Schneider Electric & Satron To Shorter Cleaning Time
Schneider Electric & Satron To Shorter Cleaning Time
Walkthrough audit
1. Check conformity
with best practices
on both Energy,
Automation and
Process part;
2. Highlight the positive
elements and do some
recommendations of
improvement when
there is a gap between
installation and best
practices;
Turbidity sensors: from sizing of a portable and reusable solution to onsite installation
Before
Corporate Network
Server with 2
RDP Connection
communication cards,
SSD 500GB storage –
48GB RAM
Corporate
FireWall Uninterruptable Power
Supply (UPS)
Corporate Laptop and screen SE Laptop for SMT1500RMI2U,
(without OptiCIP installation) commisionning
and maintenance from SE APC Smart-
UPS 1500 VA
Provided by SE
PLC Network
CIP1 – 4 Lines
CIP2 – 2 Lines PLC PLC CIP 3 - 4 Lines
Return
13min 12min 10min 10min 11min 16min
conductivity
A B C
Return
turbidity
White Waters
turbidity pattern
Time loop
A B C
• Total duration of first rinse is • Total duration of intermediate • According to us this final rinse is
presently set at 25mins. rinse is presently set at too long. The first 10mins are
According to the turbidity 20mins. Turbidity signal shows useful to push and recover acid in
measurement only the first that there is no organic food return pipe.
13mins are impactful to pollution during this period • As a best practice a final rinse
remove/evacuate organic food • According to us this duration of 3 times the Time Loop
present in the pipes. intermediate rinse is so far too is enough (first time loop duration
• The last 12mins seem of no long, the two chemical phases to push previous phase, the two
use to remove further organic are well separated with proper others as security).
materials. conductivity drop, so in this • In this example, 15mins final
case intermediate rinse can rinse including security should be
easily be shorted by half or enough, other 12min could be
even more. saved.
•
As explained in more details in Schneider Electric methodology, recipe modification must be done on iterative manner,
with manual sample and validation from quality people.
Thanks to the use of Satron Turbidity meters together with Schneider Electric CIP Advisor
Solution, now you know how to save half an hour cleaning time on your CIP !
Remember, this is only for 1 equipment, think about how many of them you have in your factory…