Site Model

OD Cabinet TP48200 with Installation AMIA


Max Config 3ABIA

SITE ID :135305
SITE NAME :GALAXY_MALL_3_4G
RECTIFIER Model :HuaweiTP48200
RECTIFIER TYPE :TP48200 A– HD15A6
SERVICE CABINET :TP48200 (650x650x1600MM)
SYSTEM MODULE :1xASIA + 3xABIA Max

1 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 1.
2.
Battery VRLA/ Lithium up to 2 banks
Proposed AMIA / BTS position Space
From Front and Bottom 1U
3. Module Rectifier up to 4 unit
4. DC circuit Breaker
4 4

3 4 3

AMIA 2
2
2

1
1
1

2 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 – DDF External Alarm Exisiting
1. Existing External Alarm
2. AMIA / BTS position Space From
Front and Bottom 1U
3. If No LSA Install on existing,
connection will be direct to UIM
1
Board ( Wiring diagram support by
EAC
IOH)
1 1

AMIA 2 2
2
2

DDF

External Alarm
1

3 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 – MCB Existing

1. AC Input main Breakers


2. AC SPD
3. LLVD Circuit Breakers
4. BLVD Circuit Breakers
5. Battery Circuit Breakers

BLVD LLVD

1 2 3 4 5 6 7 8 9 10 11 12

16A 16A 32A 32A 63A 63A 63A 63A 80A 80A 125A 125A

Airscale FXDB/ FXED/ FRGU/


BBU ARDA AREA ARGA

4 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 A– HD15A6 (MCB Existing)

1. AC Input main Breakers


2. AC SPD
3. LLVD Circuit Breakers
4. BLVD Circuit Breakers
5. Battery Circuit Breakers

BLVD LLVD

1 2 3 4 5 6 7 8 9 10 11 12

16A 16A 32A 32A 63A 63A 63A 63A 80A 80A 125A 125A

Airscale FXDB/ FXED/ FRGU/


BBU ARDA AREA ARGA

5 27/09/2022
Commercially Confidential
Nokia internal use
AMIA Extender Installed (Right and Left)

2 cm 6 cm

AMIA Extender

6 27/09/2022
Commercially Confidential
Nokia internal use
Cable Holder /Cable Management

Rack door
Rack door
opened
closed
• Optical cables are installed within/stick to
cable holder
• Confirmed that optical cable is not over-
bended when door is closed
• Clear alarm on BTS related with optical cable

7 27/09/2022
Commercially Confidential
Nokia internal use
Add “Prop” AMIA to back-Cabinet :

Prop (“ganjalan”)

To give equal space between AMIA-Rear


and Back-Cabinet for airflow
8 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 Bottom Back View

1. Cable gland hole not


available at bottom
back side
2. Cabinet Junction Note :
Cabinet Huawei TP48200 are not
available cable gland at bottom back
side

9 27/09/2022
1 1
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 Back View – Excess cable holder not available
Note :
Cabinet Huawei TP48200 are not available Excess
holder cable optic

1. Excess Cable Holder


Not available
2. Cabinet Junction

2
1
1 In case no cable holder :
Extra or excess cables are neatly wound
1 with special cable ties and
installed on the horizontal tower tray
(Indosat space) or outdoor cable rollers
on the BTS cabinet

10 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 RIGHT Side View – Not Available Cable Gland Allocation

Front 1
1
RIGHT SIDE
1

11 27/09/2022
Com mercially Confidential
Nokia internal use
Cabinet Huawei TP48200 LEFT Side View – Not Available Cable Gland Allocation

Front
1
LEFT SIDE

12 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 FRONT Bottom View – Gland Allocation

1
LEFT SIDE
2
Front

1
1 RIGHT SIDE

13
27/09/202
Commercially Confidential
2
Nokia internal use
Cabinet Huawei TP48200 MIDDLE FRONT Side View – Cable Gland Allocation

1
1
4
4

Middle FRONT
LEFT

14 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Airflow

Hot Air

Fresh Air

15 27/09/2022
Commercially Confidential
Nokia internal use
Design Cabinet

16 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm Test
and Simulation
- Nokia will create standart IO
- Ex H3i site Activate External alarm as
existing condition

17 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm Cabinet Huawei TP48200
FSAH

Main Fail

Rectifier Fail

BLVD Fail

Arrester AC+DC Fail

Load Fail

Door Open
18 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm TP48200 – LLVD1
Before After

Before After

19 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm TP48200 – LLVD2
Before After

Before After

20 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm TP48200 – Temperature High
Before After

Before After

21 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm TP48200 – Arrester DC Failed
Before After

After
Before

22 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm TP48200 – Door Open
After
Before

Before After

23 27/09/2022
Commercially Confidential
Nokia internal use
Rectifier Service Cabinet
TP48200

24 27/09/2022
Commercially Confidential
Nokia internal use
Rectifier Sub Rack Installation Check
 Key points:
1
⚫ Ensure Sub Rack and modules installed as per planned (Site
Design) i.e. position, type and quantity
⚫ Ensure Cabinet and modules Installation are securely seated
and properly installed
⚫ Ensure all cable plugs are securely seated and tightened

Item Check :
2 2
Markin
Descriptions
g No
New Rectifier Cabinet Type and positioned as shown in
1
site Design
Sub Rack is clean and not scratched or dented or
1
damage
Sub Rack are screwed in firmly with all the proper
2
bolts/No Missing Screw
Sub rack is Grounded to the bus bar as per site
3
specifications

25 27/09/2022
Commercially Confidential
Nokia internal use
Rectifier Module Installation
3

Item Check : 1

Mark
ing Descriptions
No
Number and placement of module should be installed as per Site
1 Design (including add new rectifier module on existing Rectifier)

2 Confirm full set of DC MCBs installed as per Site Design


All circuits/MCBs must be connected according to the standard
2 sequence
3 All empty slots must be closed with dummy panels 2

26 27/09/2022
Commercially Confidential
Nokia internal use
Battery Installation

Item Check :

Marking
Descriptions
No
Number of New Battery & Capacity (Ah) should be
1
installed as per Site Design
Battery temperature sensor installed as per Site
2
Design

1
Note :
Space or Gap
2 between battery is 3
27 27/09/2022 hole or 1 U
Commercially Confidential
Nokia internal use
AC Input Power Rectifier Installation

Item Check :
1

Marking Descriptions
No
1 AC Cable type installed as site design
AC Power cable plugs are securely seated at both end
1
(Rectifier part and ACPDB part)
All Power cable label must be clear and neat and printed at
1
both end

28 27/09/2022
Commercially Confidential
Nokia internal use
DC Output and Battery Installation 1

Item Check :
Marking
Descriptions
No
1 DC Cable type installed as site design
DC Power cable plugs are securely seated at both end
1
(Rectifier part and Battery part)
All Power cable label must be clear and neat and printed at
1
both end
The excess power cables must be cut off and coiling of
1
remaining are not allowed 1
Verify that all power cable wiring and heat shrinkable uses
1
correct colors’
2 All battery cable connection is done properly

29 27/09/2022
Commercially Confidential
Nokia internal use
Grounding Cable Installation of
Service Cabinet 1

Item Check : 2

Marking
Descriptions
No
Grounding cable connected to Cabinet door, Sub rack
1
and/or modules and integrated to Grounding bar
2 1 x Grounding cable from each equipment to bus bar
Internal grounding wire uses Green and yellow color and
2
connect to rack grounding bar 3
All grounding connection must be terminated with cable
2
lugs
2 Is terminated using heat-shrink/ sealant tape
3 Grounding cable plugs are securely seated

30 27/09/2022
Commercially Confidential
Nokia internal use
31 27/09/2022
Commercially Confidential
Nokia internal use