INVERTER SCROLL

INVERTER SCROLL

INVERTER SCROLL

4mm 이상 ~ 15mm 미만 (음화형 규정)

LG Electronics Distributed by

http://www.lg.com
http://partner.lge.com

Copyright © 2017 LG Electronics. All rights reserved.


INVERTER SCROLL
FEATURES & BENEFITS

INVERTER SCROLL
High Efficient Inverter Technologies
• EER 2.65 / COP 3.2 / ESEER 4.79 / SCOP 3.2
• All Inverter Scroll Compressor
• Water Outlet Temperature Control Without Hunting
• Enhanced Heating Performance by Vapor Injection Cycle
INVERTER SCROLL
Reliability & Stability
• Continuous Heating Operation
• Back Up Operation In Case Emergency
• Quick Maintenance Using Black Box Function
CONTENTS
• Corrosion Resistance ‘Ocean Black Fin’

06 HIGH EFFICIENT
Convenience INVERTER TECHNOLOGIES
• Smaller Footprint Due to Compact Size • All Inverter Scroll Compressor
• Low Noise Level • Lower Load Operation
• Silent Operation Function • Vapor Injection
• 5 Inch HMI Touch Controller with Various Functions

08 RELIABILITY & STABILITY


• Continuous Heating Operation
• Back Up Operation
• Corrosion Resistance (Ocean Black Fin)
• Black Box Function

10 CONVENIENCE
• Compact Size
• Low Noise Level
• Silent Operation Function (Cooling Mode)
• HMI Touch Controller
• Centralized Control of LG CHILLER (Option)
• Easy BMS Interface

14 APPENDIX
• Specification – Heat Pump Model
• Specification – Cooling Only Model
WHY
LG INVERTER SCROLL CHILLER? LINE-UP
The capacities of base models are 60 / 123 / 185 kW and
Max. 10 CHILLERS can be controlled by 1 central controller up to 1,850kW.
By applying world class EHP technology of
MULTI V, high efficient and reliable operation has achieved. Capacity (kW ) 60 123 185

Heat Pump Model


(ACHH *** LBAA)

Cooling Only Model


2 Lower Load Operation (ACAH *** LBAA)
• Wide Range of Frequency Down to 15Hz
• Minimum Operation 10%
Operation range (Hz)
Up to 1,850 kW (10 CHILLERS) by
125 ACP (Advanced Control Platform)
120
Range of Up to 925 kW (5 CHILLERS) by
HMI
Unit Control AC Smart Controller

20
15 Up to 925 kW (5 CHILLERS) by
HMI Touch controller
Other Company’s SCROLL CHILLER LG SCROLL CHILLER ※ Central controller ACP, AC Smart controller are option.

3 Continuous Heating Operation


• Continue Heating When Defrosting
5 OUR CHILLER HISTORY
4 Heating Defrost
1 Equipped with a comprehensive,
2015
full line-up of HVAC solutions,
3 LG offers optimized solutions tailored to
2 meet customer requirements. Making a Leap Forward 2012
as a Global Company
2012 World’s First Air-Bearing
Oil-Free Centrifugal CHILLER Developed

Total 92,288RT Centrifugal CHILLERS


2008 Provided in Saudi Arabia (Qurayyah IPP)

AHRI Certification Acquired


Expanding Our 2007
Capability Thru Innovation
1997 CHILLER Business in Middle East Started
(Motor City, 80,000RT, 32Units)

2 Stage Centrifugal CHILLER Developed


1 Inverter Technologies of LG EHP* 4 Pressure Control 1983
• Vapor Injection and HiPORTM** • More Precise and Reliable Operation / Applied to MULTI V Control Logic China Factory Established
1970
Building Our Base
Vapor Injection HiPORTM Technology Temperature Sensor Pressure Sensor 1968 First Shipment of Centrifugal CHILLER
for Nuclear Power Plant
High Pressure Gas Water Cooled Centrifugal
CHILLER (R11) Produced
Low
Pressure Gas
LG CHILLER Business Launched
Direct
Oil Return
Medium
Pressure Gas

※ EHP : Electric Heat Pump


※ ※ HiPORTM : High Pressure Oil Return
5 R-410A Refrigerant
• ODP* = 0, Eco-Friendly Refrigerant
※ ODP : Ozone Depletion Potential
INVERTER SCROLL

INVERTER SCROLL
HIGH EFFICIENT INVERTER
TECHNOLOGIES INVERTER SCROLL

ALL INVERTER All inverter scroll compressor with HiPORTM (Patent) is applied to LOWER LOAD 10% Part load operation and minimizing water outlet temperature
improve full load and part load energy efficiency. haunting with Inverter scroll compressors.
SCROLL OPERATION
COMPRESSOR All Inverter System LG Inverter Minimum 10%
Wide operation frequency range 15 ~ 125 Hz Scroll Compressor Operation

Target
Temperature 7°C

Compressor
Inverter Inverter
15Hz 20Hz

Normal On/Off Minimum 50%


Multi Compressor System Operation

Oil Target
Temperature 7°C
Separator
HiPORTM
On/Off On/Off
0% 100%

VAPOR Vapor injection technology (2 stage compression effect) improves


heating performance by 27% for cold region.
HiPORTM (Patent)
Maximizing reliability and efficiency
INJECTION
of the compressor through Vapor Injection Improved Heating Performance
Inverter125Hz Inverter120Hz recovering oil in compressor directly
• 2 Stage Compression Effect • T hanks to Vapor Injection and HIPORTM Technology,
• Heating Performance Heating Performance Improved by 27%
• Energy Efficiency
High Pressure
Gas Discharge
HIGH ENERGY All inverter SCROLL compressors with MULTI V technologies improve
Mid Pressure 27%
Increase
energy efficiency. Heating
EFFICIENCY Cooling Performance Heating Performance
Gas Suction Capacity

Low Pressure 160%


HiPORTM+ VI
Gas Suction
140%

9% 9% 32%32% 8% 8% 4% 4% Condenser TM
120% HiPOR
2.65 2.65 3.2 3.2 3.2 3.2 Normal
4.79 4.79 High
4.1 4.1 3.15 3.15 Temperature
2.44 2.44 2.97 2.97 3.09 3.09 100%
EEV Discharge
3.75 3.75 Mid Temperature
3.64 3.64 Suction 80%
2nd STAGE
SC
A Co. A Co. LG LG A Co. A B
Co.Co. B Co.
C Co. C Co.LG LG A Co. A Co. LG LG
A Co. A Co.
B Co. B Co.LG LG HEX Low 60% Outdoor
Temperature Temperature °C
EER EER ESEER*ESEER* Suction
COP COP SCOP**SCOP** -20 -15 -10 -5 0
1nd STAGE
Evaporator
※ 185 kW Heat pump model comparison
* ESEER : European seasonal energy efficiency ratio
** SCOP : Seasonal coefficient of performance

06 / 07
INVERTER SCROLL

INVERTER SCROLL
RELIABILITY &
STABILITY INVERTER SCROLL

CONTINUOUS Continuous heating minimizes the decrease of water outlet CORROSION ‘Ocean Black Fin’ heat exchanger is highly corrosion resistant, designed to
temperature during defrosting for multi circuit model. perform in corrosive environments such as contaminated and humid condition.
HEATING RESISTANCE
123kW (40 RT) and 185kW (60 RT) model with multi cycle can defrost each cycle individually to
OPERATION supply hot water continuously (OCEAN BLACK FIN)
• Longer Lifespan, Lower Operational Costs
• Strengthened Corrosion Resistant Coating

Hydrophilic Coating
The hydrophilic coating minimizes
moisture buildup on the fin.
Heating Operation Heating Operation Defrost
Evaporator Evaporator Condenser
Corrosion Resistant
EEV

EEV

EEV
Black Coating
Compressor Compressor Compressor
Condenser Condenser Evaporator The black coating provides strong
protection from corrosion.

Water Water
Outlet Inlet Aluminum Fin

BACK UP If one compressor or one cycle has a trouble or be repaired, backup BLACK BOX Quick service can be done because operation data can be saved
operation helps whole cycle to operate continuously. for 180 seconds before system failure.
OPERATION FUNCTION
Between Two Compressors
Without Black Box Function With Black Box Function
Check many failure causes and Search for the failure cause
error codes in person conveniently using recoded data
Backup

Take much service time and Save service time and


undergo trial and error diagnose it more accurately
Automatic
Emergency
Break
Down OFF ON OFF Backup Break
Down ON ON OFF Record operation data for
180 seconds before system failur!

Among The Cycles

Operating Operating Repairing

08 / 09
INVERTER SCROLL

INVERTER SCROLL

CONVENIENCE INVERTER SCROLL

COMPACT SIZE LG SCROLL CHILLER’S installation space is much smaller than A SILENT Silent operation function can reduce noise levels at night time by
company’s due to compact size. (43% Reduction) adjusting the fan RPM
OPERATION
INVERTER SCROLL FUNCTION Condenser Fan
INVERTER SCROLL Foot Print Comparison (COOLING MODE)
4.9m2
• RPM
INVERTER SCROLL Capacity
• Noise
43%
Area Peak Load

Load
A Co. 8.6m2
B Co. 5.4m2

※ 185kW (60 RT) Comparison

Sound
Level

Reduce Noise
LOW NOISE Lower noise can remove complains from noise pollution and provide a 3dB
quieter environment.
LEVEL
Noise Comparison ※ 185kW (60 RT) Comparison
(Heat Pump Model)

90 dB(A)
8
dB(A)
76 dB(A)
Highest Mode Mode Time
68 dB(A) Outdoor
Temperature Day
Start
Night
End
Day
8 hours 9 hours
60 dB(A)

50 dB(A)

Typical Urban Commercial A Company


Daytime Area LG SCROLL CHILLER SCROLL CHILLER Truck

10 / 11
INVERTER SCROLL

INVERTER SCROLL

CONVENIENCE INVERTER SCROLL

HMI TOUCH High level control option is preinstalled such as cycle monitoring, EASY BMS LG provides CHILLER controller system and BMS communication function.
schedule control and demand control with HMI touch controller.
CONTROLLER INTERFACE
User Friendly HMI Touch Controller
BMS : Building Management system
* LG ACP BACnet / LONwork Gateway is unconvertable to
LG CHILLER. Direct Modbus connection is available.
BMS
Unit Mounted
(Factory Installed)
LG HVAC Group
5”TFT LCD
Touch screen

Modbus
*LG Gateway

• Checking CHILLER Information MAX


(Pump / Flow Status, Pump On / Off, Flow
500M HMI Touch Controller Can Be Installed
Separately In Operation Room
Switch On / Off Etc.)

• Monitoring CHILLER Operation


(Each Cycle Operation Status, Air RS485 communication CHILLER AHU EHP AWHP Ventilation
Temperature Etc.) 500m
Remote
Controlling Operation Room
• Scheduling Function
• Anti-Freezing Function / Displaying Error History Etc. CHILLER Kit
(S/W)
• RS485 1Port, SD Card (Memory) LG Central Controller

Field devices

CENTRALIZED LG central CONTROLLER IV series (+CHILLER kit) provide CHILLER remote control and Security Lighting Sensor Actuator Valve
cycle monitoring (ACP IV : Max. 10 CHILLERS , AC SMART IV : Max. 5 CHILLERS).
CONTROL OF
Other Company’s HVAC Group
LG CHILLER
(OPTION) CHILLER
Status
Overview

Main View
Various HVAC Units
Web Access • Scroll, Screw, Centrifugal CHILLER
• Control and Monitor Absorption CHILLER & Heater
by Web Access • A/C, Ventilation, AHU, AWHP
ACP IV + CHILLER kit

Detail / Cycle view


Control /Monitor view
Detailed Control and Monitor Schedule Operation
• Automatic Unmanned Operation
• Control and Monitor on Screen

12 / 13
INVERTER SCROLL

INVERTER SCROLL

SPECIFICATION INVERTER SCROLL

HEAT PUMP (LG) participates in the ECP programme


for (EUROVENT LCP-HP program). COOLING ONLY (LG) participates in the ECP programme
for (EUROVENT LCP-HP program).

MODEL Check ongoing validity of certificate:


www.eurovent-certification.com
MODEL
Check ongoing validity of certificate:
www.eurovent-certification.com

Model ACHH020LBAA ACHH040LBAA ACHH060LBAA Model ACAH020LBAA ACAH040LBAA ACAH060LBAA


Inverter SCROLL CHILLER Inverter SCROLL CHILLER
H/P H/P H/P C/O C/O C/O
Power Phase, Lines, V 3, 4, 380 ~ 415 3, 4, 380 ~ 415 3, 4, 380 ~ 415 Power Phase, Lines, V 3, 4, 380 ~ 415 3, 4, 380 ~ 415 3, 4, 380 ~ 415
kW 60.0 123.0 185.0 kW 60.0 123.0 185.0
Cooling Capacity Cooling
RT 17 35 53 RT 17 35 53
Capacity
kW 70.3 141.0 211.0 Input
Heating Cooling kW 22.8 46.4 69.8
RT 20 40 60 Power

Input Cooling kW 22.8 46.4 69.8 Max Operating Current A 52 104 156
Power Heating kW 22.0 43.9 65.9 Efficiency Cooling W 2.63 2.65 2.65
Max Operating Current A 52 104 156 ESEER W/W 4.79 4.79 4.79
Cooling W/W 2.63 2.65 2.65 Sound Pressure dBA 67 68 68
Efficiency
Heating W/W 3.20 3.20 3.20 Sound power Cooling dBA 84 91 92
ESEER W/W 4.79 4.79 4.79 Type - Scroll Scroll Scroll
SCOP W/W 3.20 3.20 3.20 No. of Compressor EA 2 4 6
Sound Pressure dBA 67 68 68 Compressor Oil Type - PVE PVE PVE
Cooling 84 91 92 Oil Charge cc 1,400 * 2 1,400 * 4 1,400 * 6
Sound Power dBA
Heating 85 92 93 Sump Heater W 60 * 2 60 * 4 60 * 6
Type - Scroll Scroll Scroll Type - R410A R410A R410A
Refrigerant
No. of Compressor EA 2 4 6 Amout of Charged Kg 15 15 * 2 15 * 3
Compressor Oil Type - PVE PVE PVE Type - Plate Plate Plate
Oil Charge cc 1,400 * 2 1,400 * 4 1,400 * 6 Pressure Drop kPa 58.2 34 34
Sump Heater W 60 * 2 60 * 4 60 * 6 Operating Maxium Pressure
Condenser kg /cm2 42 / 10 42 / 10 42 / 10
(Refrigrant / Water)
Type - R410A R410A R410A
Refrigerant Standard Flow (Cooling) LPM 172 353 531
Amout of Charged Kg 14 14 * 2 14 * 3
Inlet / Outlet diameter mm 40A / 40A 65A / 65A 65A / 65A
Type - plate plate plate (Water pipe)
Pressure Drop kPa 58.2 34 34 Type - BLDC BLDC BLDC
Operating Maxium Pressure No. of Fan EA 2 4 6
Condenser kg /cm2 42 /10 42 /10 42 /10
(Refrigrant / Water)
Fan Motor No. of Vanes EA 4 4 4
Standard Flow (Cooling / Heating) LPM 172 / 202 353 / 404 531 / 604
Air Flow Rate CMM 210 * 2 @1,000rpm 210 * 4 @1,000rpm 210 * 6 @1,000rpm
Inlet / Outlet Diameter mm 40A / 40A 65A / 65A 65A / 65A
(Water Pipe) Motor Power W 900 * 2 900 * 4 900 * 6
Type - BLDC BLDC BLDC Expension Unit - EEV EEV EEV
No. of Fan EA 2 4 6 Weight kg 525 1,000 1,470
Fan motor No. of Vanes EA 4 4 4 W mm 765 1,528 2,291
Air Flow Rate CMM 210 * 2 @1,000rpm 210 * 4 @1,000rpm 210 * 6 @1,000rpm Dimension H mm 2,351 2,351 2,351
Motor Power W 900 * 2 900 * 4 900 * 6 D mm 2,154 2,154 2,154
Expension Unit - EEV EEV EEV Footprint m2/ RT 0.097 0.094 0.094
Weight kg 540 1,030 1,530 High / Low Pressure - ○ ○ ○
Protection
W mm 765 1,528 2,291 Devices Reversed Phase Sensor - ○ ○ ○
Dimension H mm 2,351 2,351 2,351 Flow Switch - ○ ○ ○
D mm 2,154 2,154 2,154 Remote Control - Modbus Modbus Modbus
Footprint m2 / RT 0.097 0.094 0.094 Power Power Line mm2 25.0mm2 × 5C 50.0mm2 × 5C 95.0mm2 × 5C
High / Low Pressure - ○ ○ ○ Outlet
Temperature Cooling ℃ 5 ~ 15 5 ~ 15 5 ~ 15
Protection Anti Frost - ○ ○ ○ Ambient Cooling ℃ -10 ~ 48 -10 ~ 48 -10 ~ 48
Devices Reversed Phase Sensor - ○ ○ ○ Temperature
Flow Switch - ○ ○ ○ Earth Leakage Breaker A 75 125 200
Remote Control - Modbus Modbus Modbus
Power Power Line mm2 25.0mm2 × 5C 50.0mm2 × 5C 95.0mm2 × 5C
Outlet Cooling ℃ 5 ~ 15 5 ~ 15 5 ~ 15
Temperature Heating ℃ 35 ~ 55 35 ~ 55 35 ~ 55
Ambient Cooling ℃ -10 ~ 48 -10 ~ 48 -10 ~ 48
Temperature Heating ℃ -15 ~ 35 -15 ~ 35 -15 ~ 35
Earth Leakage Breaker A 75 125 200

14 / 15