Standar Instalasi - Indosat - Cabinet For TP48200 - Dwi - Review Nurudin - Rev1
Standar Instalasi - Indosat - Cabinet For TP48200 - Dwi - Review Nurudin - Rev1
SITE ID :135305
SITE NAME :GALAXY_MALL_3_4G
RECTIFIER Model :HuaweiTP48200
RECTIFIER TYPE :TP48200 A– HD15A6
SERVICE CABINET :TP48200 (650x650x1600MM)
SYSTEM MODULE :1xASIA + 3xABIA Max
1 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 1.
2.
Battery VRLA/ Lithium up to 2 banks
Proposed AMIA / BTS position Space
From Front and Bottom 1U
3. Module Rectifier up to 4 unit
4. DC circuit Breaker
4 4
3 4 3
AMIA 2
2
2
1
1
1
2 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 – DDF External Alarm Exisiting
1. Existing External Alarm
2. AMIA / BTS position Space From
Front and Bottom 1U
3. If No LSA Install on existing,
connection will be direct to UIM
1
Board ( Wiring diagram support by
EAC
IOH)
1 1
AMIA 2 2
2
2
DDF
External Alarm
1
3 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 – MCB Existing
BLVD LLVD
1 2 3 4 5 6 7 8 9 10 11 12
16A 16A 32A 32A 63A 63A 63A 63A 80A 80A 125A 125A
4 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 A– HD15A6 (MCB Existing)
BLVD LLVD
1 2 3 4 5 6 7 8 9 10 11 12
16A 16A 32A 32A 63A 63A 63A 63A 80A 80A 125A 125A
5 27/09/2022
Commercially Confidential
Nokia internal use
AMIA Extender Installed (Right and Left)
2 cm 6 cm
AMIA Extender
6 27/09/2022
Commercially Confidential
Nokia internal use
Cable Holder /Cable Management
Rack door
Rack door
opened
closed
• Optical cables are installed within/stick to
cable holder
• Confirmed that optical cable is not over-
bended when door is closed
• Clear alarm on BTS related with optical cable
7 27/09/2022
Commercially Confidential
Nokia internal use
Add “Prop” AMIA to back-Cabinet :
Prop (“ganjalan”)
9 27/09/2022
1 1
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 Back View – Excess cable holder not available
Note :
Cabinet Huawei TP48200 are not available Excess
holder cable optic
2
1
1 In case no cable holder :
Extra or excess cables are neatly wound
1 with special cable ties and
installed on the horizontal tower tray
(Indosat space) or outdoor cable rollers
on the BTS cabinet
10 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 RIGHT Side View – Not Available Cable Gland Allocation
Front 1
1
RIGHT SIDE
1
11 27/09/2022
Com mercially Confidential
Nokia internal use
Cabinet Huawei TP48200 LEFT Side View – Not Available Cable Gland Allocation
Front
1
LEFT SIDE
12 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Huawei TP48200 FRONT Bottom View – Gland Allocation
1
LEFT SIDE
2
Front
1
1 RIGHT SIDE
13
27/09/202
Commercially Confidential
2
Nokia internal use
Cabinet Huawei TP48200 MIDDLE FRONT Side View – Cable Gland Allocation
1
1
4
4
Middle FRONT
LEFT
14 27/09/2022
Commercially Confidential
Nokia internal use
Cabinet Airflow
Hot Air
Fresh Air
15 27/09/2022
Commercially Confidential
Nokia internal use
Design Cabinet
16 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm Test
and Simulation
- Nokia will create standart IO
- Ex H3i site Activate External alarm as
existing condition
17 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm Cabinet Huawei TP48200
FSAH
Main Fail
Rectifier Fail
BLVD Fail
Load Fail
Door Open
18 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm TP48200 – LLVD1
Before After
Before After
19 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm TP48200 – LLVD2
Before After
Before After
20 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm TP48200 – Temperature High
Before After
Before After
21 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm TP48200 – Arrester DC Failed
Before After
After
Before
22 27/09/2022
Commercially Confidential
Nokia internal use
External Alarm TP48200 – Door Open
After
Before
Before After
23 27/09/2022
Commercially Confidential
Nokia internal use
Rectifier Service Cabinet
TP48200
24 27/09/2022
Commercially Confidential
Nokia internal use
Rectifier Sub Rack Installation Check
Key points:
1
⚫ Ensure Sub Rack and modules installed as per planned (Site
Design) i.e. position, type and quantity
⚫ Ensure Cabinet and modules Installation are securely seated
and properly installed
⚫ Ensure all cable plugs are securely seated and tightened
Item Check :
2 2
Markin
Descriptions
g No
New Rectifier Cabinet Type and positioned as shown in
1
site Design
Sub Rack is clean and not scratched or dented or
1
damage
Sub Rack are screwed in firmly with all the proper
2
bolts/No Missing Screw
Sub rack is Grounded to the bus bar as per site
3
specifications
25 27/09/2022
Commercially Confidential
Nokia internal use
Rectifier Module Installation
3
Item Check : 1
Mark
ing Descriptions
No
Number and placement of module should be installed as per Site
1 Design (including add new rectifier module on existing Rectifier)
26 27/09/2022
Commercially Confidential
Nokia internal use
Battery Installation
Item Check :
Marking
Descriptions
No
Number of New Battery & Capacity (Ah) should be
1
installed as per Site Design
Battery temperature sensor installed as per Site
2
Design
1
Note :
Space or Gap
2 between battery is 3
27 27/09/2022 hole or 1 U
Commercially Confidential
Nokia internal use
AC Input Power Rectifier Installation
Item Check :
1
Marking Descriptions
No
1 AC Cable type installed as site design
AC Power cable plugs are securely seated at both end
1
(Rectifier part and ACPDB part)
All Power cable label must be clear and neat and printed at
1
both end
28 27/09/2022
Commercially Confidential
Nokia internal use
DC Output and Battery Installation 1
Item Check :
Marking
Descriptions
No
1 DC Cable type installed as site design
DC Power cable plugs are securely seated at both end
1
(Rectifier part and Battery part)
All Power cable label must be clear and neat and printed at
1
both end
The excess power cables must be cut off and coiling of
1
remaining are not allowed 1
Verify that all power cable wiring and heat shrinkable uses
1
correct colors’
2 All battery cable connection is done properly
29 27/09/2022
Commercially Confidential
Nokia internal use
Grounding Cable Installation of
Service Cabinet 1
Item Check : 2
Marking
Descriptions
No
Grounding cable connected to Cabinet door, Sub rack
1
and/or modules and integrated to Grounding bar
2 1 x Grounding cable from each equipment to bus bar
Internal grounding wire uses Green and yellow color and
2
connect to rack grounding bar 3
All grounding connection must be terminated with cable
2
lugs
2 Is terminated using heat-shrink/ sealant tape
3 Grounding cable plugs are securely seated
30 27/09/2022
Commercially Confidential
Nokia internal use