PROJECT SPECIFIC DATA

3.1. PROJECT SPECIFIC DATA


3.1.1 Name of Project MERIDA CCC Project
The site of the current C.T. Mérida II has its access through Benito Juárez Avenue (Aviación) which connects with the Mérida-Umán highway
3.1.2 Site Location
through the peripheral ring.
3.1.3 GT Type M501JAC
3.1.4 No. of GTs One (1)
SUPPLIER COMPLIANCE RESPONSE
3.2. SITE DATA REQUIREMENTS FINAL AGREEMENT
(HHITMC 2022-05-30)
Ambient Temperature, Outdoor MPW060522: Confirm Compliance.
Extreme Minimum Temperature [°F (°C)] 41 [5.0] HHITMC140622: Confirm
Extreme Maximum Temperature [°F (°C)] 113.0 [45.0] HHITMC140622: Confirm
Average year Temperature [°F (°C)] 80.24 [26.8] HHITMC140622: Confirm
Winter design Temperature [°F (°C)] 62.6 [17.0] HHITMC140622: Confirm
Summer design Temperature [°F (°C)] 98.06 [36.7] HHITMC140622: Confirm

Relative Humidity MPW060522: Confirm Compliance.


Minimum RH [%] 12% HHITMC140622: Confirm
Maximum RH [%] 98% HHITMC140622: Confirm
MPW062722: Added. Confirm Compliance.
Summer Design Humidity 36%
HHITMC062922: Confirm
MPW062722: Added. Confirm Compliance.
Annual Average Humidity 79%
HHITMC062922: Confirm

Barometric Pressure [mmHg (kPa)] 758.16 (101.08) MPW060522: Confirm Compliance.


HHITMC140622: Confirm

MPW060522: Confirm Compliance.


Site Altitude [ft (m)] [81.23 (24.76 MASL)]
HHITMC140622: Confirm

MPW062722: Added. Not Applicable To ECA


Calculation of Wind/Seismic Loads:
Compressor.
MDOC CFE-2015 Diseno Por Sismo
HHITMC062922: Confirm
Building Code - Modular MDOC CFE-2020 Diseno Por Viento
MPW070122: Revised. Not Applicable To ECA
Combination of Load Cases:
Compressor.
ASCE 7-16
HHITMC070722: Confirm
Calculation of Wind/Seismic Loads:
MPW062722: Added. Confirm Compliance.
MDOC CFE-2015 Diseno Por Sismo
HHITMC062922: Later
Building Code - Non-Modular MDOC CFE-2020 Diseno Por Viento
MPW070122: Requirement revised. Please
Combination of Load Cases:
confirme compliance.
ASCE 7-16

Occupancy Category

Precipitation MPW060522: Confirm Compliance.


Annual Average [in (mm)] 43.15 (1096.1) HHITMC140622: Confirm
24-hour Max [in (mm)] 79.88 (2029) HHITMC140622: Confirm

Wind Site Conditions Data MPW060522: Confirm Compliance.


Structural Group A1 HHITMC140622: Confirm
Regional Speed VR [km/h] 197 HHITMC140622: Confirm
Topographic Factor FT 1 HHITMC140622: Confirm
MPW062722: Added. Confirm Compliance.
Correction Factor, G 1.011
HHITMC062922: Confirm
Exposure Factor Frz 1-1.19 HHITMC140622: Confirm
Wind Speed Design. See values in wind tab for different elevations [km/h] 197-234 HHITMC140622: Confirm
MPW062722: Added. Confirm Compliance.
Dynamic Pressure, qz "WIND TABLE" Tab
HHITMC062922: Confirm

Ice Design Data


Nominal Ice Thickness, t, due to freezing rain at a height of 33ft [in (mm)] N/A
Concurrent Wind speed, Vc [mph (kph)] N/A
Importance Factor (Ice Loads - Ice Thickness), Ii N/A
Importance Factor (Ice Loads - Concurrent Wind), Iw NA

Snow Design Data


Ground Snow Load, Pg, [lb/ft2 (kgf/m2)] N/A
Importance Factor (Snow Loads), I N/A

Seismic Design Criteria

Seismic Site Conditions Data MPW060522: Confirm Compliance.


Importance Factor (IE) Group A1 HHITMC140622: Confirm
Structural group = A HHITMC140622: Confirm
Seismic zone A HHITMC140622: Confirm
Maximum rim acceleration (cm / s2): obtained from PRODISIS for Rock of MPW062722: Changed. Confirm Compliance.
110.129
the CFE of 2015 for Land Category II:= HHITMC062922: Confirm
Lower limit of the spectral plateau, Ta = 0.05 HHITMC140622: Confirm
Upper limit of the spectral plateau, Tb = 0.6 HHITMC140622: Confirm
Disintegration period, Tc = 2 HHITMC140622: Confirm
Spectral decay parameter of the second branch, r = 0.5 HHITMC140622: Confirm
Spectral decay parameter, k = 2 HHITMC140622: Confirm
Site factor F SIT = N/A MPW062722: N/A Added.
Response factor F RES = N/A MPW062722: N/A Added.
MPW062722: Added. Confirm Compliance.
Group factor / Importance factor GF = 1
HHITMC062922: Confirm
Peak acceleration to ground, a0 = 0.1123 HHITMC140622: Confirm
Maximum spectral acceleration, c = 0.3026 HHITMC140622: Confirm
Peak horizontal acceleration (assuming Q=1, R0 = 1.25, p = 1.0; these
parameters are dependent on the type of structures being designed and are to be 0.242g HHITMC140622: Confirm
determined by the designer).
Peak vertical acceleration (assuming Q=1, R0 = 1.25, p = 1.0; these parameters HHITMC140622: Confirm
are dependent on the type of structures being designed and are to be determined 0.187g MPW062722: Changed. Confirm Compliance.
by the designer). HHITMC062922: Confirm

Seismic conditions for HRSG (in addition to above or where conflict exists HRSG specific value prevales) MPW060522: Not Applicable To ECA Compressor.
HHITMC140622: Confirm (HHITMC062922:
Effective Shear Wave Propagation Rate, Vs(m/s) 372.09
Delete)
HHITMC140622: Confirm (HHITMC062922:
Period of Dominance at the Site, Ts( sec) 0.43
Delete)
HHITMC140622: Confirm (HHITMC062922:
Response Factor, Fr= 3.571
Delete)
HHITMC140622: Confirm (HHITMC062922:
Site Factor, Fs= 1.75
Delete)
3.3. GENERAL TECHNICAL REQUIREMENTS REQUIREMENTS FINAL AGREEMENT

© All Rights Reserved, Confidential Proprietary


LS-03927-R0 Mitsubishi Power Americas, Inc. Page 1 of 3
3. PROJECT SPECIFIC DATA

Documentation to be submitted in English for


Mitsubishi Power Review, Documents as (HHITMC)
identified in the project and vendor MDL shall be
dual language (english/spanish) or final HHITMC follow as below (4.6.B)
drawings resubmitted again in spanish. (OPTION PRICE)
Communication and site services with end user
Language
(if any) will be in spanish. Vendor to provide option price for dual
The Contractor must prepare and submit in language (english/spanish) MDL Item#s
Spanish the Plant Manual and the Operation 3,9,33,36,43,44,45 in Tab.6 MDL.
and Maintenance Manual described in Annex 5
of the Agreement, both manuals to the MPW060522: Noted.
satisfaction of the Contracting Party.

Design: Metric units shall be the presiding units


for engineering design.
HHITMC140622: Confirm
Units of Measurement Reference: Dual units (SI and US) COULD be
MPW060522: Confirm Compliance.
provided within design documentation for
reference.

Mitsubishi Standard (based on KKS code) as


provided by Mitsubishi via this specification, unit
HHITMC140622: Confirm
Tagging Sequence numbering as follows:
MPW060522: Confirm Compliance.
- All tags to have prefix “**” as follows:
“11” for Unit #1

Area Classification

Noise:

The combined sound pressure level (SPL)


Sound pressure level of equipment being provided for the Project shall not exceed XX dBA
measured at awhen measured
height at theand
of 5ft [1.5m] locations specified
3 ft [1m] Yes below:
from any surface shall not exceed 85 dBA.

Compressors, Pumps, Speed Reducers, Engines


Fans and Blowers
Control Valves
Vents, Silencers, Intakes, Exhausts
Other Equipment - General Requirement

Electrical Power Requirements


Low Voltage, 3 Phase (Power)
Nom 480 VAC HHITMC140622: Confirm
Source Voltage [Volts]
Max Refer to "ANCE" tab MPW060522: Confirm Compliance.
Min Refer to "ANCE" tab
Low Voltage, 1 Phase (Power)
Nom Refer to "ANCE" tab HHITMC140622: Confirm
Max Refer to "ANCE" tab MPW060522: Confirm Compliance.
Min Refer to "ANCE" tab
DC Control Power
Nom 125 VDC
HHITMC140622: Confirm
Max 140 VDC
Min 105 VDC
AC Control Power
Nom 127
HHITMC140622: Confirm
Max Refer to "ANCE" tab
Min Refer to "ANCE" tab
HHITMC140622: Confirm
Motors >250 HP [Volts/Ph] 6600V/3
MPW060522: Confirm Compliance.
HHITMC140622: Confirm
Motors 1/2 to 250 HP [Volts/Ph] 460V, 3P
MPW060522: Confirm Compliance.
Motors smaller than 1/2 HP [Volts/Ph] 120/127V, 1P HHITMC140622: Confirm
Nom: 125VDC
D.C. Motors [Volts] Min: 100VDC HHITMC140622: Confirm
Max: 140VDC
MPW060522: Control External Power is
Control External Power [Volts/Ph] 127 VAC, 120V (UPS)
not applicable to ECA Compressor
HHITMC140622: Confirm
Control & Instrumentation Control Signals [Volts/Ph] 24 VDC, Analog 4-20mA
MPW060522: Confirm Compliance.
HHITMC140622: Confirm
Normal Lighting [Volts/Ph] 127VAC/1
MPW060522: Confirm Compliance.
HHITMC140622: Confirm
Frequency [Hz] 60 (Nominal)
MPW060522: Confirm Compliance.

Utility Supply
Cooling Water Requirements MPW060522: Confirm Compliance.
Type Treated Demineralized Water HHITMC140622: Confirm
Max Supply Temperature for Heat Exchanger Sizing [°F (°C)][122 (50)] HHITMC140622: Confirm
Mechanical Design Temperature [°F (°C)] [165.2 (74)] HHITMC140622: Confirm
Minimum Supply Temperature [°F (°C)] [50 (10)] HHITMC140622: Confirm
Mechanical Design Pressure [psig (MPag)] [150 (1.03)] HHITMC140622: Confirm
Instrument Air Requirements MPW060522: Confirm Compliance.
Mechanical Design Temperature [°F (°C)] [140 (60)] HHITMC140622: Confirm
Mechanical Design Pressure [psig (MPag)] 145 [1] HHITMC140622: Confirm
Maximum Operating Pressure [psig (MPag)] HOLD
Normal Operating Pressure [psig (MPag)] 100 [0.69] HHITMC140622: Confirm
Normal Operating Temperature [°F (°C)] More than 41 degF HHITMC140622: Confirm
80air
Minimum Supply Pressure to be used for sizing (i.e. instrument [0.55]
actuators) HHITMC140622: Confirm
Minimum Supply Pressure [psig (MPag)] 80 [0.55] HHITMC140622: Confirm
Instrument Air Dew Point [°F (°C)] [-40 (-40)] HHITMC140622: Confirm

3.4. SPECIAL REQUIREMENTS


Pressure vessel list and calculation per NOM- HHITMC140622: Confirm
List if any
020 MPW060522: Confirm Compliance.
CENACE Grid Code HHITMC140622: Confirm
3.5. PROJECT OPERATIONAL CRITERIA REQUIREMENTS
Plant Minimum Useful Life (Years) 30 HHITMC140622: Confirm
Plant Projected Service Hours / year
Plant Number of cold starts per year 12 (Combined - The worst startup scenario HHITMC140622: Confirm
Plant Number of warm starts per year should be taken into consideration for all HHITMC140622: Confirm
Plant Number of hot starts per year equipment design) HHITMC140622: Confirm
HHITMC140622: Confirm
Individual Equipment Availability > %95
MPW060522: Confirm Compliance.

3.6. CODES AND STANDARDS

All Mexican national and local laws and Codes


shall govern, including but not limited to:
List if any - NOM: All applicable. Yes
- NMX: All applicable.
- CENACE: All applicable.