Solenoid valves for controlling pneumatic actuators in hazardous areas
General features
– SIL according to IEC 61508 (optional)
– Fail-safe action for use on control valves (optional) Fig. 1: 5/2-way solenoid valve · Actuated on one side · With
spring return mechanism · KVS 0.16 · G ¼ connection
– Corrosion-resistant enclosure with degree of protection
IP 54 or IP 65 for use in humid or rough ambient condi-
tions
– Version compatible with paint (on request)
– Service life of over 20 million switching cycles
– Ambient temperature range –20 to +80 °C or
–45 to +80 °C
– Rail, wall or pipe mounting
– Mounting to linear actuators with NAMUR rib according
to IEC 60534-6 or to rotary actuators with NAMUR inter-
face according to VDI/VDE 3845
SAMSON AKTIENGESELLSCHAFT · Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany Edition January 2022
Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 · samson@samsongroup.com · www.samsongroup.com
– Electrical connection using M20x1.5 cable gland to termi- – Exhaust air feedback (optional)
nals or with connector – KVS coefficients 0.16 to 4.3
– Cable break protection (accessories) – Supply/exhaust air restrictions to adjust different closing
Special features of the booster valve and opening times in a ratio of 1:15 (optional) · u AB 11
– Diaphragm actuator with return spring or spool actuated – G ¼ or G ½ (¼ NPT or ½ NPT) threaded connections
either on one side or both sides – NAMUR interface ¼” or ½”
– 3/2-, 5/2-, 5/3 or 6/2-way function
9 5 4 9 5 4 9 4 1.5 2.5
81+ E 81+ E 81+ E 81+ E
82– 82– 82– 82–
P P P P
3 3 1.3 2.3
Type 3963-XXX0111X0XXXX0
Solenoid Valve
– 3/2-way function
– Adjustable exhaust air restrictor
– KVS 0.16
– G ¼ or ¼ NPT connection
– Rail mounting, wall mounting or
mounting to linear actuators (e.g.
Type 3271 or Type 3277) for on/off
service using pipe fitting
2 T 3963 EN
Table 1.2: Solenoid valves for mounting on actuators for throttling or on/off service
P E
12
4 2
Type 3963-XXX5013XXXXXX0X
Solenoid Valve
– 5/3-way function with spring-
centered mid-position (ports 2 and 4
vented)
– KVS 1.4
– G ¼ or ¼ NPT connection
– Safety function (TÜV)
– Wall or pipe mounting
T 3963 EN 3
Table 2: Versions with NAMUR interface
Table 2.1: Solenoid valves for mounting on actuators for throttling or on/off service
Type 3963-XXX1001XXXXXX0 Type 3963-XXX0101X0XXXX0
Solenoid Valve Solenoid Valve
– 5/2-way function – 3/2-way function
– KVS 0.16 – Exhaust air feedback
– G ¼ or ¼ NPT connection, NAMUR – Adjustable exhaust air restrictor
– Mounting on rotary actuators for on/ – KVS 0.16
off service with NAMUR interface – G ¼ or ¼ NPT connection, NAMUR
– Mounting on rotary actuators for on/
off service with NAMUR interface or
with an adapter plate (item no. 1400-
6751) on linear actuators with
NAMUR rib (e.g. Type 3241-1)
4 9 4 2.3
81+ E 81R E
82– 82S
P P
1.3 2.3 1.3 2.3
Type 3963-XXX1201X0XXXX0 Type 3963-XXX0301XXXXXX0
Solenoid Valve Solenoid Valve
– 5/2-way function – 3/2-way function
– Two adjustable exhaust air restrictors – Adjustable supply air/exhaust air
– KVS 0.16 restrictors
– G ¼ or ¼ NPT connection, NAMUR – KVS 0.16
– Mounting on rotary actuators for on/ – G ¼ or ¼ NPT connection, NAMUR
off service with NAMUR interface – Mounting on rotary actuators with
NAMUR interface or with an adapter
plate (item no. 1400-6751) on linear
actuators with NAMUR rib (e.g.
Type 3241-1)
4 T 3963 EN
Table 2.2: Solenoid valves for mounting on actuators for throttling or on/off service
9 4 5 9 31 9 5 13 9 9 5 13
81R E E 81+ E P 81+ 81+ E
82S 82– 82– 82–
P P P E P
3 5 4 2 4 2 4 2
Type 3963-XXX0004XXXXXXX Type 3963-XXX0003XXXXXXX Type 3963-XXX2003XXXXXXX Type 3963-XXX1006XXXXXX0
Solenoid Valve Solenoid Valve Solenoid Valve Solenoid Valve
– 3/2-way function – 3/2-way function – 5/2-way function with two detent – 5/2-way function
– Exhaust air feedback – Exhaust air feedback positions – KVS 2.9
– KVS 4.3 – KVS 1.4 – KVS 1.4 – G ½/½ NPT connection or NAMUR
– G ½/½ NPT connection or NAMUR – G ¼ or ¼ NPT connection, NAMUR – G ¼ or ¼ NPT connection, NAMUR ½”
½” – Safety function (TÜV) – Safety function (TÜV) – Mounting on rotary actuators with
– Safety function (SIL/TÜV) – Mounting on rotary actuators with – Mounting on rotary actuators with NAMUR interface 3/8“ or ½“
– Mounting on rotary actuators for on/ NAMUR interface or mounting on NAMUR interface
off service with NAMUR interface 3/8“ linear actuators with NAMUR rib
or ½“ using an adapter plate (item no.
1400-6751)
9 5 13 9 5 13 9
81+ E 81+ E P 81+
82– 82– 82–
P P E
4 2 4 2
Type 3963-XXX1003XXXXXX0 Type 3963-XXX3003XXXXXX0
Solenoid Valve Solenoid Valve
– 5/2-way function – 5/3-way function with spring-
– KVS 1.4 centered mid-position (ports 2 and 4
– G ¼ or ¼ NPT connection, NAMUR closed)
– Mounting on rotary actuators with – KVS 1.4
NAMUR interface or mounting on – G ¼ or ¼ NPT connection, NAMUR
linear actuators with NAMUR rib – Mounting on rotary actuators with
using an adapter plate (item no. NAMUR interface
1400-6751)
9 513 9 9 5 13 9
81+ E P 81+ 81+ E P 81+
82– 82–
14
82– 82–
P E P E
12
4 2 4 2
Type 3963-XXX5003XXXXXXX Type 3963-XXX2006XXXXXX0
Solenoid Valve Solenoid Valve
– 5/3-way function with spring- – 5/2-way function with two detent
centered mid-position (ports 2 and 4 positions
vented) – KVS 2.9
– KVS 1.4 – G ½/½ NPT connection or NAMUR
– G ¼ or ¼ NPT connection, NAMUR ½”
– Mounting on rotary actuators with – Mounting on rotary actuators with
NAMUR interface NAMUR interface 3/8“ or ½“
T 3963 EN 5
Design and principle of operation Functional diagram
Solenoid valves actuated on one side B
The solenoid valves consist of an electropneumatic binary
converter (A) with manual override (B, optional) and a 2
A 3
booster valve (C) actuated on one side with return spring
(Fig. 4). 1
The air supply for the electropneumatic binary converter (A) is
4 4
routed internally through the booster valve (C) (delivered
state). The solenoid valve can be converted to accept an
external pilot supply at port 9 by turning a gasket.
The pressure reducer (5) reduces the supply air pressure to Nom. +81
1.4 bar. signal
–82
In the idle position, the flapper (2) is lifted off the outlet nozzle
(1) by the spring (3). As a result, a pressure lower than the
deactivation pressure of the booster valve (C) builds up in the
pressure divider, which consists of the restrictor (6) and outlet 9
6 5 Changeover
nozzle (1).
to external
When the solenoid coil (4) is energized by an electric binary 5 pilot supply
signal, the outlet nozzle (1) is closed by the flapper (2)
against the force of the spring (3). This causes the pressure in
the pressure divider to rise above the activation pressure of
C
the booster valve (C), switching it to the operating position.
4
After the solenoid coil is de-energized, the booster valve (C) is
switched to the neutral position again by a return spring.
3
Solenoid valves actuated on both sides
The solenoid valves consist of two electropneumatic binary 1 Outlet nozzle A Electropneumatic binary
converters (A) with manual override (B, optional) and a 2 Flapper plate converter
booster valve (C) actuated on both sides with two detent 3 Spring B Manual override
positions or spring-centered mid-position. 4 Solenoid C Booster valve
The air supply for the electropneumatic binary converters (A) 5 Pressure reducer
is routed internally through the booster valve (C) (delivered 6 Restrictor
state). The solenoid valve can be converted to accept an
external pilot supply at port 9 by turning two gaskets. Fig. 4: Solenoid valve with diaphragm switching element as a
The pressure reducer (5) reduces the supply air pressure to booster valve (KVS 0.16)
1.4 bar.
In the idle position, the flapper (2) is lifted off the outlet nozzle
(1) by the spring (3). As a result, a pressure lower than the
deactivation pressure of the booster valve (C) builds up in the
pressure divider, which consists of the restrictor (6) and outlet
nozzle (1).
When the solenoid coil (4) is energized by an electric binary
signal, the outlet nozzle (1) is closed by the flapper (2)
against the force of the spring (3). This causes the pressure in
the pressure divider to rise above the activation pressure of
the booster valve (C), switching it to the operating position.
After the solenoid coil is de-energized, the operating position
of the detented booster valve (C) is kept until the opposing
signal is received. The spring-centered booster valve (C) is
switched to the mid-position by a return spring after the
solenoid coil is de-energized.
A simultaneous control of the electropneumatic binary con-
verter (A) must be ruled out on the electric control level.
6 T 3963 EN
Technical data
General data
Design Solenoid with flapper/nozzle assembly and booster valve
IP 54 with filter
Degree of protection
IP 65 with filter check valve
Enclosure Polyamide PA 6-3-T-GF35, black
AlMg, powder coated, gray beige RAL 1019 or Ematal coating (depending on the version: see
article code)
Connecting plate
1.4404 (see ‘Versions and ordering data’ for special versions)
Polyamide PA 6-3-T-GF35, black
Material
Screws 1.4571
Springs 1.4310
Seals Silicone rubber, Perbunan
Chloroprene rubber 57 Cr 868 (–20 to +80 °C)
Diaphragms
Silicone rubber (–45 to +80 °C)
Medium Instrument air free from corrosive substances or nitrogen
Supply air
Pressure 1.4 to 6 bar/2.7 to 6 bar 1)
≤ 80 l/h at 1.4 bar supply air in neutral position
Air consumption
≤ 10 l/h at 1.4 bar pilot supply in operating position
Switching time ≤65 ms
≥2 x 107 switching cycles (at –20 to +80 °C)
Service life
≥2 x 106 switching cycles (at –45 to +80 °C)
Ambient temperature Refer to ‘Electric data’
Mounting orientation Any desired position (u EB 3963)
1) Only in the version with KVS 2.0 and 4.3 with attachment according to NAMUR interface
T 3963 EN 7
Electric data
Type 3963 -X1 -X2 -X3 -06 -05
6 V DC 12 V DC 24 V DC 115 V AC 230 V AC
UN
Nominal signal Max. 27 V 1) Max. 25 V 1) Max. 32 V 1) Max. 130 V 1) Max. 255 V 1)
fN 48 to 62 Hz
U+80 °C ≥4.8 V ≥9.6 V ≥18 V 82 to 130 V 183 to 255 V
Switching ON I+20 °C ≥ 1.41 mA ≥ 1.52 mA ≥ 1.57 mA ≥ 2.2 mA ≥ 2.6 mA
point P+20 °C ≥5.47 mW ≥13.05 mW ≥26.71 mW ≥0.17 VA ≥0.46 VA
OFF U–25 °C ≤1.0 V ≤2.4 V ≤4.7 V ≤18 V ≤36 V
Impedance R+20 °C 2.6 kΩ 5.5 kΩ 10.7 kΩ Approx. 40 kΩ Approx. 80 kΩ
Effect of temperature 0.4 %/°C 0.2 %/°C 0.1 %/°C 0.05 %/°C 0.03 %/°C
Type of protection Ex ia IIC 2) for use in hazardous areas (Zone 1)
Type 3963 -11 -12 -13
Maximum values when connected to a certified intrinsically safe circuit
Output voltage 4) Ui 25 V · 27 V · 28 V · 30 V · 32 V
Output current 4) Ii 150 mA · 125 mA · 115 mA · 100 mA · 85 mA
Power dissipation Pi 250 mW No restrictions
Outer capacitance Ci ≈0
Outer inductance Li ≈0
T6 –45 to +60 °C
Ambient temperature
T5 –45 to +70 °C
in temperature class
T4 –45 to +80 °C
Type of protection Ex nA II for use in hazardous areas (Zone 2)
3)
8 T 3963 EN
Solenoid valve, actuated on one side, KVS 4.3, with threaded connections
Switching function 3/2-way function 3/2-way function 5/2-way function 8) 6/2-way function 8)
1.9 (43), 1.5 (34) 1.9 (43), 1.5 (34) 1.9 (43), 1.5 (34) 1.9 (43), 1.5 (34)
KVS 1) (direction of flow)
4.3 (35), 4.7 (53) 4.3 (35), 4.7 (53) 4.3 (35), 4.7 (53) 4.3 (35), 4.7 (53)
Ambient temperature 2) –20 to +80 °C –45 to +80 °C –20 to +80 °C –20 to +80 °C
Safety function SIL 3), TÜV 4) SIL 3), TÜV 4) – –
Design Poppet valve with diaphragm actuator, soft seated, with return spring
GD AlSi 12, powder coated, gray beige RAL 1019
Enclosure
1.4404 (see ‘Versions and ordering data’ for special versions)
Material Diaphragm Chloroprene rubber Silicone rubber Chloroprene rubber Chloroprene rubber
Seals Chloroprene rubber Silicone rubber Chloroprene rubber Chloroprene rubber
Screws 1.4571
Actuation Controlled on one side with a pilot valve, KVS 0.16
Instrument air free from corrosive substances or nitrogen 5)
Operating medium
Instrument air free from corrosive substances, air containing oil or non-corrosive gases 6)
1.4 to 6 bar 5) or 10 bar 6) 1.4 to 6 bar 5) or 10 bar 6) 1.4 to 6 bar 5) or 10 bar 6) 1.4 to 6 bar 5) or 10 bar 6)
Max. operating pressure
(43, 35) (43, 35) (as required) (as required)
(direction of flow)
2 bar (as required) 2 bar (as required) 2 bar (as required) 2 bar (as required)
Switching cycles (operating ≥107 (6 bar) ≥106 (6 bar) ≥107 (6 bar) ≥107 (6 bar)
pressure) ≥106 (10 bar) ≥105 (10 bar) ≥106 (10 bar) ≥106 (10 bar)
Port G ½ or ½ NPT
Approx. weight 585 g (standard version) 1100 g (standard version)
Solenoid valve, actuated on one side, KVS 2.0 or 4.3, with NAMUR interface
Switching function 3/2-way function with exhaust air feedback
1.1 (43) 1.1 (43) 1.9 (43) 1.9 (43)
KVS 1) (direction of flow)
2.0 (35) 2.0 (35) 4.3 (35) 4.3 (35)
Ambient temperature 2) –20 to +80 °C –45 to +80 °C –20 to +80 °C –45 to +80 °C
Safety function SIL , TÜV
3) 4)
SIL , TÜV
3) 4)
SIL , TÜV
3) 4)
SIL 3), TÜV 4)
Design Poppet valve with diaphragm actuator, soft seated, with return spring
GD AlSi 12, powder coated, gray beige RAL 1019
Enclosure
1.4404 (see ‘Versions and ordering data’ for special versions)
Material Diaphragm Chloroprene rubber Silicone rubber Chloroprene rubber Silicone rubber
Seals Chloroprene rubber Silicone rubber Chloroprene rubber Silicone rubber
Screws 1.4571
Actuation Controlled on one side with a pilot valve, KVS 0.16
Instrument air free from corrosive substances or nitrogen 5)
Operating medium
Instrument air free from corrosive substances, air containing oil or non-corrosive gases 6)
Max. operating pressure 2.7 to 6 bar 5) or 10 bar 6)
Switching cycles (operating ≥107 (6 bar) ≥106 (6 bar) ≥107 (6 bar) ≥107 (6 bar)
pressure) ≥106 (10 bar) ≥105 (10 bar) ≥106 (10 bar) ≥105 (10 bar)
Supply air G ¼ or ¼ NPT, NAMUR interface ¼” 7), G 3/8 G ½ or ½ NPT, NAMUR interface ½” 7)
Connection
Exhaust air G ½ or ½ NPT, NAMUR interface ½” , G 7) 3/8 G ½ or ½ NPT, NAMUR interface ½” 7)
Approx. weight 1380 g (standard version) 1500 g (standard version)
1) The air flow rate when p1 = 2.4 bar and p2 = 1.0 bar is calculated using the following formula: Q = KVS x 36.22 in m³/h.
2) The permissible ambient temperature of the solenoid valve depends on the permissible ambient temperature of the components, type of
protection and temperature class.
3) SIL according to IEC 61508
4) Emergency release or locking of compressed air supply
5) With internal pilot supply
6) With external pilot supply
7) NAMUR interface according to VDI/VDE 3845
8) Connecting hose between booster valves made of polyamide, see Fig. 12 and Fig. 13
T 3963 EN 9
Solenoid valves actuated on one side, KVS 1.4 or KVS 2.9
Switching function 3/2-way function with exhaust air feedback 5/2-way function
KVS 1)
1.4 or 2.9
Safety function TÜV 2) (with KVS 1.4) –
Design Spool, metal-to-metal seat, zero overlap, with return spring
GD AlSi 12, powder coated, gray beige RAL 1019
Enclosure
1.4404 (see ‘Versions and ordering data’ for special versions)
10 T 3963 EN
Dimensions
All dimensions in mm
Screw plug
M20x1.5
63
62 62
31 38 61 31
Screw plug
M20x1.5
80
62 62
T 3963 EN 11
Dimensions of devices with threaded connections
1
2
3
1 M4/7 mm deep
28
38
48
2 M3/6 mm deep
3 Ø3 mm/3.5 mm deep 3
2
1
62
61 31 38 31
124
4 9
1.3 2.5
25
25
2.3 1.5
40 40
10
10
62
1
2
3
1 M4/7 mm deep
28
38
48
2 M3/6 mm deep 3
3 Ø3 mm/3.5 mm deep 2
1
62
61 31 38 31
9(4) 5
3 9
19
19
10
10
40 40
62
Port 9 in Type 3963-XXX0X11X0XXXXX Ports 9 and 5 only in Type 3963-XXX0X12XXXXXXX
Port 4 in Type 3963-XXX0X12XXXXXXX
12 T 3963 EN
Bottom view of connecting plate
1
2
1 M4/7 mm deep 3
2 M3/6 mm deep
48
28
38
3 Ø3 mm/3.5 mm deep 3
2
1
62
61 31 38 31
129
1.4 2.4 9
49
1.3 2.3
39
34
2.5 1.5
24
25 40
10
62
42
61 31 38 31
108,5
*
12 12
24
*
22,5
22,5
16 16 60 60
* Mounting to a mounting block us-
ing two M5x60 (DIN 912) screws
Fig. 10: 3/2-way solenoid valve, actuated on one side, KVS 0.16 or KVS 0.32, for mounting to linear actuators using a mounting block
T 3963 EN 13
64 29 38 31
M20x1.5 Screw plug
cable gland M20x1.5
G ¼ blank-
ing plug
9
9
193
Int
½"
94,5
4 3 ½"
53
5
50
7
31
34
½" 21 21 9
53 35 62
65
64 29
G ¼ blank-
ing plug
194
G½
M6
4
3 G½
94,5
22
53
50
5
34
31
38 G½ 21 21
100
53 35
135 11
64
65
14 T 3963 EN
64 29
G ¼ blank-
ing plug
194
G½
M6
4
94,5
3
G½
22
53
50
5
34
31
38 G½
100 21 21
135 11
53 35
64
65
T 3963 EN 15
61 31
M20x1.5
Screw plug
cable gland
M20x1.5
G ¼ blank-
122
ing plug
9 9
Ø4,3
47
5
1 4
44,4
22
2 ¼"
3
47
32 14 13
50,8 56
Port 5 is sealed when the 3/2-way function is used
14 56
61 31 17
M20x1.5
Screw plug
cable gland
M20x1.5
122
G ¼ blank-
ing plug Int
9 9
14
47
Ø4,3
5
4 ¼"
44,4
1
22
2
3 32
47
50,8 12
9
9 Int
122
16 T 3963 EN
Dimensions of devices with threaded connections for linear actuators with NAMUR rib
70 12
8,4
62
61 31 38 31
Screw plug
M20x1.5
M20x1.5
80
cable gland
109
3 9
6 23
4 5
19
19
14
G¼
40
40
10
16,8
62
60°
67 25
12 12 G¼
1.3
1.3
60°
16,8
30
8,5
32
12
18
34
60
2.3
2.3
5,3 6
10 11
30
Fig. 17: Adapter plate with NAMUR interface/NAMUR rib (item no. 1400-6751)
T 3963 EN 17
Dimensions of devices with NAMUR interface for rotary actuators
61 31 38 31
Screw plug
M20x1.5
63
M20x1.5
88
cable gland
12,5
24 4
25
62
1.3 2.3
NAMUR fixing level
96
69
36 25
32
62
Fig. 18: 3/2 or 5/2-way solenoid valve, actuated on one side, KVS 0.16
61 31 38 31
Screw plug
M20x1.5
M20x1.5
cable gland
114
9
2.3 24
34
4
22,2
17
13
5 18,5 62
1.3 2.3
62 NAMUR fixing level
96
69
36 25
62
32
18 T 3963 EN
61 31 38 31
Screw plug
M20x1.5
102
9
1.4 2.4 24 2.5 1.5
39
25
10
62 16
10
1.3 2.3
24 25 36
25 56
49 32
NAMUR fixing level
25
M20x1.5
cable gland
67
Fig. 20: 6/2-way solenoid valve, actuated on one side, KVS 0.16
72
61 31 34 38
M20x1.5
cable gland
Screw plug
M20x1.5
31
122
Int
9 9
5 5,3
47
4 ¼"
44,4
22
1
12
2
3
47
32 16
50,8 29
36
Port 5 is sealed when the 3/2-way function is used
T 3963 EN 19
61 31
M20x1.5 Screw plug
cable gland M20x1.5
207
G(NPT) ¼
Cap screw ISO 4762,
G 3/8 M5x60 with spring
washer, DIN 128, A5
108
66
NAMUR interface ¼”
21,5 12
G 3/8
G(NPT) ½ 26
63
32
62 6
61 31
M20x1.5 Screw plug
cable gland M20x1.5
9.
¼” blanking
216
NAMUR interface ½”
72
21,5 20
5
G(NPT) ½ 26
63
45
62 6
20 T 3963 EN
61 31
169,5
9.
¼” blanking G¼
plug
½"
77,25
5
½" ½"
Ø6 ½" 1
1
64
20
½" NAMUR
3 interface
79
45 1
66 24
49
71
72
61 31 34 38
M20x1.5
cable gland
Screw plug
M20x1.5
31
122
Int
9 9
5
47
5,3
4 ¼"
1
44,4
2
3
12
47
9
9 Int
122
T 3963 EN 21
61 31
M20x1.5 Screw
cable plug
gland M20x1.5
9.
170
¼” blank- G¼
ing plug
½"
77,25
5
½"
½" Ø6 ½" 1
1
64
NAMUR
20
½" interface
3
66
¼” blank-
9.
ing plug
1
32
71
22 T 3963 EN
Versions and ordering data
Note
The "NAMUR interface according to VDI/VDE 3845" version in combination with KVS 0.32 has an Ematal coating
(Type 3963-xxxxx02xxxxxxxxxx).
T 3963 EN 23
Type 3963 Solenoid Valve Type 3963- x x x x x x x x x x x x x x x x x
Pneumatic connection
G ¼ (KVS 0.16, 0.32, 1.4, 2.0) 0
¼ NPT (KVS 0.16, 0.32, 1.4, 2.0) 1
G ½ (KVS 2.9, 4.3) 2
½ NPT (KVS 2.9, 4.3) 3
Without (pilot valve as spare part/mounting block for Type 3277 Linear Actuator) 4
Pilot supply
Internal pilot supply for actuators for on/off service 0
External pilot supply for actuators for throttling service 1
Electrical connection
Blanking plug M20x1.5 0 0
M20x1.5 cable gland, black polyamide 0 1
M20x1.5 cable gland, blue polyamide 1 1
Adapter M20x1.5 to ½ NPT (aluminum) 1 2
M20x1.5 cable gland (CEAG), black polyamide 1 3
M20x1.5 cable gland, nickel-plated brass 1 4
M20x1.5 cable gland, nickel-plated brass, blue 1 5
M20x1.5 cable gland (CEAG), blue polyamide 1 6
M20x1.5 cable gland (Jacob), blue polyamide 1 7
Device connector according to DIN EN 175301-803, black polyamide 1) 2 3
Device connector with LED according to DIN EN 175301-803, black polyamide 1)
2 5
Adapter M20x1.5 to ½ NPT (stainless steel) 2 6
Degree of protection
IP 54 with polyethylene filter 0
IP 65 with filter check valve made of polyamide 1
IP 65 with filter check valve made of stainless steel 2
NEMA 4 with filter check valve made of polyamide 4
NEMA 4 with filter check valve made of stainless steel 5
IP 65 with labyrinth-type vent plug 6
Ambient temperature 5)
–20 to +80 °C 0
–45 to +80 °C 2
Safety function
Without 0
SIL 6)
1
TÜV 7) 2
Special version 8)
Without 0 0 0
Material
Connecting plate/booster valve enclosure made of 1.4404 on request 0 0 1
Explosion protection
CCC Ex Ex ia IIC T4 ~ T6 0 0 9
EAC (GOST) 1Ex ia IIC T6...T4 Gb X 0 1 1
KCS Ex ia IIC T6/T5/T4 0 1 3
TR CMU 1055 II 2G Ex ia IIC T6 Gb 0 1 7
24 T 3963 EN
Summary of explosion protection approvals
Type 3963 Certification Type of protection
Number PTB 01 ATEX 2085
ATEX II 2G Ex ia IIC T6...T4 Gb
Date 2019-11-18
Number 2020322307003489
Date 2020-12-11 Ex ia IIC T4 ~ T6
Valid until 2025-12-10
CCC Ex
Number 021322307003631
Date 2021-01-08 Ex ia IIC T4 ~ T6
Valid until 2026-01-07
Number RU C-DE.HA65.B.00806/20
EAC (GOST) Date 2020-11-10 1Ex ia IIC T6...T4 Gb X
-1
Valid until 2025-05-11
Number 13-KB4BO-0039
KCS Date 2013-01-31 Ex ia IIC T6/T5/T4
Valid until 2023-01-31
Number ZETC/37/2021
Date 2021-07-26 II 2G Ex ia IIC T6 Gb
Valid until 2024-07-25
TR CMU 1055
Number ZETC/111/2021
Date 2021-08-25
Valid until 2024-08-24
Number 1607857 Ex ia IIC T6: Class I, Zone 0;
CSA Class I, II, Div. 1, Groups A, B, C, D, E, F, G;
Date 2005-09-16
Class I, II, Div. 2, Groups A, B, C, D, E, F, G
Number 3020228 Class I, Zone 0 AEx ia IIC
-3
Class I, II, III, Div. 1, Groups A, B, C, D, E, F, G
FM Class I, Div. 2, Groups A, B, C, D;
Date 2015-10-12
Class II, Div. 2 Groups F, G; Class III;
Type 4X
Number PTB 01 ATEX 2086 X II 3G Ex nA II T6 Gc
ATEX
Date 2014-04-17 II 3G Ex ic IIC T6 Gc
Number ZETC/37/2021
II 3G Ex ic IIC T6 Gc
Date 2021-07-26
-8 II 3G Ex nA II T6 Gc
Valid until 2024-07-25
TR CMU 1055
Number ZETC/111/2021
Date 2021-08-25
Valid until 2024-08-24
T 3963 EN 25
Spare parts and accessories
Spare parts for Type 3963 Solenoid Valve
Designation Order no.
Gasket made of silicone rubber (VMQ), –45 to +80 °C (for connecting plate) 0430-2287
Molded seal (for supply air in booster valves with KVS 1.4) 8502-1091
Diaphragm made of chloroprene rubber (CR), –20 to +80 °C (for booster valve with KVS 2.0 or KVS 4.3) 0520-0620
Diaphragm made of chloroprene rubber (CR), –20 to +80 °C (for all booster valves, except those with KVS 2.0 or KVS 4.3) 0520-0622
Diaphragm made of silicone rubber (VMQ), –45 to +80 °C (for booster valve with KVS 2.0 or KVS 4.3) 0520-1097
Diaphragm made of silicone rubber (VMQ), –45 to +80 °C (for all booster valves, except those with KVS 2.0 or KVS 4.3) 0520-1128
Switching element, –20 to +80 °C (for booster valve with KVS 2.0 or 4.3) 1180-8311
Switching element, –45 to +80 °C (for booster valve with KVS 2.0 or 4.3) 1180-8553
O-ring 13×3.5, –45 to +80 °C (for NAMUR interface ¼", KVS 1.4) 8421-9002
O-ring 16×2, –20 to +80 °C (for NAMUR interface ¼", KVS 2.0) 8421-0364
O-ring 16×2, –45 to +80 °C (for NAMUR interface ¼", KVS 2.0) 8421-0368
O-ring 24×2, –20 to +80 °C (for NAMUR interface ½”, KVS 4.3) 8421-1077
O-ring 24×2, –45 to +80 °C (for NAMUR interface ½”, KVS 4.3) 8421-0425
O-ring 28×2, –45 to +80 °C (for NAMUR interface ½”, KVS 2.9) 8421-0419
O-ring 26×2, –20 to +80 °C (for booster valve with KVS 2.0 or KVS 4.3) 8421-0085
O-ring 26×2, –45 to +80 °C (for booster valve with KVS 2.0 or KVS 4.3) 8421-0418
O-ring 30×2, –45 to +80 °C (for booster valve with KVS 2.9) 8421-0439
O-ring 36×2, –20 to +80 °C (for booster valve with KVS 2.0, KVS 2.9 or KVS 4.3) 8421-0102
O-ring 36×2, –45 to +80 °C (for booster valve with KVS 2.0 or KVS 4.3) 8421-0101
O-ring 48×1, –20 to +80 °C (for booster valve with KVS 4.3) 8421-0112
O-ring 48×1, –45 to +80 °C (for booster valve with KVS 4.3) 8421-0474
O-ring 48×1.5, –45 to +80 °C (for booster valve with KVS 2.0 or KVS 4.3) 8421-1027
O-ring 48×1.5, –20 to +80 °C (for booster valve with KVS 2.0 or KVS 4.3) 8421-1061
Enclosure cover without filter (for pilot valve)
Without manual override 1099-0673
With external switch (accessible using a screwdriver) 1099-0674
With external pushbutton (accessible using a pin) 1099-0675
With switch lever (accessible from the outside) 1099-1194
Enclosure cover for start-up 1402-1298
Blanking plug G ¼, 1.4571 (for port 9 at the pilot valve) 0070-0858
Blanking plug ¼ NPT, 1.4571 (for port 9 at the pilot valve) 0070-0862
NBR O-ring 14x1.5 (for blanking plug) 8421-0070
26 T 3963 EN
Accessories for Type 3963 Solenoid Valves
Designation Order no.
Cable socket according to EN 175301-803, form A, made of polyamide, black, degree of protection IP 65 0790-6658
Cable socket with LED according to EN 175301-803, form A, made of polyamide, black, degree of protection IP 65 1170-4069
Cable socket (Harting), 7-pole, made of aluminum, silver, degree of protection IP 65 1400-8298
Sensor connecting lead, two-wire, 3 m, blue, with angle connector M12x1, 4-pole, degree of protection IP 68 8801-2810
Cable socket (Binder), 7-pole, made of PBT GV, black, degree of protection IP 67 8831-0716
Cable socket M12x1, 4-pole, angled design, made of polyamide, black, degree of protection IP 67 8831-0865
Cable breakage protection with activation delay, enclosure for 35 mm rail mounting, IP 20 (for Type 3963-X1 with 6-V DC 3994-0160
nominal signal)
Filter made of polyethylene, G 1/G ½ connection, degree of protection IP 54 (required for actuator size >1400 cm²) 1400-5268
Filter made of polyethylene, G ¼ connection, degree of protection IP 54 8504-0066
Filter made of polyethylene, G ½ connection, degree of protection IP 54 8504-0068
Filter check valve in housing with G ¼ thread made of polyamide, degree of protection IP 65 1790-7408
Filter check valve in housing with G ¼ thread made of 1.4301, degree of protection IP 65 1790-7253
Filter check valve in housing with G ¼ thread made of polyamide, degree of protection NEMA 4 1790-9645
Filter check valve in housing with G ¼ thread made of 1.4301, degree of protection NEMA 4 1790-9646
Mounting base for G-profile rail 32 according to EN 50035 (2 pcs. required) 1400-5930
Mounting base for 35 mm top-hat rail according to EN 50022 (2 pcs. required) 1400-5931
Mounting plate for wall mounting 1400-6726
Vent plug with G1/4 thread made of polyamide, degree of protection IP 65 1991-0451
T 3963 EN 27
Mounting kits for Type 3963 Solenoid Valves with NAMUR interface
Designation Order no.
Mounting kit for linear actuators (350/355/700/750 cm² actuator area, G 3/8 connection) with NAMUR rib using adapter
plate for NAMUR rib/interface (order no. 1400-6751)
and screw fittings for 12×1 pipe, G ¼/G 3/8 connection, made of zinc-plated steel 1400-6746
and screw fittings for 12×1 pipe, G ¼/G 3/8 connection, made of CrNiMo steel 1400-6747
and screw fittings for 10×1 pipe, G ¼/G 3/8 connection, made of polyamide 1400-6748
Mounting kit for linear actuators (175/240 cm² actuator area, G ¼ connection) with NAMUR rib using adapter plate for
NAMUR rib/interface (order no. 1400-6751)
and screw fittings for 6×1 pipe, G ¼/G ¼ connection, made of zinc-plated steel 1400-6752
and screw fittings for 6×1 pipe, G ¼/G ¼ connection, made of CrNiMo steel 1400-6753
and screw fittings for 10×1 hose, G ¼/G ¼ connection, made of polyamide 1400-6756
Mounting kit for linear actuators (350/355/700/750 cm² actuator area, G 3/8 connection) with NAMUR rib using adapter
plate for NAMUR rib/interface (order no. 1400-6751)
and screw fittings for 8×1 pipe, G ¼/G 3/8 connection, made of zinc-plated steel 1400-6754
and screw fittings for 8×1 pipe, G ¼/G 3/8 connection, made of CrNiMo steel 1400-6755
and screw fittings for 10×1 pipe, G ¼/G 3/8 connection, made of polyamide 1400-6757
Mounting kit for linear actuators (175/240 cm² actuator area, G ¼ connection)
with pipe fitting, G ¼/G ¼ connection, made of CrNiMo steel 1400-6759
Mounting kit for Type 3353 Angle Seat Valve
with adapter plate for NAMUR interface, 1.4301 1400-3001
Mounting blocks and accessories for mounting solenoid valves to Type 3277 Linear Actuators
Designation Order no.
Mounting block for Type 3277 Linear Actuator with mounted Types 3793, 3766, 3767 and 3730 Positioners
G ¼ connection 1400-8813
¼ NPT connection 1400-8814
Pressure gauge mounting block, 1x Output and 1x Supply, made of stainless steel/brass (for mounting block) 1400-6950
Piping for actuator with "stem retracts" fail-safe action
240 cm² actuator area, zinc-plated steel 1400-6444
240 cm² actuator area, CrNiMo steel 1400-6445
350 cm² actuator area, zinc-plated steel 1400-6446
350 cm² actuator area, CrNiMo steel 1400-6447
700 cm² actuator area, zinc-plated steel 1400-6448
700 cm² actuator area, CrNiMo steel 1400-6449