TCD220015AA Safety Considerations


• Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
• ᜸ symbol indicates caution due to special circumstances in which hazards may occur.

᜸ Warning Failure to follow instructions may result in serious injury or death.

01. Fail-safe device must be installed when using the unit with machinery that
may cause serious injury or substantial economic loss. (e.g. nuclear power
control, medical equipment, ships, vehicles, railways, aircraft, combustion
apparatus, safety equipment, crime / disaster prevention devices, etc.)
Failure to follow this instruction may result in personal injury, economic loss or fire.

4-Digit Multi Panel Meters


02. Do not use the unit in the place where flammable / explosive / corrosive gas,
high humidity, direct sunlight, radiant heat, vibration, impact or salinity
may be present.
Failure to follow this instruction may result in explosion or fire.
03. Install on a device panel to use.
Failure to follow this instruction may result in fire or electric shock.
04. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in fire or electric shock.
05. Check ‘Connections’ before wiring.
Failure to follow this instruction may result in fire.
06. Do not disassemble or modify the unit.
Failure to follow this instruction may result in fire or electric shock.

᜸ Caution Failure to follow instructions may result in injury or product damage.

01. When connecting the power / measurement input and relay output, use
AWG 24 (0.20 mm2) to AWG 15 (1.65 mm2)cable or over and tighten the
terminal screw with a tightening torque of 0.98 to 1.18 N m.
Use the wiring suitable for the load current capacity.
Failure to follow this instruction may result in fire or malfunction due to contact
failure.
02. Use the unit within the rated specifications.
Failure to follow this instruction may result in fire or product damage.
03. Use a dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in fire or electric shock.
04. Keep the product away from metal chip, dust, and wire residue which flow
into the unit.
Failure to follow this instruction may result in fire or product damage.

Cautions during Use


• Follow instructions in ‘Cautions during Use’.
Otherwise, It may cause unexpected accidents.
• Power supply should be insulated and limited voltage / current or Class 2, SELV power
supply device.
• Install a power switch or circuit breaker in the easily accessible place for supplying or

MT4W Series
disconnecting the power.
• Use twisted pair wire for communication line.
• Keep away from high voltage lines or power lines to prevent inductive noise.

PRODUCT MANUAL
In case installing power line and input signal line closely, use line filter or varistor at
power line and shielded wire at input signal line.
Do not use near the equipment which generates strong magnetic force or high
frequency noise.
Connection with the line filter Connection with the varistor
For your safety, read and follow the considerations written in the instruction Install the line filter
close to the panel meter Panel meter
manual, other manuals and Autonics website. Panel meter
HI
The specifications, dimensions, etc. are subject to change without notice for product HI 110 / 220 VACᜠ
110 / 220 VACᜠ LOW
improvement. Some models may be discontinued without notice. LOW

Earth ground
• This unit may be used in the following environments.
- Indoors (in the environment condition rated in ‘Specifications’)
- Altitude max. 2,000 m
Features - Pollution degree 2
- Installation category II
• Various input / output options (by model)
- Input options: DC voltage, DC current, AC voltage, AC current
- Output options: RS485 communication output, low speed serial output,
BCD dynamic output, transmission output (DC 4 - 20 mA),
NPN / PNP open collector output,
relay contact output (default option: indicator / no output)
• Maximum allowed input: 500 VDCᜡ, DC 5 A, 500 VACᜠ, AC 5 A
• Display range: -1999 to 9999
• High / low-limit display scale function
• AC frequency measurement (range: 0.1 to 9999 Hz)
• Various functions: p
 eak display value monitoring, display cycle delay,
zero-point adjustment, peak display value correction,
PV transmission output (DC 4 - 20 mA) scale, etc.
• Power supply: 12 - 24 VDCᜡ, 100 - 240 VACᜠ
• DIN W 72 × H 36 mm

ᜢᜧᜫ
-|Transparent Guide|-

Ordering Information Cautions during Wiring


This is only for reference, the actual product does not support all combinations. Use the Copper-conductor wire with the temperature class 60 ℃.
For selecting the specified model, follow the Autonics website. • Unit: mm, Use terminals of size • Contact the manufacture for the socket and
specified below. cable.
MT 4 W - ❶ - ❷ ❸ Model
Hirose connector HIF3BA-20PA-2.54DS
❶ Input type ❷ Power supply Hirose connector socket HIF3BA-20D-2.54R
DV: DC voltage 01) 1: 12 - 24 VDCᜡ ± 10 % 2 20
DA: DC current 4: 100 - 240 VACᜠ ± 10 % 50 / 60 Hz ≥3.5
AV: AC voltage 02) ≤7.0
AA: AC current 02) 19
❸ Preset output + Sub output 1

Preset output Sub output


N None (indicator) Connections
0 Relay Transmission (DC 4 - 20 mA) ■ Input
1 Relay - • DC voltage • DC current
2 NPN open collector BCD Dynamic SOURCE SOURCE
12 - 24 VDCᜡ 5 W 12 - 24 VDCᜡ 5 W
3 PNP open collector BCD Dynamic 100 - 240 VACᜠ 100 - 240 VACᜠ
4 NPN open collector Transmission (DC 4 - 20 mA) 50 / 60 Hz 5 VA 50 / 60 Hz 5 VA

5 PNP open collector Transmission (DC 4 - 20 mA) HOLD / ZERO HOLD / ZERO

6 NPN open collector Low speed serial


1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
7 PNP open collector Low speed serial
8 NPN open collector RS485 Communication 250 mVDCᜡ / 50 mVDCᜡ 5 mA / 2 mA
5 VDCᜡ / 1 VDCᜡ 50 mA / 4 - 20 mA
9 PNP open collector RS485 Communication 50 VDCᜡ / 10 VDCᜡ 500 mA / 200 mA
01) To measure the current over DC 5 A, please select DV type because the shunt should be used. 500 VDCᜡ / 100 VDCᜡ 5A/2A
COM COM
02) In case of selecting frequency display, no output will be provided even if it is output support model.
• AC voltage • AC current
SOURCE SOURCE
12 - 24 VDCᜡ 5 W 12 - 24 VDCᜡ 5 W
Product Components 100 - 240 VACᜠ 100 - 240 VACᜠ
50 / 60 Hz 5 VA 50 / 60 Hz 5 VA
• Product • Instruction manual HOLD / ZERO HOLD / ZERO
• Bracket × 2 • Unit sticker × 1
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9

Manual
2 VACᜠ / 1 VACᜠ 100 mA / 50 mA
20 VACᜠ / 10 VACᜠ 500 mA / 250 mA
110 VACᜠ / 50 VACᜠ 1A
For proper use of the product, refer to the manuals and be sure to follow the safety 500 VACᜠ / 250 VACᜠ 5 A / 2.5 A
COM COM
considerations in the manuals.
Download the manuals from the Autonics website. ■ Output
• 0: Relay + Transmission (DC 4 - 20 mA) • 1: Relay
Main OUT Main OUT
Contact OUT: 250 VACᜠ 3A 1a DC 4 - 20 mA Contact OUT: 250 VACᜠ 3A 1a
Software resistive load Load 600 Ω Max. resistive load
10 11 12 13 14 15 10 11 12 13 14 15
Download the installation file and the manuals from the Autonics website.
■ DAQMaster HI GO LO COM
mA HI GO LO
It is the comprehensive device management program for Autonics' products, providing
• 2: NPN open collector + BCD Dynamic • 3: PNP open collector + BCD Dynamic
parameter setting, monitoring and data management. Main OUT: PNP open collector
Main OUT: NPN open collector
12 - 24 VDCᜡ Max. 50 mA 12 - 24 VDCᜡ Max. 50 mA
B D D1 D3 DOTCOM2 B D D1 D3 DOTCOM2

Dimensions 2 4 6 8 10 12 14 16 18 20 2 4 6 8 10 12 14 16 18 20

GO +24 VDCᜡ GO +24 VDCᜡ


• Unit: mm, For the detailed drawings, follow the Autonics website. 30mA Max. BCD OUT 30mA Max. BCD OUT
(NPN open collector) (PNP open collector)
12 - 24 VDCᜡ Max. 50 mA
■ Indicator / Relay preset output model
12 - 24 VDCᜡ Max. 50 mA
0V 0V
1 3 5 7 9 11 13 15 17 19 1 3 5 7 9 11 13 15 17 19
96 6 100
COM1 HI LO A C D0 D2 POL COM1 HI LO A C D0 D2 POL
• 4: N
 PN open collector + • 5: PNP open collector +
Transmission (DC 4 - 20 mA) Transmission (DC 4 - 20 mA)
Main OUT: NPN open collector Main OUT: PNP open collector
12 - 24 VDCᜡ Max. 50 mA 12 - 24 VDCᜡ Max. 50 mA
45
48

2 4 6 8 10 12 14 16 18 20 2 4 6 8 10 12 14 16 18 20
+24 VDCᜡ - +24 VDCᜡ -
■ NPN / PNP open collector preset output model
GO GO
30mA Max. DC 4 - 20 mA 30mA Max. DC 4 - 20 mA
Load 600 Ω Max. Load 600 Ω Max.
96 6 89.5 14.9
0V + 0V +
1 3 5 7 9 11 13 15 17 19 1 3 5 7 9 11 13 15 17 19
COM1 HI LO COM1 HI LO
• 6: NPN open collector + Low speed serial • 7: PNP open collector + Low speed serial
Main OUT: NPN open collector Main OUT: PNP open collector
45
48

12 - 24 VDCᜡ Max. 50 mA 12 - 24 VDCᜡ Max. 50 mA


POL CLOCK LATCH POL CLOCK LATCH
2 4 6 8 10 12 14 16 18 20 2 4 6 8 10 12 14 16 18 20
■ Bracket ■ Panel cut-out GO +24 VDCᜡ GO +24 VDCᜡ
≥ 116 30mA Max. Serial OUT 30mA Max. Serial OUT
(NPN open collector) (NPN open collector)
4.4

12 - 24 VDCᜡ Max. 50 mA 12 - 24 VDCᜡ Max. 50 mA


0V 0V
10

1 3 5 7 9 11 13 15 17 19 1 3 5 7 9 11 13 15 17 19
73
45+0.6
0

COM1 HI LO COM2 DATA COM1 HI LO COM2 DATA


≥ 52

92+0.8 • 8: NPN open collector + RS485 Comm. • 9: PNP open collector + RS485 Comm.
14.5
12

Main OUT: NPN open collector Main OUT: PNP open collector
0

12 - 24 VDCᜡ Max. 50 mA 12 - 24 VDCᜡ Max. 50 mA

2 4 6 8 10 12 14 16 18 20 2 4 6 8 10 12 14 16 18 20
GO +24 VDCᜡ B (-) SG GO +24 VDCᜡ B (-) SG
30mA Max. 30mA Max.
RS485 RS485
0V A (+) SG 0V A (+) SG
1 3 5 7 9 11 13 15 17 19 1 3 5 7 9 11 13 15 17 19
COM1 HI LO COM1 HI LO
-|Transparent Guide|-

Specifications Mode Setting


Model MT4W-DV-□□ MT4W-DA-□□ MT4W-AV-□□ MT4W-AA-□□
Parameter 1
Input type DC voltage DC current AC voltage 01) AC current 01) [MODE] 3 sec → [MODE] 3 sec →
group
Max. allowable input 110 % F.S. for each measured input range
Display method 7-segment (red) LED (character height: 14.2 mm) Parameter 2
[MODE] 5 sec → [MODE] 3 sec →
Display accuracy Dependent on the ambient temperature group
± 0.1 % F.S. rdg ± 0.1 % F.S. rdg ± 0.3 % F.S. rdg ± 0.3 % F.S. rdg
23 ± 5 ℃ RUN Parameter 0 RUN
± 2 digit ± 2 digit 02) ± 3 digit ± 3 digit [MODE] → [MODE] 3 sec →
group
-10 to 50 ℃ ± 0.5 % F.S. rdg ± 3 digit
Max. display range -1999 to 9999 (4 digit) [◀] + [▲] 3 sec → Zero adjustment Auto →
A / D conversion
ΣΔ (Sigma Delta) ADC
method
[◀] + [▲] + [▼] 5 sec → Reset [MODE] →
Sampling cycle 50 ms 16.6 ms
Unit weight
≈ 211 g (≈ 326 g)
(packaged)

Parameter Setting
Approval ᜢ ᜧ 03) ᜫ
01) Available frequency display, Display accuracy (23 ± 5 ℃): ± 0.1 % F.S. rdg ± 2 digit
02) 5 A terminal: ± 0.3 % F.S. rdg ± 3 digit
• Some parameters are activated / deactivated depending on the model or setting of
03) Except p ower supply 12 - 24 VDCᜡ model
other parameters. Refer to the description of each parameter.
• If any key is not entered for 60 sec in each parameter, it returns to RUN mode.
None (indicator) / Relay / NPN open collector / PNP open collector
Preset output
output model • After returning to RUN mode, press the [MODE] key within 2 sec, it returns to
previous parameter.
Contact capacity: 250 VACᜠ 3 A, 30 VDCᜡ 3 A • [MODE] key: Saves current setting value and moves to the next parameter.
Relay
Contact composition: N.O (1a)
[◀] key: Checks fixed value / Changes setting digits.
NPN / PNP [▲], [▼] key: Changes setting values.
Output capacity: ≤ 12 - 24 VDCᜡ ± 2 VDCᜡ, 50 mA resistive load
open collector
None (indicator) / BCD Dynamic / Transmission (DC 4 - 20 mA) / ■ Parameter 1 group
Sub output
Low speed serial / RS485 Communication output model Display
Parameter Mark Defaults Setting range
BCD Dynamic / NPN open collector output condition
Low speed serial Output capacity: ≤ 12 - 24 VDCᜡ, 50 mA resistive load [DC voltage model], [AC voltage model]
-
Transmission Resolution: 1/12,000 (load resistance: ≤ 600 Ω) • Refer to Input Range and Display Range
500V
1-1 Input range
(DC 4 - 20 mA) Response time: ≤ 450 ms [DC current model], [AC current model]
IN-R
-
RS485 communication Protocol: Modbus RTU • Refer to Input Range and Display Range
5A

Display STND: standard, SCAL: scale, FREQ:


1-2 -
Model MT4W-□□-1□ MT4W-□□-4□ method frequency 01)
DISP STND

100 - 240 VACᜠ ± 10 % 50 / 60 [AC voltage model], [AC current model]


Power supply 12 - 24 VDCᜡ ± 10 %
Hz T.RMS: True RMS, A.RMS: Average RMS,
Power consumption 5W 5 VA AVG
1-2
A 2 + A22 + ··· + An2
Insulation resistance Between external terminal and case: ≥ 100 MΩ (500 VDCᜡ megger) • True RMS = 1 Display
Measurement n
1-3 method:
Dielectric strength Between external terminal and case: 2,000 VACᜠ 50 / 60 Hz for 1 min method A + A2 + ··· + An
IN-T tRMS
• Average RMS =  1 STND,
Noise immunity ± 2 kV square wave noise (pulse width: 1 ㎲) by the noise simulator n SCAL
× Waveform rate
0.75 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) in (n = number of display values ​​per cycle,
Vibration
each X, Y, Z direction for 2 hours A = display value)
Vibration 0.5 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) in [DC voltage model], [AC voltage model]
(malfunction) each X, Y, Z direction for 10 min Max. display 50)0
Max. value of display range
Shock 300 m/s2 (≈ 30 G) in each X, Y, Z direction for 3 times 1-4 value
[DC current model], [AC current model]
STND
(fixed)
Shock (malfunction) 100 m/s2 (≈ 10 G) in each X, Y, Z direction for 3 times Max. value of display range
%000

Mechanical: ≥ 20,000,000 operations High-limit 1-2


Relay life cycle Display
Electrical: ≥ 100,000 operations (250 VACᜠ 3A resistive load) display value
1-5 !000 0.100 to 5.000 % method:
gradient
INbH
Ambient temp. -10 to 50 ℃, storage: -20 to 60 ℃ (freezing or condensation) STND
correction
Ambient humi. 35 to 85 %RH, storage: 35 to 85 %RH (freezing or condensation)
Low-limit
Symbol: , double or reinforced insulation (dielectric strength between display value
Insulation type 1-6 00 -99 to 99
the measurement input part and the power part: 1 kV) deviation
INbL
correction
[DC voltage model], [AC voltage model]
Decimal
Communication Interface 0, 0.0, 0.00, 0.000
)0
1-7 point
[DC current model], [AC current model]
1-2
DOT
position
■ RS485 0, 0.0, 0.00, 0.000 Display
)000

1-8 High-limit scale H-SC - Display value against max. measurement input* method:
Comm. protocol Modbus RTU SCAL
1-9 Low-limit scale L-SC - Display value against min. measurement input* &
Application standard Compliance with EIA RS485
High-limit * 1-7
Max. connection 31 units (address: 01 to 99) display value Decimal
1-10 !000 0.100 to 5.000 %
Comm. synchronous method Asynchronous gradient point
INbH
correction position:
Comm. method 2-wire half duplex
0.0, 0.00,
Comm. distance ≤ 800 m Low-limit
0.000
display value
Comm. speed 1,200 / 1,400 / 4,800 / 9,600 / 19,200 / 38,400 bps 1-11 00 -99 to 99
deviation
INbL
Start bit 1-bit (fixed) correction 02)
Data bit 8-bit (fixed) [AC voltage model]
Decimal )0
0, 0.0, 0.00, 0.000
Parity bit None, Even, Odd 1-12 point
[AC current model]
DOT
Stop bit 1-bit, 2-bit position 03)
0, 0.0, 0.00, 0.000 1-2
)000
EEPROM life cycle ≈ 1,000,000 operations (Erase / Write) Display
High-limit
display value method:
1-13 !000 0.100 to 9.999 FREQ
gradient
INbH
correction
Exponent of
1-14 10-0 10-0: 100, 10-1: 10-1, 10-2: 10-2, 10 1: 101
INB
INbE

01) Displays at AC voltage or AC current model only.


02) Low-limit display value deviation correction range is within -99 to 99 for D0, D-1 digit regardless of decimal point position.
03) Display range is variable according to decimal point position.
Dot Display range Frequency measurement range
0 -1999 to 9999 1 to 9999 Hz
)0 -199.9 to 999.9 0.1 to 999.9 Hz
)00 -19.99 to 99.99 0.10 to 99.99 Hz
)000 -1.999 to 9.999 0.100 to 9.999 Hz
-|Transparent Guide|-

■ Parameter 2 group Input Range and Display Range


Display When the max. input value is over the 100 %, it may result in input terminal damage.
Parameter Mark Defaults Setting range
condition
[Except indicator model] ■ DC voltage model
Output
OFF, L.ST, H.ST, LH.ST, HH.ST, LL.ST, Display range
2-1 operation - Input
LD.ST Input range
OUtT OFF
mode Diaplay method: STND (fixed) Diaplay method: SCAL 01) impedance
• Refer to Output Operation Mode
0 - 500 VDCᜡ 0.0 to 500.0 4.33348 MΩ
2-1
500V
Output 0 - 100 VDCᜡ 0.0 to 100.0 4.33348 MΩ
Decimals Display range
100V
[Except indicator model] operation 0 - 50 VDCᜡ 0.00 to 50.00 433.48 kΩ
2-2 Hysteresis 0 -1999 to 9999
Within 10 % of max. display range, digit mode:
HYS 001 50V
0 - 10 VDCᜡ 0.00 to 10.00 433.48 kΩ
except )0 -199.9 to 999.9
10V
OFF 0 - 5 VDCᜡ 0.000 to 5.000 43.48 kΩ
)00 -19.99 to 99.99
5V

Startup 0 - 1 VDCᜡ 0.000 to 1.000 43.48 kΩ


[Except indicator model] )000 -1.999 to 9.999
1V
2-3 compensation - 0 - 250 mVDCᜡ 0.0 to 250.0 2.28 kΩ
0.0 to 99.9 sec
STaT 0)0 )25V
time 0 - 50 mVDCᜡ 0.00 to 50.00 50MV 2.28 kΩ
Peak 01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input
2-4 monitoring PEkT 00 S 00 to 30 sec - range to measure.
delay time When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
2-5 Display cycle )2 S 0.1 to 5.0 sec -
DIsT
■ DC current model
NO, YES
Keys for zero Display range Input
2-6 NO • YES: Press the [◀] + [▲] keys for 3 - Input range
adjustment
ZERO
sec to adjust zero. Diaplay method: STND (fixed) Diaplay method: SCAL 01) impedance

[Except indicator model] 0-5A 0.000 to 5.000 5A 0.022 Ω


External HOLD, ZERO 0-2A 0.000 to 2.000 0.022 Ω
2-7 input HOLD • If the external input terminal is - Decimals Display range
2A
0 - 500 mA 0.0 to 500.0 0.222 Ω
EVLN
terminal short-circuited for 50 ms or more, it 0 -1999 to 9999
)5A
operates with the set function. 0 - 200 mA 0.0 to 200.0 0.222 Ω
)0 -199.9 to 999.9
)2A
[DC voltage & Transmission (DC 4 - 20 0 - 50 mA 0.00 to 50.00 2.222 Ω
)00 -19.99 to 99.99
50MA
mA) output model], 4 - 20 mA 4.00 to 20.00 2.222 Ω
50)0 [AC voltage & Transmission (DC 4 - 20 )000 -1.999 to 9.999
4-20
0 - 5 mA 0.000 to 5.000 22.222 Ω
High-limit mA) output model]
5MA

Max. value of display range 0 - 2 mA 0.000 to 2.000 22.222 Ω


value of
2-8 -
2MA
transmission [DC current & Transmission (DC 4 - 20 01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input
FS-H
output mA) output model], range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
%000 [AC current & Transmission (DC 4 - 20
mA) output model] ■ AC voltage model
Max. value of display range
Display range Input
[DC voltage & Transmission (DC 4 - 20 Input range
Diaplay method: STND (fixed) Diaplay method: SCAL impedance
mA) output model],
01)

00)0 [AC voltage & Transmission (DC 4 - 20 0 - 500 VACᜠ 0.0 to 500.0 5.01092 MΩ
mA) output model]
500V
Low-limit 0 - 250 VACᜠ 0.0 to 250.0 5.01092 MΩ
value of Min. value of display range Decimals Display range
250V
2-9 - 0 - 110 VACᜠ 02) 0.0 to 440.0 1.11092 MΩ
transmission [DC current & Transmission (DC 4 - 20 0 -1999 to 9999
FS-L 110P
output mA) output model], 0 - 50 VACᜠ 0.00 to 50.00 1.11092 MΩ
)0 -199.9 to 999.9
50V
)000 [AC current & Transmission (DC 4 - 20 0 - 20 VACᜠ 0.00 to 20.00 200.92 kΩ
)00 -19.99 to 99.99
20V
mA) output model] 0 - 10 VACᜠ 0.00 to 10.00 200.92 kΩ
Min. value of display range )000 -1.999 to 9.999
10V
0 - 2 VACᜠ 0.000 to 2.000 20.92 kΩ
Comm. [RS485 Comm. output model]
2V
2-10 - 0 - 1 VACᜠ 0.000 to 1.000 20.92 kΩ
Address 01 to 99
ADRS 01 1V
01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input
Comm. [RS485 Comm. output model]
2-11 - range to measure.
speed 38.4k, 19.2k, 9600, 4800, 2400, 1200 bps
BPS 9600
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
[RS485 Comm. output model] 02) In case of 0 to 110 VACᜠ of AC voltage range and using P.T (potential transformer) for 440 VACᜠ / 110 VACᜠ, if
2-12 Parity bit - 110 VACᜠ is input, and the unit displays 440 VACᜠ automatically by preset scale value for P.T user’s convenient.
NONE, EVEN, ODD
PRTY NONE

2-13 Stop bit


[RS485 Comm. output model]
- ■ AC current model
2, 1 bit
STP 2
Display range Input
Response [RS485 Comm. output model] Input range
2-14 - Diaplay method: STND (fixed) Diaplay method: SCAL 01) impedance
waiting time 5 to 99 sec
RSwT 5
0-5A 0.000 to 5.000 0.02 Ω
OFF: unlock,
5A
LOC1: lock parameter 1, 0 - 2.5 A 0.000 to 2.500 Decimals Display range 0.02 Ω
2-15 Lock -
@5A
LOC2: lock parameter 1, 2, 0-1A 0.000 to 1.000 0 -1999 to 9999 0.102 Ω
LOC OFF
LOC3: lock parameter 0, 1 and 2
1A
0 - 500 mA 0.0 to 500.0 )5A )0 -199.9 to 999.9 0.202 Ω

■ Parameter 0 group 0 - 250 mA 0.0 to 250.0 )25A )00 -19.99 to 99.99 0.202 Ω
0 - 100 mA 0.0 to 100.0 )000 -1.999 to 9.999 1.022 Ω
Display
)1A
Parameter Mark Defaults Setting range 0 - 50 mA 0.00 to 50.00 1.022 Ω
condition 50MA

[DC voltage & Preset setting model] 01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input
range to measure.
-5 to 110 % of display range 2-1 When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
[AC voltage & Preset setting model] Output
50)0
Output high- 0 to 110 % of display range operation
0-1 limit output
[DC current & Preset setting model] mode:
hSET
setting value
-5 to 110 % of display range except
%000
[AC current & Preset setting model] OFF
0 to 110 % of display range
[DC voltage & Preset setting model]
-5 to 110 % of display range 2-1
[AC voltage & Preset setting model] Output
00)0
Output low- 0 to 110 % of display range operation
0-2 limit output
[DC current & Preset setting model] mode:
lSET
setting value
-5 to 110 % of display range except
)000
[AC current & Preset setting model] OFF
0 to 110 % of display range
[DC voltage], [AC voltage] 2-1
Max. peak value in run mode Output
Display max.
)0
0-3 operation
peak value 01) [DC current], [AC current] mode:
hPEK
)000
Max. peak value in run mode except
OFF
[DC voltage], [AC voltage] &
Display min. Min. peak value in run mode 2-4 Peak
)0
0-4 monitoring
peak value 01) [DC current], [AC current]
lPEK
delay time:
Min. peak value in run mode except 00
)000

01) Reset: Press any one of [◀], [▼], [▲] keys.


-|Transparent Guide|-

Output Operation Mode Time Chart


• H.SET or L.SET is displayed according to the output operation mode setting. In case of output ■ Low speed serial output (negative logic)
operation mode as OFF, H.SET and L.SET are not displayed.
• When changing output operation mode, high-limit / low-limit output setting value, hysteresis It outputs current display value as Low-frequency (50 Hz) type.
are reset.
[Clock frequency: 50 Hz]
tw t: 20 ms
Preset output
MODE Output operation ta: 0.05 ms
LO ON HI ON GO ON tw: 5 ms
Latch tb: 4.95 ms
H.SET ON
t ta tb
OFF H
L.SET
H: Hysteresis
Clock Cn-1 Cn C1
OFF No output
GO L.SET ≥ L.SET <
- Data Dn-1 Dn D1
LO H Display value Display value
lST

HI H H.SET ≤ H.SET > Output


- 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 2
GO Display value Display value ordering
hST
DP D C B A DP D C B A DP D C B A DP D C B A DP D
HI H Clock
L.SET <
L.SET ≥ H.SET ≤
GO Display value
Display value Display value
LhST
< H.SET Data H H L H H H H H L L L H H L H H H H H L
LO H
tw
HI H ta tb
L.SET ≤ H.SET ≤ L.SET >
GO Latch
Display value Display value Display value
HhST
LO H
Display
HI H 4 3 @ 1
GO
L.SET ≥ H.SET ≥ H.SET <
Display value Display value Display value ■ BCD Dynamic output (negative logic)
LlST
LO H
It outputs display value as BCD code.
GO Second L.SET
L.SET < t
≥ Display -
H Display value t: 7.8 ms
LdST
LO value ta tw tb ta: 0.5 ms
tw: 5 ms
tb: 2.3 ms
Digit signal

Reset
Output data Data
01. Press the [◀] + [▲] + [▼] keys for over 5 sec. in run mode, INIT flashes for 0.5
sec. 31.2 ms
02. Press the direction keys to flash NO for 0.5 sec in turn.
03. Change the setting value as YES by pressing the direction keys. D3
04. Press the [MODE] key to reset all parameter values as default and to return D2
to run mode. Digit
D1

D0
Error
A H L H L H
Error display is released automatically when it is in the measured and display range.
Display Description Troubleshooting B H L L H H
Flashes when measurement input is exceeded the
max. allowable input (110 %) Disconnect power supply Data C L H H H H
HHHH

Flashes when measurement input is exceeded the and check the cables.
LLLL 01)
min. allowable input (-10 %) D H H H H H
Turns ON when display input is exceeded high-limit
scale setting value or max. display range (9999) Reset within the display dot H H L H H
D-HH

Turns ON when display input is exceeded low-limit range.


Display
scale setting value or min. display range (-1999) 4 3 @ 1
D-LL

Turns ON when input frequency is exceeded the


-
max. display value of measured range
F-HH

Flashes twice when it exceeds zero range (±99)


Reset within the zero range.
and returns to run mode
OVER

01) Displays at DC input model only.


-|Transparent Guide|- -

Function Description ■ Transmission (DC 4 - 20 mA) output scale adjustment


It sets transmission output for the display value at the output current DC 4 - 20 mA.
■ Display method: frequency It sets display value for 4 mA at low-limit value of transmission output and 20 mA at high-limit
It measures input signal frequency when it is AC input. value of transmission output.
In order to measure frequency normally, input signal, over 10 % F.S. of the rated input range, • The range between high-limit value of transmission output and low-limit value of
should be supplied. transmission output should be 10 %.
Otherwise, it may not be measured normally. When min. set interval under 10 % F.S., it changed as over 10 % F.S. automatically.
The measurement range differs depending on the decimal point position. • Preset display value is fixed to output as 4 mA at under low-limit value of transmission output
It is available to adjust the high-limit display value gradient correction and exponent of INB at and 20 mA at over high-limit value of transmission output.
parameter setting. Output
• Accuracy of frequency measurement: below 1 kHz, F.S. ± 0.1 % rdg ± 2-digit, 20 mA
from 1 k to 10 kHz, F.S. ± 0.3 % rdg ± 2-digit

■ High-limit display value gradient correction


This function is to correct a gradient of High / Low-limit scale value. 4 mA Min. setting range
And also can be used as correction function of high-limit scale value.
F.S. 10 %
Adjustment range is setting value and multiply current gradient. Display value
• E.g.: To display 3.000 when 200 mVDC for input range 0-1 VDC Low-limit value High-limit value
of transmission of transmission
H-SC L-SC INB.H Result output output
15.000
- 0.000 1.000 Disable
12.000
7.500 0.000 2.000
Display value

9.000
5.000 0.000 3.000 200 mVDCᜡ
Segment Table
6.000 = 3.000
3.750 0.000 4.000
Display value for The segments displayed on the product indicate the following meanings. It may differ
3.000 measuring input 3.000 0.000 5.000
depending on the product.
1.000
0.2 0.4 0.6 0.8 1V 7 segment 11 segment 12 segment 16 segment
Input value 0 0 I I 0 0 I I 0 0 I I 0 0 I I
1. Select input range = 1V, decimal point position = 0.000 for measurement input in Parameter 1. 1 1 J J 1 1 J J 1 1 J J 1 1 J J
2. It has to be 15.000 at high-limit scale for 1 VDCᜡ in order to display 3.000 for 200 mVDCᜡ. 2 K 2 2 K K 2 K 2 K
But if is disable due to setting range is 9.999.
2 K 2 K 2 K

3. In this case, please set as high-limit display value gradient correction × high-limit scale = 3 3 L L 3 3 L L 3 3 L L 3 3 L L
15.000. 4 4 M M 4 4 M M 4 4 M M 4 4 M M

■ High / Low-limit scale value 5 5 N N 5 5 N N 5 5 N N 5 5 N N

This function is to display setting of particular High / Low-limit value in order to display High / 6 6 O O 6 6 O O 6 6 O O 6 6 O O
Low-limit value of measured input. 7 7 P P 7 7 P P 7 7 P P 7 7 P P
If measured inputs are a and b and particular values are A and B, it will display a = A, b = B as
8 Q 8 Q 8 Q 8 Q
below graphs.
8 Q 8 Q 8 Q 8 Q
• When changing input range, it is changed automatically as factory default display range of 9 9 R R 9 9 R R 9 9 R R 9 9 R R
the input range. A A S S A A S S A A S S A A S S

Display Display Display B B T T B B T T B B T T B B T T


value value value C U C U C U C U
B B
C U C U C U C U
B
D D V V D D V V D D V V D D V V
A E W E W E W E W
A
a b Input
E W E W E W E W
a b Input a b Input A value F F X X F F X X F F X X F F X X
value value G Y G Y G Y G Y
Display Display Display
G Y G Y G Y G Y
value value value H Z H Z H Z H Z
a b
H Z
A
H Z H Z H Z
A
A Input a b
B value Input
B value
a b Input B
value

■ Zero adjustment
It adjusts the display value of the optional configured input value as zero by force.
Zero point error can be adjusted with 3 ways as below.
1. Direct input correction value at Low-limit display value deviation correction parameter.
2. S
 et the keys for zero adjustment parameter to YES and press the [◀] + [▲] keys for 3 sec in
RUN mode.
3. S
 et the external input terminal parameter to ZERO and short the Hold / Zero terminal for
over 50 ms.

■ Error correction
It corrects display value error of measured input.
Display value = ( Measured value × High-limit display value gradient correction)
+ Low-limit display value deviation correction
• E.g.: When the Input range 0 to 500 VDCᜡ and the display range is 0 to 500.0
If the low-limit display value is 1.2 to 0 VDCᜡ input, set -12 as deviation correction value to
display 0.0 by adjusting offset of the low-limit display value.
The display value to 500 VDCᜡ measured input varies by adjusting the offset of low-limit
display value.
If this display value is 501.0, calculate 500.0 / 501.0 (desired display value / the display value),
and set the 0.998 correction value as the High-limit display value gradient correction parameter
to display 500.0 by adjusting gradient of high-limit value.

■ Startup compensation time


This time function limits the operation of an output until the measured input (overvoltage
or inrush current) is stable at moment of power on. All outputs are OFF during startup
compensation time setting after power is applied.

■ Display cycle
In some applications the measured input may fluctuate which in turn causes the display to
fluctuate.
By adjusting the display cycle delay function time the operator can adjust the display time.
For example, if the operator sets the display cycle time to 4 sec, the display value displayed
will be the average input value over 4 sec and also will show any changes if any every 4 sec.

■ Max. / Min. peak value


It monitors max./min. peak value of display value based on the current displays value and then
displays the data at the parameters.
When pressing any one of front keys at the parameters, the monitored data is initialized.
Set the delay time at peak monitoring delay time parameter in order to prevent malfunction
caused by initial overcurrent or overvoltage, when monitoring the peak value.