DC-PV, Lda (Portugal)
Project: Eltaş Trafo
Variant: New simulation variant
Project summary
Geographical Site Situation Project settings
Çaraklar Latitude 38.83 °N Albedo 0.20
Turkey Longitude 27.05 °E
Altitude 15 m
Time zone UTC+3
Meteo data
Çaraklar
PVGIS api TMY
System summary
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 6777 units Nb. of units 24 units
Pnom total 3084 kWp Pnom total 2640 kWac
Grid power limit 2600 kWac
Grid lim. Pnom ratio 1.186
Results summary
Produced Energy 4463 MWh/year Specific production 1447 kWh/kWp/year Perf. Ratio PR 79.84 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Horizon definition 7
Main results 8
Loss diagram 9
Special graphs 10
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed planes 4 orientations No 3D scene defined Transposition Perez
Tilts/azimuths 7 / -160 ° Diffuse Imported
7 / 20 ° Circumsolar separate
7 / -70 °
7 / 110 °
PV Array Characteristics
PV module Inverter
Manufacturer Elin (verified by SolPEG) Manufacturer SMA
Model ELNSM-455-72M-HC-HV Model Sunny Tripower Core2 prelim
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 455 Wp Unit Nom. Power 110 kWac
Number of PV modules 6777 units Number of inverters 24 units
Nominal (STC) 3084 kWp Total power 2640 kWac
Array #1 - PV Array
Mixed orient.
#1/2: 61/61 strings
Tilt/Azimuth 7/-160 °
7/20 °
Number of PV modules 2196 units Number of inverters 8 units
Nominal (STC) 999 kWp Total power 880 kWac
Modules 122 Strings x 18 In series
At operating cond. (50°C) Operating voltage 500-800 V
Pmpp 929 kWp Pnom ratio (DC:AC) 1.14
U mpp 697 V
I mpp 1333 A
Array #2 - Sub-array #2
Mixed orient.
#1/2: 18/18 strings
Tilt/Azimuth 7/-160 °
7/20 °
Number of PV modules 648 units Number of inverters 2 units
Nominal (STC) 295 kWp Total power 220 kWac
Modules 36 Strings x 18 In series
At operating cond. (50°C) Operating voltage 500-800 V
Pmpp 274 kWp Pnom ratio (DC:AC) 1.34
U mpp 697 V
I mpp 393 A
PV Array Characteristics
Array #3 - Sub-array #3
Orientation #3
Tilt/Azimuth 7/-70 °
Number of PV modules 486 units Number of inverters 22 * MPPT 8% 1.8 units
Nominal (STC) 221 kWp Total power 202 kWac
Modules 27 Strings x 18 In series
At operating cond. (50°C) Operating voltage 500-800 V
Pmpp 206 kWp Pnom ratio (DC:AC) 1.10
U mpp 697 V
I mpp 295 A
Array #4 - Sub-array #4
Orientation #3
Tilt/Azimuth 7/-70 °
Number of PV modules 45 units Number of inverters 2 * MPPT 8% 0.2 unit
Nominal (STC) 20.48 kWp Total power 18.3 kWac
Modules 3 Strings x 15 In series
At operating cond. (50°C) Operating voltage 500-800 V
Pmpp 19.04 kWp Pnom ratio (DC:AC) 1.12
U mpp 581 V
I mpp 33 A
Array #5 - Sub-array #5
Orientation #4
Tilt/Azimuth 7/110 °
Number of PV modules 504 units Number of inverters 2 units
Nominal (STC) 229 kWp Total power 220 kWac
Modules 28 Strings x 18 In series
At operating cond. (50°C) Operating voltage 500-800 V
Pmpp 213 kWp Pnom ratio (DC:AC) 1.04
U mpp 697 V
I mpp 306 A
Array #6 - Sub-array #6
Mixed orient.
#1/2: 46/39 strings
Tilt/Azimuth 7/-160 °
7/20 °
Number of PV modules 1530 units Number of inverters 6 units
Nominal (STC) 696 kWp Total power 660 kWac
Modules 85 Strings x 18 In series
At operating cond. (50°C) Operating voltage 500-800 V
Pmpp 647 kWp Pnom ratio (DC:AC) 1.05
U mpp 697 V
I mpp 929 A
Array #7 - Sub-array #7
Orientation #3
Tilt/Azimuth 7/-70 °
Number of PV modules 702 units Number of inverters 2 units
Nominal (STC) 319 kWp Total power 220 kWac
Modules 39 Strings x 18 In series
At operating cond. (50°C) Operating voltage 500-800 V
Pmpp 297 kWp Pnom ratio (DC:AC) 1.45
U mpp 697 V
I mpp 426 A
PV Array Characteristics
Array #8 - Sub-array #8
Orientation #4
Tilt/Azimuth 7/110 °
Number of PV modules 666 units Number of inverters 2 units
Nominal (STC) 303 kWp Total power 220 kWac
Modules 37 Strings x 18 In series
At operating cond. (50°C) Operating voltage 500-800 V
Pmpp 282 kWp Pnom ratio (DC:AC) 1.38
U mpp 697 V
I mpp 404 A
Array losses
Array Soiling Losses Thermal Loss factor Serie Diode Loss
Loss Fraction 3.0 % Module temperature according to irradiance Voltage drop 0.7 V
Uc (const) 20.0 W/m²K Loss Fraction 0.1 % at STC
Uv (wind) 0.0 W/m²K/m/s
LID - Light Induced Degradation Module Quality Loss Module mismatch losses
Loss Fraction 2.5 % Loss Fraction -0.3 % Loss Fraction 1.0 % at MPP
DC wiring losses
Global wiring resistance 2.8 mΩ
Loss Fraction 1.5 % at STC
System losses
Unavailability of the system
Time fraction 0.8 %
2.9 days,
5 periods
AC wiring losses
Inv. output line up to injection point
Inverter voltage 400 Vac tri
Loss Fraction 0.14 % at STC
Inverter: Sunny Tripower Core2 prelim
Wire section (24 Inv.) Alu 24 x 3 x 185 mm²
Average wires length 10 m
Horizon definition
Horizon from PVGIS website API, Lat=38°49"33', Long=27°2"58', Alt=m
Horizon profile
Azimuth [°] -180 -173 -165 -158 -150 -143 -135 -128 -120 -113 -105 -98
Height [°] 1.9 3.8 3.8 5.0 6.1 6.5 6.9 6.9 6.1 5.7 5.0 5.0
Azimuth [°] -90 -83 -75 -68 -60 -53 -45 -38 -30 -23 -15 -8
Height [°] 5.3 5.3 4.2 3.8 4.2 4.6 4.6 5.3 5.3 5.7 6.1 6.5
Azimuth [°] 0 8 15 23 30 45 53 60 68 75 83 90
Height [°] 6.1 6.5 6.5 6.9 6.5 6.5 6.1 5.0 4.2 3.4 2.3 0.8
Azimuth [°] 98 105 113 120 128 135 143 150 158 165 180
Height [°] 0.8 0.0 0.4 0.4 1.9 3.8 4.6 4.6 3.8 1.9 1.9
Orientation #3 Orientation #4
Main results
System Production
Produced Energy 4463 MWh/year Specific production 1447 kWh/kWp/year
Performance Ratio PR 79.84 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
Loss diagram
1818 kWh/m² Global horizontal irradiation
Special graphs
Daily Input/Output diagram