Calculation of concrete compressive strength

*)
DX 450-SCT: Standard-method, Green Cartridge, power setting 1
Date: 17/02/2023 Powder-actuated test tool: DX450-SCT L140 Air temperature: - Mix temperature: - Test by: Jishan
Type and serial number: HAT28_01 / 21293

Gallery/tunnel: C883 Stage: Stage 8(Heading) Location:Entrance 3 Tensile tester: HILTI Mark 5

Aggregrate size: 10mm Cement: GR30 Accelerator: SA160 Time of completing spraying t0 = 16/2/2023 12:30

(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
Time after Mean value
Stud type and Penetration Concrete cube
Time spraying Standoff Pullout load Nu Actual pullout Nu,/hnom
Total length hnom= Ltot-NVS Nu,/hnom strength Calibr.
[h:min.] completed NVS [mm] Reading, [N] load Nu, **) [N] (ΣNu,/hnom)/10
(1)- t0 [h:min.] Ltot [mm] [mm]
[N/mm]
Curve [Mpa]

t= All measurements and calculations in the same order as studs driven


33 47 3000 3000 64
31 49 3500 3500 71
30 50 4000 4000 80
30 50 3800 3800 76
17/02/2023 29 51 3000 3000 59
9hr 80 65.44 11.86
1:30:00 pm 28 52 3100 3100 60
29 51 3000 3000 59
30 50 3000 3000 60
32 48 3200 3200 67
31 49 2900 2900 59
*) Green 1 for standard equipment of the DX 450-SCT, In case a tool DX 450 with a piston guide L125 is used, Σ= 654.37
the power setting amounts to 1.625

**) this column is reserved for corrected pullout loads, only necessary in case the former Hilti tester 4 is used. If the tester Mark 5 is used:Value(7)= Value(6).