PROJECT

POLLUTION ABATEMENT (INTERCEPTION AND DIVERSION WITH STP) WORKS FOR


RIVER GANGA AT HOWRAH, BALLY AND BARANAGAR - KAMARAHATI MUNICIPAL TOWN
IN WEST BENGAL INCLUDING 15 YEARS O&M BASED ON HYBRID ANNUITY BASED PPP
MODE

IMPLEMENTING AGENCY

NATIONAL MISSION FOR CLEAN GANGA (NMCG)


PROJECT NO. & TENDER NO.

KMDA/WS/GAP/SE(N)/NIT-6/18-19 &
28 / SE (N)/GAP/W&S/KMDA of 2018-2019
CLIENT

KOLKATA METROPOLITAN DEVELOPMENT AUTHORITY (KMDA)


PROJECT ENGINEER

-
CONCESSIONAIRE

GANGA STP PROJECTS PRIVATE LIMITED


DOCUMENT TITLE

ELECTRICAL ERECTION BOQ FOR LS & MPS AREA

DOC. NUMBER REV


10P153-BOQ-M-XXX-LS&MPS 0
DISCIPLINE ENGINEERING-MECHANICAL,ELECTRICAL, C&I, CIVIL
STAMPING AREA

0 15-Apr-22 Submitted for Approval AG AG ARC


REV.
DATE DESCRIPTION PREPARED CHECKED APPROVED
NO

REVISION HISTORY

TOTAL NO. OF SHEETS (INCLUDING THIS COVER)= 1Nos

THIS DOCUMENT IS THE PROPERTY OF M/S VA TECH WABAG LIMITED


AND MUST NOT BE COPIED IN WHOLE OR PART OR LENT OUT WITHOUT THEIR WRITTEN PERMISSION
THIS DOCUMENT IS THE PROPERTY OF M/S VA TECH WABAG LIMITED
AND MUST NOT BE COPIED IN WHOLE OR PART OR LENT OUT WITHOUT THEIR WRITTEN PERMISSION

CONFIDENTIAL - Not to Disclose without authorisation


10P153 - ELECTRICAL ERECTION BOQ FOR LS & MPS AREA

HANUMAN BELUR MATH BALLY KHAL PANCHANANTALA


LOCATION JUTE MILL LS-2 LS-3 LS-4
LS-1
Sl. No. ITEM Description Dimension Weight / Unit UOM Quantity

A) ERECTION OF PANELS
Labour charges for shifting of Panels from the respective store/store –yard to work site with the help of Hydra & Crane (which is accessible in
site) & trained rigger, Placing /Erection of the same shall be done as per drawing in position with the help of Hydra/ Crane /Manual
Derrick/Chain-pully block /Other mechanical devices etc –(which is safer for erection and accessible to the site) & trained rigger. including
fabrication of frame work and painting of the same,alignment of the panel,interconnection of bus and control wiring, pre-commissioning and
commissioning of the same to the satisfaction of VA TECH
WABAG/client and all the test reports needs to be maintained, Incoming /Outgoing: As per SLD and panel wiring diagram .The rate includes
proper alignment as per procedure (including the supply of any kind consumeables and machineries) .
1 750 mm(L) X 1575 mm(D) X 2540 mm(H) 950 Kgs
11 KV CICO Panel
Rating : 3 Phase ,3 Wire, 11KV,50HZ,800A,20KA/3 Sec, No
Power Pack : 7HA, Input :230 V Ac,Output 24 V DC
2 750 mm(L) X 1575 mm(D) X 2540 mm(H) 950 Kgs
6 KV CICO Panel
Rating : 3 Phase ,3 Wire, 6KV,50HZ,800A,20KA/3 Sec, No 1
Power Pack : 7HA, Input :230 V Ac,Output 24 V DC
3 415 V LT PMCC With integreted APFC PANEL ,Incommer-1250A, and outgoing feeder as per SLD (APFC Rating : 150 KVAr) Location : Itchapur PS Location : Itchapur PS
Location : Itchapur PS 4250 mm(L) X 1050 mm(D) X 2075 mm(H) TS1: 230 Kgs
Transportation Section-1 : Length -1500 mm,Depth - 1000 mm,Height- 2075 mm TS2-150 Kgs
Transportation Section-2 : Length -1600 mm,Depth - 1000 mm,Height- 2075 mm TS3-180 Kgs
Transportation Section-3 : Length -1100 mm,Depth - 1000 mm,Height- 2075 mm
Type : Metallic Enclosure- Compartmetalized, Double Front, Fixed Type Feeder,Form-3B
Cable Entry: Bottom ,Dgree of Protection: IP-54

415 V LT PMCC With integreted APFC PANEL ,Incommer-1250A, and outgoing feeder as per SLD (APFC Rating : 200 KVAr) Location :Kona MPS
Location :Kona MPS Location :Kona MPS TS1: 230 Kgs
Transportation Section-1 : Length -1500 mm,Depth - 1000 mm,Height- 2075 mm 4750 mm(L) X 1050 mm(D) X 2075 mm(H) TS2-150 Kgs
Transportation Section-2 : Length -1700 mm,Depth - 1000 mm,Height- 2075 mm TS3-180 Kgs
Transportation Section-3 : Length -1500 mm,Depth - 1000 mm,Height- 2075 mm
Type : Metallic Enclosure- Compartmetalized, Double Front, Fixed Type Feeder,Form-3B
Cable Entry: Bottom ,Dgree of Protection: IP-54
Location :Hanuman Jute Mill-LS-1
415 V LT PMCC With integreted APFC PANEL ,Incommer-1250A, and outgoing feeder as per SLD (APFC Rating : 200 KVAr) TS1: 230 Kgs
Location :Hanuman Jute Mill-LS-1 TS2-150 Kgs
Transportation Section-1 : Length -1500 mm,Depth - 1000 mm,Height- 2075 mm Location :Hanuman Jute Mill-LS-1 TS3-180 Kgs No 1
Transportation Section-2 : Length -1800 mm,Depth - 1000 mm,Height- 2075 mm 4850 mm(L) X 1050 mm(D) X 2075 mm(H)
Transportation Section-3 : Length -1500 mm,Depth - 1000 mm,Height- 2075 mm Location :Matkhal MPS
Type : Metallic Enclosure- Compartmetalized, Double Front, Fixed Type Feeder,Form-3B TS1: 230 Kgs
Cable Entry: Bottom ,Dgree of Protection: IP-54 TS2-150 Kgs
TS3-180 Kgs
415 V LT PMCC With integreted APFC PANEL ,Incommer-1250A, and outgoing feeder as per SLD (APFC Rating : 200 KVAr) Location :Matkhal MPS
Location :Matkhal MPS 4850 mm(L) X 1050 mm(D) X 2075 mm(H)
Transportation Section-1 : Length -1500 mm,Depth - 1000 mm,Height- 2075 mm
Transportation Section-2 : Length -1800 mm,Depth - 1000 mm,Height- 2075 mm
Transportation Section-3 : Length -1500 mm,Depth - 1000 mm,Height- 2075 mm
Type : Metallic Enclosure- Compartmetalized, Double Front, Fixed Type Feeder,Form-3B
Cable Entry: Bottom ,Dgree of Protection: IP-54

4 415V Metering Panel No 1 1 1


5 415 V LT MCC With integreted APFC PANEL,Incommer-315A, and outgoing feeder as per SLD (APFC Rating : 50 KVAr) Location : BESU-IPS-1 Location : BESU-IPS-1
Location : BESU-IPS-1 3850 mm(L) X 650 mm(D) X 2075 mm(H) TS1: 230 Kgs
Transportation Section-1 : Length -1200 mm,Depth - 600 mm,Height- 2075 mm TS2-150 Kgs
Transportation Section-2 : Length -1450 mm,Depth - 600 mm,Height- 2075 mm TS3-180 Kgs
Transportation Section-3 : Length -1150 mm,Depth - 600 mm,Height- 2075 mm
Type : Metallic Enclosure- Compartmetalized, Single Front, Fixed Type Feeder,Form-3B
Cable Entry: Bottom ,Dgree of Protection: IP-54

415 V LT MCC With integreted APFC PANEL,Incommer-200A, and outgoing feeder as per SLD (APFC Rating : 30 KVAr) Location : CPT Land-IPS-2
Location : CPT Land-IPS-2 Location :CPT Land-IPS-2 TS1: 230 Kgs
Transportation Section-1 : Length -1100 mm,Depth - 500 mm,Height- 2075 mm 2300 mm(L) X 550 mm(D) X 2075 mm(H) TS2-150 Kgs
Transportation Section-2 : Length -1150 mm,Depth - 500 mm,Height- 2075 mm
Type : Metallic Enclosure- Compartmetalized, Single Front, Fixed Type Feeder,Form-3B
Cable Entry: Bottom ,Dgree of Protection: IP-54 Location : Round Tank-IPS-3
TS1: 230 Kgs
415 V LT MCC With integreted APFC PANEL,Incommer-315A, and outgoing feeder as per SLD (APFC Rating : 50 KVAr) Location Round Tank-IPS-3 TS2-150 Kgs
Location : Round Tank-IPS-3 3300 mm(L) X 650 mm(D) X 2075 mm(H)
Transportation Section-1 : Length -1200 mm,Depth - 600 mm,Height- 2075 mm
Transportation Section-2 : Length -2050 mm,Depth - 600 mm,Height- 2075 mm Location :Bally Khal -LS-3 No 1 1
Type : Metallic Enclosure- Compartmetalized, Single Front, Fixed Type Feeder,Form-3B TS1: 230 Kgs
Cable Entry: Bottom ,Dgree of Protection: IP-54 TS2-150 Kgs

415 V LT MCC With integreted APFC PANEL,Incommer-125A, and outgoing feeder as per SLD (APFC Rating : 20 KVAr) Location Bally Khal -LS-3
Location :Bally Khal -LS-3 2300 mm(L) X 550 mm(D) X 2075 mm(H)
Transportation Section-1 : Length -1100 mm,Depth - 500 mm,Height- 2075 mm
Transportation Section-2 : Length -1050 mm,Depth - 500 mm,Height- 2075 mm Location : Panchanantala-LS-4
Type : Metallic Enclosure- Compartmetalized, Single Front, Fixed Type Feeder,Form-3B TS1: 230 Kgs
Cable Entry: Bottom ,Dgree of Protection: IP-54 Location Panchanantala-LS-4 TS2-150 Kgs
2300 mm(L) X 550 mm(D) X 2075 mm(H)
415 V LT MCC With integreted APFC PANEL,Incommer-125A, and outgoing feeder as per SLD (APFC Rating : 20 KVAr)
Location :Panchanantala-LS-4
Transportation Section-1 : Length -1100 mm,Depth - 500 mm,Height- 2075 mm
Transportation Section-2 : Length -1150 mm,Depth - 500 mm,Height- 2075 mm
Type : Metallic Enclosure- Compartmetalized, Single Front, Fixed Type Feeder,Form-3B
Cable Entry: Bottom ,Dgree of Protection: IP-54

6 415 V LT MCC PANEL-Incommer-400A, and outgoing feeder as per SLD Location : Golabari-LS-6 Location : Golabari-LS-6
Location : Golabari-LS-6 2250 mm(L) X 550 mm(D) X 2075 mm(H) TS1: 230 Kgs
Transportation Section-1 : Length -2000 mm,Depth - 600 mm,Height- 2075 mm TS2-150 Kgs
Transportation Section-2 : Length -500 mm,Depth - 600 mm,Height- 2075 mm
Type : Metallic Enclosure- Compartmetalized, Single Front, Fixed Type Feeder,Form-3B
Cable Entry: Top ,Dgree of Protection: IP-54
Location : Arupara MPS
415 V LT MCC PANEL-Incommer-1000A, and outgoing feeder as per SLD Location :Arupara MPS TS1: 230 Kgs
Location : Arupara MPS 2650 mm(L) X 1050 mm(D) X 2075 mm(H) TS2-180 Kgs
Transportation Section-1 : Length -1600 mm,Depth - 1000 mm,Height- 2075 mm
Transportation Section-2 : Length -1000 mm,Depth - 1000 mm,Height- 2075 mm
Type : Metallic Enclosure- Compartmetalized, DoubleFront, Fixed Type Feeder,Form-3B
Cable Entry: Bottom ,Dgree of Protection: IP-54 Location : Belur Math-LS-2
Location : Belur Math-LS-2 TS1: 230 Kgs
415 V LT MCC PANEL-Incommer-400A, and outgoing feeder as per SLD 2600 mm(L) X 850 mm(D) X 2075 mm(H) TS2-180 Kgs
Location : Belur Math-LS-2
Transportation Section-1 : Length -1200 mm,Depth - 800 mm,Height- 2075 mm
Transportation Section-2 : Length -1350 mm,Depth - 800 mm,Height- 2075 mm
Type : Metallic Enclosure- Compartmetalized, DoubleFront, Fixed Type Feeder,Form-3B Location : Belur Math-LS-2 No 1
Cable Entry: Bottom ,Dgree of Protection: IP-54 TS1: 230 Kgs
Location : Saltgola-LS-5 TS2-180 Kgs
415 V LT MCC PANEL-Incommer-200A, and outgoing feeder as per SLD 2700 mm(L) X 550 mm(D) X 2075 mm(H)
Location : Saltgola-LS-5
Transportation Section-1 : Length -1100 mm,Depth - 500 mm,Height- 2075 mm
Transportation Section-2 : Length -1550 mm,Depth - 500 mm,Height- 2075 mm
Type : Metallic Enclosure- Compartmetalized, Single Front, Fixed Type Feeder,Form-3B
Cable Entry: Top ,Dgree of Protection: IP-54

7 415 V LT APFC PANEL Location : Golabari-LS-6 Location : Golabari-LS-6 :200 Kgs


Ratings : 62.5 KVAr 600 mm(L) X 500 mm(D) X 1775 mm(H)
Location : Golabari-LS-6 Location : Belur Math-LS-2
Cable Entry: Top ,Dgree of Protection: IP-54 :200 Kgs

415 V LT APFC PANEL Location : Belur Math-LS-2


Ratings : 50 KVAr 600 mm(L) X 500 mm(D) X 1775 mm(H)
Location : Belur Math-LS-2 Location : Saltgola-LS-5
Cable Entry: Top ,Dgree of Protection: IP-54 :200 Kgs
No 1
415 V LT APFC PANEL Location : Saltgola-LS-5
Ratings : 25 KVAr 600 mm(L) X 500 mm(D) X 1775 mm(H)
Location : Saltgola-LS-5
Cable Entry: Top ,Dgree of Protection: IP-54

B) ERECTION OF DISTRIBUTION TRNSFORMER


Labour charges for shifting of Panels from the respective store/store –yard to work site with the help of Hydra & Crane (which is accessible in
site) & trained rigger, Placing /Erection of the same shall be done as per drawing in position with the help of Hydra/ Crane /Manual
Derrick/Chain-pully block /Other mechanical devices etc –(which is safer for erection and accessible to the site) & trained rigger. including
fabrication of frame work and painting of the same,alignment of the RTCC panel,interconnection of control wiring, pre-commissioning and
commissioning of the same to the satisfaction of VA TECH
WABAG/client and all the test reports needs to be maintained, The rate includes Transformerwith OLTC & RTCC panel proper alignment as per
procedure (including the supply of any kind consumeables and machineries)
1 11 /0.433 KV ,800 KVA oil type Transformer with OLTC and RTCC panel Transformer with OLTC:
Vector Grope: Dyn11 4110 KG Approx/unit
Tappings on winding on HV side: ON-Load Tap Changer RTCC Panel: 150 KG/Unit
Number of Steps : 8 steps9 PositionRange of tappings for variation : +5% to -15% @2.5 %
Losses(KW) : Total Lossess at 50% loading :2287watts.Total Lossessat 100% loading : 6402watts
Positive sequence impedance on rated MVA base at rated current and
frequency at 75 deg C.winding temperature at Principle tap precent : :5 % Transformer with OLTC:
Efficiency at full load percent at 0.8 P.f : 99.02% 2600 mm(L) X 1700 mm(D) X 2250 mm(H)
RTCC Panel: Set
Type of cooling : ONAN
Mass of Oil : 860 Kgs 600 mm(L) X 600 mm(D) X 2200 mm(H)
Vol. of Oil : 1055 Ltr

2 6 /0.433 KV ,800 KVA oil type Transformer with OLTC and RTCC panel Transformer with OLTC:
Vector Grope: Dyn11 3395 KG Approx/unit
Tappings on winding on HV side: ON-Load Tap Changer RTCC Panel: 150 KG/Unit
Number of Steps : 8 steps9 PositionRange of tappings for variation : +5% to -15% @2.5 %
Losses(KW) : No load Loss : 1450 Watts, Load Loss: 9000 Watts
Positive sequence impedance on rated MVA base at rated current and Transformer with OLTC:
frequency at 75 deg C.winding temperature at Principle tap precent : :5 % 2600 mm(L) X 2600 mm(D) X 2200 mm(H)
Efficiency at full load percent at 0.8 P.f : 98.39% RTCC Panel: Set 1
Type of cooling : ONAN 600 mm(L) X 600 mm(D) X 2200 mm(H)
Mass of Oil : 810 Kgs
Vol. of Oil : 980 Ltr

C) ERECTION OF DIESEL GENERATOR


Labour charges for shifting of Panels from the respective store/store –yard to work site with the help of Hydra & Crane (which is accessible in
site) & trained rigger, Placing /Erection of the same shall be done as per drawing in position with the help of Hydra/ Crane /Manual
Derrick/Chain-pully block /Other mechanical devices etc –(which is safer for erection and accessible to the site) & trained rigger. including
fabrication & insultion of DG stack and painting of the same,alignment of the panel,interconnection of DG and control wiring, pre-
commissioning and commissioning of the same to the satisfaction of VA TECH
WABAG/client and all the test reports needs to be maintained, .The rate includes DG proper alignment as per procedure including fabrication &
insultion of DG stack (including the supply of any kind consumeables and machineries) .
1

415V, 50 KVA DG SET with Exhaust Stack and accessories


Application : Suitable for Prime continuous duty
Sound Proofing : Acoustic Enclosure
Engine Make : CUMMINS
Model No: 4BTAA3.3-G11
Rating : 50 KVA( BHP: 84)
Engine Speed: 1500RPM
No of cylinder: 4 Nos
Governer Class: G2 2950 mm(L) X 1150 mm(D) X 1550 mm(H) Static Weight - 1550 Kgs
Dinamic Weight - 2325 Kgs Set 1 1
Fuel consumption at full Load : 0.31 Liters/KWH
Inbuilt Fuel tank capacity : 170 (Ltr)
Electrical Syetm : Battery : 12V , 95 AH
Exhaust silencer Type: CRITICAL Grade
Exhaust Chimney Height : 6.11 Meter
Alternator make : Stamford
Model No: UCI224D
Rating : 50 KVA at 0.8 P.F
Insulation : Class H
Efficiency of Alternator at 100 % MCR & rated PF: 92.2
Power & Control Panel-Inside enclouser, Stand Mounted
Degree of Protection : IP4X
Cable Entry : Bottom
Controller : Integrated Microprocessor
Make : Cummins
Model No : PS0600
2

415V, 62.5 KVA DG SET with Exhaust Stack and accessories


Application : Suitable for Prime continuous duty
Sound Proofing : Acoustic Enclosure
Engine Make : CUMMINS
Model No: 4BTAA3.3-G11
Rating : 62.5 KVA(BHP: 84)
Engine Speed: 1500RPM
No of cylinder: 4 Nos 2950 mm(L) X 1150 mm(D) X 1550 mm(H) Static Weight - 1550 Kgs
Dinamic Weight - 2325 Kgs Set
Governer Class: G2
Fuel consumption at full Load : 0.30 Liters/KWH
Inbuilt Fuel tank capacity : 155 (Ltr)
Electrical Syetm : Battery : 12V , 95AH
Exhaust silencer Type: Residential Grade
Exhaust Chimney Height : 6.93 for IPS-2 CPT Land
Exhaust Chimney Height : 6.08 for LS-5 Salt Gola
Alternator make : Stamford
Model No: UCI224G
Rating : 82.5 KVA at 0.8 P.F
Insulation : Class H
Efficiency of Alternator at 100 % MCR & rated PF: 90.4
Power & Control Panel-Inside enclouser, Stand Mounted
Degree of Protection : IP4X
Cable Entry : Bottom
Controller : Integrated Microprocessor
Make : Cummins
Model No : PS0600
3

415V, 82.5 KVA DG SET with Exhaust Stack and accessories


Application : Suitable for Prime continuous duty
Sound Proofing : Acoustic Enclosure
Engine Make : CUMMINS
Model No: 4BTAA3.9-G4
Rating : 82.5 KVA( BHP: 110)
Engine Speed: 1500RPM
No of cylinder: 4 Nos
Governer Class: G2 Static Weight - 2000 Kgs
3850 mm(L) X 1150 mm(D) X 1700 mm(H) Set 1
Fuel consumption at full Load : 0.31 Liters/KWH Dinamic Weight - 3000 Kgs
Inbuilt Fuel tank capacity : 175 (Ltr)
Electrical Syetm : Battery : 12V , 95 AH
Exhaust silencer Type: Residential Grade
Exhaust Chimney Height :7.00 Meter
Alternator make : Stamford
Model No: UCI274V
Rating : 125 KVA at 0.8 P.F
Insulation : Class H
Efficiency of Alternator at 100 % MCR & rated PF: 91
Power & Control Panel-Inside enclouser, Stand Mounted
Degree of Protection : IP4X
Cable Entry : Bottom
Controller : Integrated Microprocessor
Make : Cummins
ModelNo : PS0600
4

415V, 100KVA DG SET with Exhaust Stack and accessories


Application : Suitable for Prime continuous duty
Sound Proofing : Acoustic Enclosure
Engine Make : CUMMINS
Model No: 6BTAA5.9-G13
Rating : 100 KVA( BHP: 159)
Engine Speed: 1500RPM
No of cylinder: 6 Nos
Governer Class: G2 Static Weight - 2200 Kgs
4000 mm(L) X 1150 mm(D) X 1850 mm(H) Set
Fuel consumption at full Load : 0.31 Liters/KWH Dinamic Weight - 3300 Kgs
Inbuilt Fuel tank capacity : 370 (Ltr)
Electrical Syetm : Battery : 12V , 95 AH
Exhaust silencer Type: HOSPITAL Grade
Exhaust Chimney Height :7.29 Meter
Alternator make : Stamford
Model No: UCI274V
Rating : 125 KVA at 0.8 P.F
Insulation : Class H
Efficiency of Alternator at 100 % MCR & rated PF: 91
Power & Control Panel-Inside enclouser, Stand Mounted
Degree of Protection : IP4X
Cable Entry : Bottom
Controller : Integrated Microprocessor
Make : Cummins
ModelNo : PS0600
5 4000 mm(L) X 1150 mm(D) X 1850 mm(H)

415V, 100KVA DG SET


Application : Suitable for Prime continuous duty
Sound Proofing : Acoustic Enclosure
Engine Make : CUMMINS
Model No: 6BTAA5.9-G13
Rating : 100 KVA( BHP: 159)
Engine Speed: 1500RPM
No of cylinder: 6 Nos
Governer Class: G2 Static Weight - 2200 Kgs
Fuel consumption at full Load : 0.31 Liters/KWH Dinamic Weight - 3300 Kgs Set 1
Inbuilt Fuel tank capacity : 370 (Ltr)
Electrical Syetm : Battery : 12V , 95AH
Exhaust silencer Type: Residential Grade
Exhaust Chimney Height :8.34Meter for IPS-1 -BESU
Exhaust Chimney Height :8.00Meter for LS-6 -Golabari
Alternator make : Stamford
Model No: UCI274F1
Rating : 160 KVA at 0.8 P.F
Insulation : Class H
Efficiency of Alternator at 100 % MCR & rated PF: 92.5
Power & Control Panel-Inside enclouser, Stand Mounted
Degree of Protection : IP4X
Cable Entry : Bottom
Controller : Integrated Microprocessor
Make : Cummins
Model No : PS0600
6 415V, 380KVA DG SET with Exhaust Stack and accessories
Application : Suitable for Prime continuous duty
Sound Proofing : Acoustic Enclosure
Engine Make : CUMMINS
Model No: QSN14-G2
Rating : 380 KVA (BHP: 487)
Engine Speed: 1500RPM
No of cylinder: 6 Nos
Governer Class: A1
Fuel consumption at full Load : 0.28 Liters/KWH
Inbuilt Fuel tank capacity : 450 (Ltr)
Electrical Syetm : Battery : 12V , 95 AH
Exhaust silencer Type: Hospital Grade
Exhaust Chimney Height : 12.69 Meter for Kona MPS
Exhaust Chimney Height : 11.65 Meter for Hanuman Jute Mill-LS-1
Alternator make : Stamford
Model No: HCI544D 5500 mm(L) X 1900 mm(D) X 2150 mm(H) Static Weight - 6250 Kgs
Dinamic Weight - 9375 Kgs Set 1
Rating : 500 KVA at 0.8 P.F
Insulation : Class H
Efficiency of Alternator at 100 % MCR & rated PF: 94.8
Power & Control Panel-Inside enclouser, Stand Mounted
Degree of Protection : IP4X
Cable Entry : Bottom
Controller : Integrated Microprocessor
Make : Cummis
Model No : PC1.2
415V, 600KVA DG SET with Exhaust Stack and accessories
Application : Suitable for Prime continuous duty
Sound Proofing : Acoustic Enclosure
Engine Make : CUMMINS
Model No: KTAA19-G12
Rating : 600 KVA (BHP: 713)
Engine Speed: 1500RPM
No of cylinder: 6 Nos
Governer Class: A1
Fuel consumption at full Load : 0.26 Liters/KWH
Inbuilt Fuel tank capacity : 832 (Ltr)
Electrical Syetm : Battery : 12V , 100 AH -2 Nos
Exhaust silencer Type: Hospital Grade
Exhaust Chimney Height : 12.90 Meter for Itchapur PS
Alternator make : Stamford
Model No: HCI544E Static Weight - 8090 Kgs
Rating : 600 KVA at 0.8 P.F 6500 mm(L) X 2000 mm(D) X 2775 mm(H) Set
Dinamic Weight - 12135 Kgs
Insulation : Class H
Efficiency of Alternator at 100 % MCR & rated PF: 94.9
Power & Control Panel-Inside enclouser, Stand Mounted
Degree of Protection : IP4X
Cable Entry : Bottom
Controller : Integrated Microprocessor
Make : Cummis
Model No : PC3.3

415V, 625KVA DG SET with Exhaust Stack and accessories


Application : Suitable for Prime continuous duty
Sound Proofing : Acoustic Enclosure
Engine Make : CUMMINS
Model No: KTAA19-G13
Rating : 625 KVA (BHP: 739)
Engine Speed: 1500RPM
No of cylinder: 6 Nos
Governer Class: A1
Fuel consumption at full Load : 0.26 Liters/KWH
Inbuilt Fuel tank capacity : 832 (Ltr)
Electrical Syetm : Battery : 12V , 100 AH -2 Nos
Exhaust silencer Type: Hospital Grade
Exhaust Chimney Height : 15.20 Meter for Kamarhati MPS
Alternator make : Stamford
Model No: HCI634W Static Weight - 8090 Kgs
Rating :750 KVA at 0.8 P.F 6500 mm(L) X 2000 mm(D) X 2775 mm(H) Set
Dinamic Weight - 12135 Kgs
Insulation : Class H
Efficiency of Alternator at 100 % MCR & rated PF: 95
Power & Control Panel-Inside enclouser, Stand Mounted
Degree of Protection : IP4X
Cable Entry : Bottom
Controller : Integrated Microprocessor
Make : Cummis
Model No : PC3.3
D) ERECTION OF UPS With Battery Bank
Labour charges for shifting of UPS With Battery Bank and ,
Battery Rack from the respective store/store- Placing /Erection of the same shall be done as per drawing (which is safer for erection and
accessible to the site). including alignment of the UPS,interconnection of battery and battery to UPS pre-commissioning and commissioning of
the same to the satisfaction of VA TECH
WABAG/client and all the test reports needs to be maintained. The rate includes proper alignment as per procedure (including the supply of
any kind consumeables and machineries)
Note: WABAG will arrange the visit of Vendor for Commissioniong of the same , erection contractor will have to assist him during the whole
process with manpower,machineries, tools and tackles and will cooperate with the vendor in every possible way.
1 1KVA UPS with Battery Bank( 2 Hour Battery Backup) UPS : UPS : 5.6 Kgs
1KVA UPS with ModBus Card Details 333mm(L) X 145 mm(D) X 282 mm(H)
Liebert GXT MT+ CX 16A UPS Battery Rack Diamension: 12 V Battery : 32.8 Kgs/Each
Input voltage : 230 V AC 350 mm(L) X 500 mm(D) X 550 mm(H)
Output voltage : 230 V AC
Make : Vertive
Battery Details : Set 1 1 1 1
No of Battery : 03 Nos
Battery Type : SMF 12 V , 100 AH , Make : Exide(EP100-12
No of Battery Stand (MOC: Metal): 1 Set

E) ERECTION OF DISTRIBUTION BOARDS WITH SUPPORTS


Labour charges for shifting of Distribution Boards from the respective store/store –yard to work site.
Placing/Erecting the same (including the fabrication , erection and painting of support ) and cable termination .
Pre-commissioning and commissioning of the same at different location (indoor + outdoor )of the plant , to the satisfaction of VA TECH
WABAG/client and all the test /reports needs to be maintained. The rate includes proper erection and testing as per procedure (including the
supply of any kind consumeables and machineries req for completion of work to the satisfactory of VA TECH / Client )

1 LDB Panel 500 mm(L) X 200 mm(D) X 600 mm(H) 80 Kgs No 1 1 1 1


2 PDB Panel (POWER DB) 700 mm(L) X 250 mm(D) X750 mm(H) 150 Kgs
Cable Entry: Bottom ,Dgree of Protection: IP-54 No 1 1 1 1
3 SPDB Panel (SUB- POWER DB) 500 mm(L) X 200 mm(D) X 400 mm(H) 80 Kgs
Cable Entry: Bottom ,Dgree of Protection: IP-54 No 1 1 1 1

4 SPDB Panel (SUB- POWER DB) 600 mm(L) X 200 mm(D) X 400 mm(H) 80 Kgs
Cable Entry: Bottom ,Dgree of Protection: IP-54 No 1

E) LAYING OF HT POWER CABLES


Labour charges for shifting of HT POWER CABLES drums/cutting and shifting of required length from the respective store/store –yard to work
site with the help of Hydra & Crane (which is accessible in site) & trained rigger.
Placing /Laying of the same shall be done as per
Electrical Cable Tray Routing Drawing in cable tray,Conduit pipes including excavation of soil in trench, laying of the cables in a neat way all
consumables like cable ties, cable tags, soldering materials,cable dressing materials such as clamps etc are in contractor scope. (Including
Burried cable trench and route marker for buried U/G Cables ) .Supply and erection of sand layer and brick as indicate in the cable tray routing
drawing & back filling of soil.except free issue materials like HT cable , HT cable termination kit & Cable routr marker.
Pre-commissioning and commissioning of the same to the satisfaction of VA TECH
WABAG/client and all the test /reports needs to be maintained. The rate includes proper laying and testing as per procedure (including the
supply of any kind consumeables and machineries)
1 Cable Size : 1C X 500 Sq.mm
Type: A2XCeWaY Mtr
Voltage Grade : 11 /!!KV (UE)
2 Cable Size : 1C X 630 Sq.mm
Type: A2XCeWaY 150
Voltage Grade :6.6 KV/6.6 KV (UE)

F) LAYING OF LT POWER AND CONTROL CABLES


Labour charges for shifting of LT POWER AND CONTROL CABLES drums/cutting and shifting of required length from the respective store/store –
yard to work site with the help of Hydra & Crane (which is accessible in site) & trained rigger.
Placing /Laying of the same shall be done as per
Electrical Cable Tray Routing Drawing in cable tray,Conduit pipes including excavation of soil in trench, laying of the cables in a neat way all
consumables like cable ties, cable tags, soldering materials,cable dressing materials such as clamps etc are in contractor scope. (Including
Burried cable trench and route marker for buried U/G Cables ) .Supply of lugs (power and control cable ) and erection of sand layer and brick as
indicate in the cable tray routing drawing & back filling of soil.except free issue materials like cable , GLAND & Cable routr marker.
Pre-commissioning and commissioning of the same to the satisfaction of VA TECH
WABAG/client and all the test /reports needs to be maintained. The rate includes proper laying and testing as per procedure (including the
supply of any kind consumeables and machineries)
LT Power cable
1
Cable Size: 3.5C x 400
Cable Type : A2XFY Mtr
Colour Scheme for identification:
Red, Yellow,Blue and Black
2
Cable Size: 3.5C x 300
Cable Type : A2XFY Mtr 200
Colour Scheme for identification:
Red, Yellow,Blue and Black
3
Cable Size: 3.5C x 150
Cable Type : A2XFY Mtr
Colour Scheme for identification:
Red, Yellow,Blue and Black
4
Cable Size: 3.5C x 120
Cable Type : A2XFY Mtr 100
Colour Scheme for identification:
Red, Yellow,Blue and Black
5
Cable Size: 3.5C x 95
Cable Type : A2XFY Mtr 50 50
Colour Scheme for identification:
Red, Yellow,Blue and Black
6
Cable Size: 3C x 300
Cable Type : A2XFY Mtr 200
Colour Scheme for identification:
Red, Yellow,Blue
7
Cable Size: 3C x 150
Cable Type : A2XFY Mtr
Colour Scheme for identification:
Red, Yellow,Blue
8
Cable Size: 3C x 120
Cable Type : A2XFY Mtr 75
Colour Scheme for identification:
Red, Yellow,Blue
9
Cable Size: 3C x 70
Cable Type : A2XFY Mtr
Colour Scheme for identification:
Red, Yellow,Blue
10
Cable Size: 3C x 35
Cable Type : A2XFY Mtr
Colour Scheme for identification:
Red, Yellow,Blue
11
Cable Size: 3C x 25
Cable Type : A2XFY Mtr 50
Colour Scheme for identification:
Red, Yellow,Blue
12
Cable Size: 3C x 10
Cable Type : A2XFY Mtr
Colour Scheme for identification:
Red, Yellow,Blue
13
Cable Size: 4C x 4
Cable Type : 2XWY Mtr 75 50 50 25
Colour Scheme for identification:
Red, Yellow,Blue and Black
14
Cable Size: 3C x 4
Cable Type : 2XWY Mtr 25 200 225
Colour Scheme for identification:
Red, Yellow,Blue and Black
15
Cable Size: 4C x 2.5
Cable Type : 2XWY Mtr 25
Colour Scheme for identification:
Red, Yellow,Blue and Black
16
Cable Size: 3C x 2.5
Cable Type : A2XFY Mtr 275 175 175 175
Colour Scheme for identification:
Red, Yellow,Blue
LT Control cable
1
Cable Size: 3C x 4
Cable Type : 2XWY Mtr 50
Colour Scheme for identification:
Red, Yellow,Blue and Black
2
Cable Size: 4C x 2.5
Cable Type : 2XWY Mtr 75 25 25 25
Colour Scheme for identification:
Red, Yellow,Blue and Black
3
Cable Size: 10C x 2.5
Cable Type : 2XWY Mtr 100
Colour Scheme for identification:
White core with number printing
4
Cable Size: 12C x 2.5
Cable Type : 2XWY Mtr 125 125 125 125
Colour Scheme for identification:
White core with number printing

G) HT CABLE TERMINATION
HT Cables end Termination along with suitable termination kit -including proper insulation,, Meggaring, testing, commissioning
complete to the satisfication(HT termination kit will be Supply By WABAG)
Pre-commissioning and commissioning of the same at different location (indoor + outdoor )of the plant , to the satisfaction of VA TECH
WABAG/client and all the test /reports needs to be maintained. The rate includes proper erection and testing as per procedure (including the
supply of any kind consumeables and machineries req for completion of work to the satisfactory of VA TECH / Client )
1 11 KV HT Termination Kit
suitable for Cable Size : 1C X 500 Sq.mm
Type: A2XCeWaY
Voltage Grade : 11 /!!KV (UE)
2 6.6 KV HT Termination Kit
suitable for Cable Size : 1C X 630 Sq.mm
Type: A2XCeWaY Nos 12
Voltage Grade :6.6 KV/6.6 KV (UE)
H)LV CABLE TERMINATION
Termination of Cables along with Double Compression Cable Glands, along with terminations of Lugs at Motor / PBS / Socket
Outlets/ Light Fittings/Elect. Eqpt. end including proper insulation,printed tubular ferule, Meggaring, testing, commissioning
complete to the satisfication(Gland shall be Supply By WABAG)
Pre-commissioning and commissioning of the same at different location (indoor + outdoor )of the plant , to the satisfaction of VA TECH
WABAG/client and all the test /reports needs to be maintained. The rate includes proper erection and testing as per procedure (including the
supply of required size of cable lugs ( power and control cables) and any kind consumeables and machineries req for completion of work to the
satisfactory of VA TECH / Client )
Cable Gland and Terminations
1
Weatherproof Type Double
Compression Cable Gland Suitable for Nos
Cable Size: 3.5C x 400
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 64
2
Weatherproof Type Double
Compression Cable Gland Suitable for Nos 16
Cable Size: 3.5C x 300
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 60
3
Weatherproof Type Double
Compression Cable Gland Suitable for Nos
Cable Size: 3.5C x 150
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 42
4
Weatherproof Type Double
Compression Cable Gland Suitable for Nos 8
Cable Size: 3.5C x 120
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 40
5
Weatherproof Type Double
Compression Cable Gland Suitable for Nos 4 4
Cable Size: 3.5C x 95
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 37
6
Weatherproof Type Double
Compression Cable Gland Suitable for Nos 16
Cable Size: 3C x 300
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 51
7
Weatherproof Type Double
Compression Cable Gland Suitable for Nos
Cable Size: 3C x 150
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 39
8
Weatherproof Type Double
Compression Cable Gland Suitable for Nos 6
Cable Size: 3C x 120
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 36
9
Weatherproof Type Double
Compression Cable Gland Suitable for Nos
Cable Size: 3C x 70
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 29
10
Weatherproof Type Double
Compression Cable Gland Suitable for
Cable Size: 3C x 35 Nos
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 24
Accessories : Shrouds
11
Weatherproof Type Double
Compression Cable Gland Suitable for
Cable Size: 3C x 25 Nos 4
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 23
Accessories : Shrouds
12
Weatherproof Type Double
Compression Cable Gland Suitable for
Cable Size: 3C x 10 Nos
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 20
Accessories : Shrouds
13
Weatherproof Type Double
Compression Cable Gland Suitable for
Cable Size: 4C x 4 Nos 6 4 4 2
Cable Type : 2XWY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 17
Accessories : Shrouds
14
Weatherproof Type Double
Compression Cable Gland Suitable for
Cable Size: 3C x 4 Nos 2 16 18
Cable Type : 2XWY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 16
Accessories : Shrouds
15
Weatherproof Type Double
Compression Cable Gland Suitable for
Cable Size: 4C x 2.5 Nos 2
Cable Type : 2XWY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 16
Accessories : Shrouds
16
Weatherproof Type Double
Compression Cable Gland Suitable for
Cable Size: 3C x 2.5 Nos 22 14 14 14
Cable Type : A2XFY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 15
Accessories : Shrouds
17
Weatherproof Type Double
Compression Cable Gland Suitable for
Cable Size: 3C x 4 Nos 4
Cable Type : 2XWY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 16
Accessories : Shrouds
18
Weatherproof Type Double
Compression Cable Gland Suitable for
Cable Size: 4C x 2.5 Nos 6 2 2 2
Cable Type : 2XWY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 16
Accessories : Shrouds
19
Weatherproof Type Double
Compression Cable Gland Suitable for
Cable Size: 10C x 2.5 Nos 8
Cable Type : 2XWY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 21
Accessories : Shrouds
20
Weatherproof Type Double
Compression Cable Gland Suitable for
Cable Size: 12C x 2.5 Nos 10 10 10 10
Cable Type : 2XWY
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) : 23
Accessories : Shrouds
21
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos 4 4
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
(7.5 KW & KW : 15)
Power Cable : 1R x 4C x 1.5Sq.mm
22
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos 6 6
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
(7.5 KW & KW : 15)
Power Cable : 1R x 3C x 1.5Sq.mm
23
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
(22 KW & KW : 30)
Power Cable : 1R x 4C x 4Sq.mm
24
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos 4
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
(22 KW & KW : 30)
Power Cable : 1R x 3C x 4Sq.mm
25
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
KW : 37
Power Cable : 1R x 4C x 6Sq.mm
26
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
KW : 37
Power Cable : 1R x 3C x 6Sq.mm
27
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
(45KW & KW : 55)
Power Cable : 1R x 4C x 10Sq.mm
28
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
(45KW & KW : 55)
Power Cable : 1R x 3C x 10Sq.mm
29
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos 3
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
KW : 75
Power Cable : 1R x 4C x 16Sq.mm
30
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos 3
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
KW : 75
Power Cable : 1R x 3C x 16Sq.mm
31
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
KW : 90
Power Cable : 1R x 4C x 25Sq.mm
32
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
KW : 90
Power Cable : 1R x 3C x 25Sq.mm
33
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos 2
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
KW : 132
Power Cable : 1R x 4C x 35Sq.mm
34
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos 2
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
KW : 132
Power Cable : 1R x 3C x 35Sq.mm
35
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
KW : 200
Power Cable : 1R x 4C x 95Sq.mm
36
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
KW : 200
Power Cable : 1R x 3C x 95Sq.mm
37
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos 3
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
KW : 250
Power Cable : 1R x 4C x 120Sq.mm
38
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos 3
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
KW : 250
Power Cable : 1R x 3C x 120Sq.mm
39
Nylon Type Cable Gland Suitable fo
Cable Size:
Cable Type: YY Nos 5 5 5 5
Appr. Overall Dia. of Cable (tolerance +/- 2mm)(mm) :
All rating Start from 7.5 KW to 250 KW
Power Cable : 1R x 15C x 1.5Sq.mm

I) LAYING OF CABLE TRAYS AND ACCESSORIES


Labour charges for shifting CABLE TRAYS AND ACCESSORIES from the respective store/store –yard to work site with the help of Hydra & Crane
(which is accessible in site) & trained workforce.
Placing /Laying/Cutting req length of cable trays ( along with coupler plate, nut , bolt and washer, etc. ,including the site fabrication of Angle/
Bend / TEE / Square/ Offset) with fabrication, erection and painting of supports shall be done as per Electrical Cable Tray Routing Drawing.
Pre-commissioning and commissioning of the same to the satisfaction of VA TECH WABAG/client and all the test /reports needs to be
maintained. The rates includes proper laying cable trays including the site fabrication of Angle/ Bend / TEE / Square/ Offset) with fabrication and
testing as per procedure (including the supply of any kind consumeables and machineries req for completion of work to the satisfactory of VA
TECH / Client )
Note: Billing will be as per running metres .
1 150 Width X 100 Height,thickness: 2 mm Ladder type GI Cable tray Mtr 22.5 17.5 17.5 17.5
2 300 Width X 100 Height,thickness: 2 mm Ladder type GI Cable tray Mtr 32.5 10 10 10

J) LAYING OF GI EARTHING AND LIGHTENING STRIPS/WIRES


Labour charges for shifting of GI EARTHING AND LIGHTENING STRIPS/WIRES from the respective store/store –yard to work site.
Placing/Erecting/Laying the same in buried underground trenches/Trays ,complete civil work associated with this activity,connections to all
utility items, etc., will be in contractor's scope.
Pre-commissioning and commissioning of the same at different location (indoor + outdoor )of the plant to the satisfaction of VA TECH
WABAG/client and all the test /reports needs to be maintained. The rate includes proper erection and testing as per procedure (including the
supply of any kind consumeables,Scaffolding and machineries req for completion of work to the satisfactory of VA TECH / Client )
Supply of Charcoal and salt and the civil works for earth pits will be in contractors scope.
Any joints shall be treated with anti corrosive paints, the joint below grade shall be welded/brazed. Welding or brazzing shall be done with over
lapping of strip equivalent to double the width of the strip and all four sides shall be continuously riveted/brazed . The equipment end
connection shall be bolted using passivated hardwares.
Earthing System
1 50 x 6 mm GI flat Mtr 30
2 40 x 6 mm
50 x 6 mm GI flat Mtr 20
3 25 x 3 mm GI flat Mtr 25 45 25 25
4 4 SWG GI Wire Mtr 30 30
5 8 SWG GI Wire Mtr 20 20
6
6 Sq.mm
Copper flexible cable for Ins
Earthing
Size : 1C x 6Sq.mm
Type of Insulation: PVC Mtr 25 25 25 25
Rated Voltage: 1.1 KV
Material of Conductor:StandardCopper Conductor
Colour Scheme for identification:
Yellow Green or Green

7 Earth electrode
40mm dia 3000 mm long heavy Duty G.I. pipe electrode Nos 6 6 6 6
8 75 x 10 mm GI flat Mtr 243 222 206 206
9 Earth electrode 40mm dia 3000 mm long heavy Duty G.I. Pipe with 600 x 600 x 6 mm GI plate for Plate earthing Nos 4 2 2 2
10 25 x 6 mm GI flat Mtr 30
Lightning Systems
1 25 x 3 mm GI flat Mtr 76 45 43 39
2 1.5M long lightning spike with all accessories Nos 2 2 2 2
3 TEST LINK SUITABLE FOR (25X3mm GI.FLAT) Nos 2 2 2 2
4 2METER LONG,20MM DIA. Cu AIR TERMINATION ROD WITH MOUNTING ASSEMBLY (SUITABLE FOR 25X3MM GI. FLAT) Nos 1 1 1 1
5 Fixing of Insulator - suitable for Lightning Arrester GI strip for 25x3 mm with required size of M8 x 50 mm long anchor fastner and
M8 x 15 mm long GI Bolt with double washers

Nos 102 61 58 52

K) Light Fixture Lot 1 1 1 1


L) Lighting Accessories Lot 1 1 1 1

M) ERECTION OF ANCILLARY EQUIPMENTS (Electrical Safety Items )


Labour charges for shifting of Ancillary Equipments from the respective store/store –yard to work site.
Placing/Erecting the same (including the fabrication , erection and painting of support )
Pre-commissioning and commissioning of the same at different location (indoor + outdoor )of the plant , to the satisfaction of VA TECH
WABAG/client and all the test /reports needs to be maintained. The rate includes proper erection and testing as per procedure (including the
supply of any kind consumeables and machineries req for completion of work to the satisfactory of VA TECH / Client )
1 Safety Chart One Treatment for Electrical Shock "Metal Enamel Instruction Plate,Writen in English,Hindi No 1 1 1 1
2 CPR Chart writen in English,Hindi , a Standard MS plate with painted No 1 1 1 1
3 Danger Board 11 KV Writen in English,Hindi Standard 2 mm thick MS plate with painted No
4 Danger Board 6KV Writen in English,Hindi Standard 2 mm thick MS plate with painted No 2
5 Danger Board 415V Writen in English,Hindi Standard MS plate with painted No 2 2 2 2
6 Caution board Writen in English,Hindi Standard MS plate with painted No 1 1 1 1
7 Hand Gloves(1pair= 2 Nos) Suitable for 11 KV Grade Pair 1
8 Hand Gloves(1pair= 2 Nos) Suitable for 415 V Grade Pair 1 1 1 1
9 Fire Bucket with Stand with 4 nos of Bucket Set 1
10
RMU Panel - Safety Rubber mat 11 kv As per IS:15652:2006
Sie : 1700 mm (L) X 1000 MM(W) No 1
Colour Blue
11
RTCC Panel - Safety Rubber mat 415 V As per IS: 15652 : 2006
Size : 1000 mm (L) X 1000 mm (W) No 1
Colour : Black
12
CICO Panel - Safety Rubber mat 11KV As per IS: 15652 : 2006
Size :1000 mm (L) X 1000 mm (W) No 1
Colour : Blue
13 RUBBER MAT - PUMPING STATION 1) Location : Itchapur PS : SIZE 4250 mm(L) X1000MM (W)
PMCC with APFC Panel - Safety Rubber Mat - 415 KV As per IS : 15652 : 2006 2) Location :Kona MPS : SIZE 4750 mm(L) X1000MM (W)
Colour : Black 3) Location :Hanuman Jute Mill-LS-1 : SIZE 4850 mm(L) X1000MM (W) No 1
4) Location :Matkhal MPS : SIZE 4850 mm(L) X1000MM (W)
14 RUBBER MAT - PUMPING STATION 1) Location : BESU-IPS-1 : SIZE 3850 mm(L) X1000MM (W)
MCC with APFC Panel - Safety Rubber Mat - 415 KV As per IS : 15652 : 2006 2) Location :CPT Land-IPS-2 : SIZE 2300 mm(L) X1000MM (W)
Colour : Black 3) Location Round Tank-IPS-3 : SIZE 3300 mm(L) X1000MM (W)
4) Location Bally Khal -LS-3 : SIZE 2300 mm(L) X1000MM (W) No 1 1
5) Location Panchanantala-LS-4 : SIZE 2300 mm(L) X1000MM (W)

15 RUBBER MAT - PUMPING STATION 1) Location : Golabari-LS-6 : SIZE 2550 mm(L) X1000MM (W)
APFC Panel - Safety Rubber Mat - 415 KV As per IS : 15652 : 2006 2) Location : Belur Math-LS-2 : SIZE 2600 mm(L) X1000MM (W) No 1
Colour : Black 3) Location : Saltgola-LS-5 : SIZE 2700 mm(L) X1000MM (W)

16 Fire Extinguiser Type : Co2 Wall Mounted ,Hand Operated No 1 1 1 1


Weight-4.5kgs.
Support Steel
17 ISMC-100, MOC - GI MT 0.6 0.3 0.3 0.3
18 ISA-50,MOC-GI MT 0.2 0.1 0.1 0.1
Miscellenous
M12 x 100 mmItemsLong(Anchor Fasteners,Bold
GI Anchor Fasteners (Pinand Nuts)
type Anchor) for fixing for LDB,PDB,SPBD, LCP
19 M12 x 100 mm Long GI Anchor Fasteners (Pin type Anchor) for fixing for Cable tray and panel base frame Nos
20 Nos
GI Conduit and Bends for cables Lot 1 1 1 1
Flexible Hose for cables Lot 1 1 1 1
21 Installation of Weatherproof 63 Amps Power socket , 415V , 3 Ph with Neutral, Heavey duty Non metalic power plug with FRP (3mm ) Thick Length -200 mm,Depth - 145 mm,Height- 335 mm
canopy Nos 1 1 1 1
22 Installation of Cable marker over ground for UG HT cables at all bends,loops,joints, crossing points and at every 25 Meterintraval on stright runs.
MOC: Galvanised Cast Iron
Size : 200mm x 100MM x 5mm Thickness
Colour of plate back ground and lettering – yellow colour with Black colour Letters
75mm L angle Support with Nuts & Bolt to the plate burring it. Height of the angle should be – 700mm height
Cable markers shall be anchored in the ground at a depth of minimum 500mm
Message on each plate- Example Nos
11kV HT cable Depth @ 1000mm depth (30mm size letters)

23 Installation of Cable marker over ground for UG HT cables at all bends,loops,joints, crossing points and at every 25 Meterintraval on stright runs.
MOC: Galvanised Cast Iron
Size : 200mm x 100MM x 5mm Thickness
Colour of plate back ground and lettering – yellow colour with Black colour Letters
75mm L angle Support with Nuts & Bolt to the plate burring it. Height of the angle should be – 700mm height
Cable markers shall be anchored in the ground at a depth of minimum 500mm
Message on each plate- Example Nos 5
6kV HT cable Depth @ 1000mm depth (30mm size letters)

24 Installation of Cable marker over ground for UG LT cables at all bends,loops,joints, crossing points and at every 25 Meterintraval on stright runs.
MOC: Galvanised Cast Iron
Size : 200mm x 100MM x 5mm Thickness
Colour of plate back ground and lettering – yellow colour with Black colour Letters
75mm L angle Support with Nuts & Bolt to the plate burring it. Height of the angle should be – 700mm height
Cable markers shall be anchored in the ground at a depth of minimum 500mm
Message on each plate- Example Nos 16 16 16
415V HT cable Depth @ 1000mm depth (30mm size letters)

Spreading of sand
1 As per the underground cable routing - requied sand bedding to be done ( Supply of sand will be under the Wabag Scope of Supply)
Cu.M 10000
Laying of cable protective cover
1 Laying of cable protective cover ( made of Reinforced concreate ) for HT Cable Nos 500
( Supply of sand will be under the Wabag Scope of Supply)
2 Laying of cable protective cover ( made of Earthenware ) Brick for LT cable Nos 20000
( Supply of sand will be under the Wabag Scope of Supply)
M) ERECTION OF LOCAL CONTROL PANEL FOR PUMPS WITH SUPPORTS
Labour charges for shifting of Local control panel for pumps from the respective store/store –yard to work site.
Placing/Erecting the same (including the fabrication , erection and painting of support ) and cable termination .
Pre-commissioning and commissioning of the same at different location (indoor + outdoor )of the plant , to the satisfaction of VA TECH
WABAG/client and all the test /reports needs to be maintained. The rate includes proper erection and testing as per procedure (including the
supply of any kind consumeables and machineries req for completion of work to the satisfactory of VA TECH / Client )

1 Local Control panel for 7.5KW-Wet Pit Submersible Pump


Location-Bally Khal-LS-2- Tag No-P-1208 A/B-2 Nos
Location-Panchanantala-LS-4-Tag No-P-1210 A/B-2 Nos 800 mm (L) X 300 mm(D) X 600 mm(H) 80 Kgs 2 2
Type of Feeder-DOL

2 Local Control panel for 15KW-Wet Pit Submersible Pump


Location-Bally Khal-LS-2-Tag No-P-1207 A/B/C-3 Nos
Location-Panchanantala-LS-4-Tag No-P-1209 A/B/C-3 Nos
Location-Salt Gola -LS-5-Tag No-P-1202 A/B-2 Nos 850 mm (L) X 300 mm(D) X 600 mm(H) 82 Kgs 3 3
Type of Feeder-Star Delta

3 Local Control panel for 15KW-Dry Pit Submersible Pump


Location-CPT Land-IPS-2-Tag No-P-3204 A/B/C-3 No 850 mm (L) X 300 mm(D) X 600 mm(H) 82 Kgs
Type of Feeder-Star Delta

4 Local Control panel for 22KW-Dry Pit Submersible Pump


Location-CPT Land -IPS-2-Tag No-P-3203 A/B/C-3 Nos
Location-Round Tank - IPS-3 -Tag No-P-3206 A/B/C-3 Nos 850 mm (L) X 300 mm(D) X 600 mm(H) 82 Kgs
Type of Feeder-Star Delta

5 Local Control panel for 30KW-Wet Pit Submersible Pump


Location-Belur Math - LS-2-Tag No-P-1206 A/B-2 Nos
Location-Salt Gola -LS-5 -Tag No-P-1201 A/B/C-3 Nos 850 mm (L) X 300 mm(D) X 600 mm(H) 82 Kgs 2
Type of Feeder-Soft Starter

6 Local Control panel for 37KW-Wet Pit Submersible Pump


Location-Golabari-LS-6-P-1204 A/B-2 Nos 850 mm (L) X 300 mm(D) X 600 mm(H) 82 Kgs
Type of Feeder-Soft Starter

7 Local Control panel for 37KW-Dry Pit Submersible Pump


Location-BESU-IPS-1-Tag No-P-3202 A/B-2 Nos 850 mm (L) X 300 mm(D) X 600 mm(H) 82 Kgs
Type of Feeder-Soft Starter

8 Local Control panel for 45KW-Dry Pit Submersible Pump


Location-Round Tank - IPS-3 -Tag No-P-3205 A/B/C-3 Nos 850 mm (L) X 300 mm(D) X 600 mm(H) 82 Kgs
Type of Feeder-Soft Starter

9 Local Control panel for 55KW-Dry Pit Submersible Pump


Location-BESU-IPS-1-Tag No-P-3201 A/B/C-3 Nos 850 mm (L) X 300 mm(D) X 600 mm(H) 82 Kgs
Type of Feeder-Soft Starter

10 Local Control panel for 75KW-Wet Pit Submersible Pump


Location-Belur Math - LS-2-P-1205 A/B/C-3 Nos
Location-Golabari-LS-6 -P-1203 A/B/C-3 Nos 850 mm (L) X 300 mm(D) X 600 mm(H) 82 Kgs 3
Type of Feeder-Soft Starter

11 Local Control panel for 90KW-Dry Pit Submersible Pump


Location-Itchapur PS-Tag No-P-3208 A/B-2 Nos
Location-Arupara MPS -Tag No-P-3210 A/B-2 Nos 850 mm (L) X 300 mm(D) X 600 mm(H) 82 Kgs
Type of Feeder-Soft Starter

12 Local Control panel for 132KW-Dry Pit Submersible Pump


Location-Hanuman Jute Mill-Tag No-P-1212 A/B-2 Nos
Location-Kona MPS-Tag No-P-1214 A/B-2 Nos
Location-Kamarhati MPS -Tag No-P-2202 A/B-2 Nos 950 mm (L) X 300 mm(D) X 600 mm(H) 95Kgs 2
Type of Feeder-Soft Starter

13 Local Control panel for 200KW-Dry Pit Submersible Pump


Location-Itchapur PS-Tag No-P-3207 A/B-2 Nos
Location-Arupara MPS -Tag No-P-3209 A/B-2 Nos 1000 mm (L) X 300 mm(D) X 600 mm(H) 100Kgs
Type of Feeder-Soft Starter

14 Local Control panel for 250KW-Dry Pit Submersible Pump


Location-Hanuman Jute Mill-Tag No-P-1211 A/B/C-3 Nos
Location-Kona MPS-Tag No-P-1213 A/B/C-3 Nos
Location-Kamarhati MPS -Tag No-P-2201 A/B/C-3 Nos 1000 mm (L) X 300 mm(D) X 600 mm(H) 100Kgs 3
Type of Feeder-Soft Starter
SALT GOLA GOLABARI BESU CPT LAND IPS ROUND TANK ICHAPUR
LS-5 LS-6 KONA MPS MATKHAL MPS IPS-1 IPS-2 IPS-3 PS ARUPARA MPS TOTAL

Unit Rate Total

1 1

1 1 3

1 1 1 4

1 1 1 1 1 8

1 1 1 5

1 1 1 4

1 1 3

1 1

1 1 3
2

1 1 2

1 1

1 2

1 2
1 1

1 1
1 1 1 1 1 1 1 1 1 13

1 1 1 1 1 1 1 1 1 13
1 1 1 1 1 1 1 1 1 13

1 1 1 1 1 1 1 1 1 13

1 1 1 4

150 150

150 150 450

3200 3200

200 200 50 50 200 900

50 50

50 100 250

100

200 200 600

100 100 200

75 50 50 250

75 75 150

50 50 100

75 125

150

150 300

50 50 75 75 40 40 40 65 45 680

100 25 25 150 25 775

25 25 25 100

175 175 275 275 175 200 200 250 150 2675

25 25 50 150

25 25 75 75 25 25 25 75 500

100 100 110 410

125 125 125 125 125 150 150 100 100 1625

12 12

12 12 36
16 16

16 16 4 4 16 72

4 4

4 8 20

16 16 48

8 8 16

6 4 4 20

6 6 12

4 4 8

6 10

12 12 24

4 4 6 6 4 4 4 6 4 58

8 2 2 12 2 62

2 2 2 8

14 14 22 22 14 16 16 20 12 214

2 2 4 12

2 2 6 6 2 2 2 6 40

8 8 8 32

10 10 10 10 10 12 12 8 8 130

4 6 22

6 6 12

6 10

2 2 4

2 2 4

6 6
6 6

3 6

3 6

2 2 4

2 2 4

2 2 6

2 2 6

2 2 4

2 2 4

3 3 9

3 3 9

5 5 5 5 5 6 6 4 4 65

17.5 17.5 22.5 25 20 10 22.5 17.5 227.5


10 10 15 47.5 40 32.5 42.5 42.5 40 342.5

30 30 30 30 150
20 20 20 20 100
55 25 25 25 25 55 55 25 25 435
20 80
40

25 25 25 25 25 25 25 25 25 325

6 6 6 11 6 6 6 6 6 83
201 214 248 285 265 255 247 283 259 3134
2 2 4 4 2 2 2 4 32
50 50 30 160

40 40 97 120 78 96 79 107 109 969


2 2 2 2 2 2 2 2 2 26
2 2 2 2 2 2 2 2 2 26
1 1 1 1 1 1 1 1 1 13

54 54 129 161 105 129 106 143 146 1300

1 1 1 1 1 1 1 1 1 13
1 1 1 1 1 1 1 1 1 13

1 1 1 1 1 1 1 1 1 13
1 1 1 1 1 1 1 1 1 13
2 2
2 2 6
2 2 2 2 2 2 2 2 2 26
1 1 1 1 1 1 1 1 1 13
1 1 1 4
1 1 1 1 1 1 1 1 1 13
1 1 1 4

1 1 1 4

1 1 1 4

1 1 1 4

1 1 1 4
1 1 1 1 6

1 1 3

1 1 1 1 1 1 1 1 1 13

0.3 0.3 1.2 1.2 0.6 0.6 0.6 1.2 1.2 8.7
0.1 0.1 0.4 0.4 0.2 0.2 0.2 0.4 0.4 2.9

1000
1520
1 1 1 1 1 1 1 1 1 13
1 1 1 1 1 1 1 1 1 13
1 1 1 1 1 1 1 1 1 13

5 5

5 5 15

16 16 16 16 16 16 144

2 8

3 3

3 3 6

3 5

2 2

2 2

3 3

3 3

3 6

2 2 4

2 2 6

2 2 4

3 3 9
Supply of Lugs Details
S. No Description Unit QTY
1 400 Sq.mm AL.Ring Type Lugs Nos 48
2 300 Sq.mm AL.Ring Type Lugs Nos 360
3 185 Sq.mm AL.Ring Type Lugs Nos 16
4 150 Sq.mm AL.Ring Type Lugs Nos 132
5 120 Sq.mm AL.Ring Type Lugs Nos 183
6 95 Sq.mm AL.Ring Type Lugs Nos 56
7 70 Sq.mm AL.Ring Type Lugs Nos 56
8 50 Sq.mm AL.Ring Type Lugs Nos 8
9 35 Sq.mm AL.Ring Type Lugs Nos 66
10 25 Sq.mm AL.Ring Type Lugs Nos 58
11 16 Sq.mm AL.Ring Type Lugs Nos 42
12 10 Sq.mm AL.Ring Type Lugs Nos 114
13 6 Sq.mm AL.Ring Type Lugs Nos 28
14 4 Sq.mm CU.Ring Type Lugs Nos 542
15 2.5 Sq.mm CU.Ring/PIN Type Lugs Nos 2714
16 1.5 Sq.mmCU Ring/PINType Lugs Nos 1073
Total 5496
Special Terms & Conditions
1

2
3

8
9
10
11

12

13
14
15
16
17
18

19

20

21
22

23

24

25
26

27

28
29
30

31
33
Special Terms & Conditions
Construction Power shall be provided by Wabag at one place but on a chargeable basis at per DISCOMs rates.Further distributi
distribution board etc.,
Water shall be provided by Wabag.
PF & ESI to be arranged by Vendor
Site Safety is in the scope of vendor and this must be maintained meeting all requirements without any compromise.
Safety signage and caution tape and other necessary arrangement to made by contractor.

Major scope of work as a minimum covers, Identification of equipment/ materials at stores / storage yard,technical assistance
stores / storage yard, as received from manufacturer will be handed over to you at our site stores, removal of packing if any, in
designated work areas from our stores, assembly, erection / installation of various Electrical/ Instrumentation works, etc for p
along with all consumables, tools and tackles, testing as per Wabag Engineer’s Instruction / Supervision and providing assistan
shooting, trial operation of the complete equipment

Rate is inclusive of hydra/crane for shifting and erection of panels wherever applicable.
All steel works including chequered plates cutting will be done by grinder or choksa machine. All the holes to be done through
flame cut is allowed.
Two coats of primer & 2 coats of Finished paint to be done by Vendor , the paint will be provided by Wabag as free supply.
Making holes in panels thorough holesaw cutter shall be a part of glanding no additional price is allowed.
For lighting works any chipping come in brick wall will be done by vendor
Anchor fastners for supports shall be included in structural works prices. The anchor fasteners will be provided by Wabag as a
Consumables like welding electrode , gas for cutting, drill bit, grinding wheel, insulation tape, Teflon tape, hexa blade,PVC slee
tagging,including the supply of required size of cable lugs for Power and control cables , Printed ferruls,cable ties, cable tags
dressing materials such as clamps , bricks,Cement, sand excavation (for earth pit only) materials etc.
Any work not mentioned in scope of work (BOQ provided by Wabag) required to be done shall be treated as an extra works aft
Fabrication of cable tray bends shall be included in cable tray erection price.The Cable tray will be provided by Wabag as a f
Cable trench Earth excavation & back filling shall be included in cable laying price.
Vendor shall submit reconciliation statement at least once in a month or with each RA Bill for the free issue materials .
All Equipment Testing & Transformer oil filtrationto be done by vendor
All the erection procedure to be adopted based on the Wabag engineer or consultant recommendation.
Commissioning assistance including machinery and manpower shall be provided by vendor with 2 skilled manpower
for 45 days or till project completion
Vendor shall depute a dedicated qualified Site In Charge, Planning Engineer, Supervisory personnel and crew
personnel including quality control personnel’s shall be made available at site during execution.
Vendor shall furnish daily manpower / equipment report and other information as may be required.
All necessary licences / certifications as may be required to carry out the scope of work.
Construction methodology/quality assurance plan / rigging plan and necessary inspection procedures / documents shall be su
Consultant / Client for approval after award of contract within one week. Only after approval/ clearance of the above, contrac
at site.
Venor shall adopt All statutory and other compliances as per West bengal law
Inspection will be by VA Tech Wabag / Consultant Inspectors and shall have full access to contractor’s work. The work shall be
satisfaction of VA Tech Wabag / Consultant/End user.
Vendor shall perform all works as per good standard engineering practice and guidelines of the relevant IS
Vendor should arrange Personnel Protective Equipment (PPE) for crew, supervisor & Engineer engaged in the job, non complia
penalty as per company policy.
Any damages to the equipments during erection and other permanent equipments in this project, contractor shall take efforts
over to us in its original condition.
Payments shall be made for the actual quantities executed for the work done & certified by our Site engg/RCM/PM
All necessary qualified skilled / unskilled labors,Staffs etc. Adequate manpower shall be mobilized to ensure completion of the
speed up the progress.
Vendor shall ensure that all necessary test certificates shall be made available for all equipments, tools & tackles that are used
House keeping of the respective areas of work , will be in vendor scope.

You might also like