL650 technical manu‐ search interests include relay protection and control of power system.
al. [Online]. Available: https://library. abb. com/share? cid=9AAC3030
1058 Zhinong Wei received the B.Sc. degree from Hefei University of Technolo‐
[20] Y. Yuan, Y. Lu, Z. Liu et al.,“A fast filter algorithm of short data win‐ gy, Hefei, China, in 1984, the M.Sc. degree from Southeast University, Nan‐
dow based on phase analysis,”Automation of Electric Power Systems, jing, China, in 1987, and the Ph.D. degree from Hohai University, Nanjing,
vol. 28, no. 3, pp. 58-63, Feb. 2004. China, in 2004. His research interests include power system operation, anal‐
[21] Y. Sun, Z. Zhang, Y. Shi et al.,“The short-window integral method ysis and control.