FIRE
FIGHTING
[lta NUON
ON aed
Peano
Te eee eo
Bol en ee}
Tien nage aed
Ne een)petrol, oil, etc.
NON-SMOKING
AREA
stopped
CAUSES OF FIRE |
+ Poor house keeping: Cotton,
clothes, paper, etc. are the
sources of ignition. They
should be kept away from
combusting materials like
‘Smoking; Careless smoking in
% non smoking areas should be
+ Welding/ Gas cutting: Gas
welding or oxy-acetylene
cutting produces flying sparks
which falls on inflammable
material and fire takes place.
IN A BUILDING
Rok «1
lack of awareness, incorrect use
of inflammable and electric
equipment, etc.
Kitchen: Most sensible area ina
building. Oil fire and gas fire can
take place.
Electrical panel room: No
material should be stored in
electrical panel room. Even a
small short circuit can lead into
big fire break.|
CLASSIFICATION OF FIRE
1.A Class (Solid, wood, paper, etc.)
2.B Class (Oil, paint, etc.)
3.€ Class (Electrical panel, wiring etc.)
4,D Class (Metal, zinc, copper, etc.)
5.K Class (kitchen, cooking oil, etc.)
a
Flammable
Liquids
Equipment
Wood, Paper,
Cloth, Ete.
Grease, Oil,
Paint, Solvents
Live Electrical] Electrical Panel,
Motor, Wiring,
Etc.
Combustible | Magnesium,
Commercial
Cooking
Equipment
‘Aluminum, Etc.
Cooking Oils,
‘Animal Fats,
fegetable OilsFIRE FIGHTING SYSTEM &
EQUIPMENTS IN BUILDING1. SYSTEMS & EQUIPMENTS|
FIRE EXTINGUISHERS
1.Water type:
+ Removes heat ie,, cooling.
+ Only for A class fire.
2.Foam type:
+ Cutting of oxygen ie, smothering (or blanketing + cooling).
+ Only on A,B class fires.
3.CO2tyi
+ Displace oxygen ie., smothering.
+ Use only on B,C. class fires.
4.DCP type:
+ Cutting of oxygen ie., smothering.
+ Use only B,C.E class fires.
+ If ammonium phosphate is used then it can be used on A
class also.FIRE HOSE REELS
+ Fire hose reels are provided for use by
occupants as a ‘first attack’ firefighting
measure but may, in some instances, also be
used by firefighters.
+ Because hose reels are generally located next
to an exit, in an emergency it is possible to ;
reach a safe place simply by following the
hose.FIRE HYDRANT SYSTEMS
+ All fire hydrants shall be equipped with
an auxiliary gate valve installed between
the service line and the hydrant to _
permit repair or replacement of the A
hydrant without disruption of water 4
service. 2
+ All fire hydrants shall have two hose
outlets of two and one-half inches in
diameter, and one outlet of four inches
in diameter, with a five-inch Storz
adapter and cap.
ae atFIRE HYDRANT SYSTEMS
+ The tops of hydrants are painted in sonnet
colors to indicate how much flow they
can produce in gallons per minute.
(gpm)
* Blue ~ over 1,500 gallons per minute at
(gpm)
* Green - 1000 to 1,499 gpm.
* Orange - 500 to 999 gpm. 7
ot A a a
+ Red - less than 500 gpm|
AUTOMATIC SPRINKLER SYSTEM
Automatic sprinkler systems are one of the most
reliable methods available for controlling fires.
* Sprinklers Save Lives
* Reduces Risk of Damage
* Relatively Inexpensive
+ Low MaintenanceACCESSIBILITY OF SPRINKLER SYSTEM
All parts of the sprinkler system need to be
positioned so that there are no obstructions and
that it is accessible, in particular:
+ The control panels
+ The end-of-line test pipes
+ The pump room
* The reels connected to the network
If necessary, use metal fences or yellow lines
near these parts.
CLEARANCES FOR SPRINKLER SYSTEM [ JS
a
Definitely respect the clearances (the distance between
sprinkler deflector plates and the top of the stack). If you stack
the goods too high, the functioning of the system could be in
danger.DOWN-COMER
* An arrangement of fire fighting within the
building by means of down-comer pipe
connected to terrace tank through terrace pump,
gate valve and non-return valve and having
mains not less than 100 mm internal diameter
with landing valves on each floor/landing
+ It is also fitted with inlet connections at ground
level for charging with water by pumping from,
fire service appliances and air release valve at roof
level to release trapped air inside.DRY RISER
+ An arrangement of fire fighting
within the building by means of
vertical rising mains not less than
100 mm internal diameter with
landing valves on each floor/landing
which is normally dry but is capable
of being charged with water usually
by pumping from fire service
appliances.CONTROL ROOM
+ There shall be a control room on the
entrance floor of the building with
communication systern (suitable public
address system) to all floors and
facilities for receiving the message from
different floors. Details of all floor plans
along with the details of fire fighting
equipment and installation shall be
maintained in the Control Room.
+ The Control Room shall also have
facility to detect the fire on any floor
through indicator boards connecting
fire detection and alarm system on all
floors.2. EXITS & PASSAGESFIRE EXITS
Fire exit door should be given in each
floor.
All fire escapes shall be directly
connected to the ground.
Entrance to the fire escape shall be
separate and remote from internal
staircase.
+ Fire escape shall be constructed of non-
combustible materials.
+ Fire escape stairs shall have straight
flight not less than 125 cm wide with 25
cm treads and risers not more than 19.
cm.
+ Handrails shall be at a height not less
than 100 em.|
FIRE EXITS
+ Exit doorways shall open outwards, that is, away from the room, but shall not obstruct the
travel along any exit.
+ No door, when opened, shall reduce the required width of stairway or landing to less than
900 mm; overhead or sliding doors shall not be installed.
+ No exit doorway shall be less than 1000 mm in width except assembly buildings where
door width shall be not less than 2000 mm.
Doorways shall be not less than 2000 mm in height
Exit door shall not open immediately upon a flight of stairs; a landing equal to at least the
width of the door shall be provided in the stairway at each doorway; the level of landing
shall be the same as that of the floor which it serves
+ Exit doorways shall be openable from the side which they serve without the use of a key.
Mirrors shall not be placed in exit ways or exit doors to avoid confusion regarding the
direction of exit.
Every exit doorway shall open into an enclosed stairway or a horizontal exit of a corridor
or passageway providing continuous and protected means of egress.|
FIRE LIFTS
* Provision of the lifts shall be made for
all multi-storeyed building having a
height of 15.0 m. and above.
+ Lift shall have minimum capacity of 8
persons and have closing doors which
can resist fire for atleast 2 hours
+ The speed of the fire lift shall be such
that it can reach to the top floor from
ground level within one minute.
+ Telephone/talk back communication
facilities may be provided in lift cars for
communication system and lifts shall
be connected to the fire control room
of the building.|
FIRE LIFTS
+ In case of fire, only fireman shall
operate the fire lift. In normal course, it
may be used by other persons
+ Each fire lift shall be equipped with
suitable inter-communication
equipment for communicating with the
control room on the ground floor of the
building,
+ The number and location of fire lifts in a
building shall be decided after taking
into consideration various factors like
building population, floor area,
compartmentation, etc
* Alternate power supply is provided 24/7
for these lifts
++ Fire rated Cage Roof
“ Fire rated Cage Panels
Fire rated Cage base|
EXTERNAL STAIRCASE
An external staircase is desirable to be provided for high rise buildings.
External stairs, when provided shall comply the following:
+ External stairs shall always be kept in sound operable conditions.
+ All external stairs shall be directly connected to the ground.
+ Entrance to the external stairs shall be separate and remote from the internal staircase.
+ Care shall be taken to ensure that no wall opening or window opens on to or close to an
external stairs
+ The route to the external stairs shall be free of obstructions at all times.
+ The external stairs shall be constructed of non-combustible materials, and any doorway
leading to it shall have the required fire resistance.
+ No external staircase, used as a fire escape, shall be inclined at an angle greater than 45°
from the horizontal
+ External stairs shall have straight flight not less than | 250 mm wide with 250 mm treads
and risers not more than 190 mm. The number of risers shall be limited to 15 per flight.|
EXTERNAL STAIRCASE
+ Handrails shall be of a height not less than 1000 ram and not exceeding 1200 mm. There
shall be provisions of balusters with maximum gap of 150 mm.
+ The use of spiral staircase shall be limited to low occupant load and to a building not
exceeding 9 m in height.
* A spiral stair case shall be not less than 1 500 mm in diameter and shall be designed to
give adequate headroom.
+ Unprotected steel frame staircase will not be accepted as means of escape. However,
steel staircase in an enclosed fire rated compartment of 2 h will be accepted as means of
escape|
CORRIDORS AND PASSAGEWAYS
+ Exit corridors and passageways shall be of width not less than the aggregate required
width of exit doorways leading from them in the direction of travel to the exterior.
+ Where stairways discharge through corridors and passageways, the height of corridors
and passageways shall be not less than 2.4 m.
+ All means of exit including staircases lifts lobbies and corridors shall be adequately
ventilated.|
FIRE TOWER
+ Fire towers are the preferred type of escape route for storeyed buildings and these shall
be considered as the safest route for escape. Their number, location and size shall depend
on the building concerned, and its associated escape routes.
+ In high rise buildings with over 8 storeys or 24 m in height, at least one required means of
egress shall preferably be a fire tower.
+ The fire towers shall be constructed of walls with a 2h fire resistance rating without
‘openings other than the exit doorways, with platforms, landings and balconies having the
same fire-resistance rating.
+ Ramps shall comply with all the applicable requirements for stairways regarding
enclosure.|
HORIZONTAL EXITS
+ The width of horizontal exit shall be same as for the exit doorways.
+ Ahorizontal exit shall be equipped with at least one fire/smoke door of minimum 1h fire
resistance, of self-closing type. Further, it is required to have direct connectivity to the fire
escape staircase for evacuation.
+ For buildings more than 24 m in height, refuge area of 15 m? or an area equivalent to 03
'm per person to accommodate the occupants of two consecutive floors, whichever is
higher, shall be provided as under:
+ The refuge area shall be provided on the periphery of the floor or preferably on a
cantilever projection and open to air at least on one side protected with suitable railings.RESTRICTING HORIZONTAL AND
VERTICAL SPREAD OF FIRE
Generally walls restrict horizontal movement and slabs restrict vertical movement
of fire.
+ Interior or barrier or enclosure wall Propagation of fire, smoke, gas or fume
through the openings or shafts or penetrations of fire resistive floors and walls
shall be restricted by sealing with an approved material which shall have a fire
resistance rating at least equal to that of the floor-wall assembly. The sealing
material shall be capable of preventing passage of flame and hot gases
sufficient to ignite cotton waste when tested in accordance with ASTM EN19,
Exterior walls Permitted unprotected openings in the exterior wall in two
consecutive floors lying within 1.5 m laterally or vertically shall be separated
with flame barriers as similar as sunshades or cornices or projected wall at
least 750 mm from the external face of the exterior wall. The flame barrier shall
have a fire resistance rating of not less than three-fourths hour.3. EVACUATION &
SIGNAGES|
FIRE SAFETY PLAN
+ Intended to reduce the destruction caused [21 re
by fire. EMERGENCY EVACUATION PLAN
+ Fire safety measures include those that are
intended to prevent ignition of an IN CASE |GROMTEN I) emace 4
OF FIRE om
uncontrolled fire, and those that are used to. |=
limit the development and effects of afire | 1!
after it starts. =
+ Natural disasters, fires, hazardous leaks and _| 2 Stet
other disaster events are reasons for
companies to have a safe evacuation that ana
needs the designing of an emergency plan. —y
+ First of all, in drawing an emergency planis | 4 sim,
to put an evacuation manager that will rm
develop an emergency evacuation =
procedure. fe]SIGNAGES & ALARM SYSTEM
>
ala
oN
*
3
i>!
iliil4. SETBACKSSETBACKS FOR BUILDINGS
Section : As per table 2 of section 8.2.3.1 of part III
of N.B.C.|
SETBACKS FOR BUILDINGSSETBACKS FOR BUILDINGS
For other Occupancies the setbacks shall have to be allowed as follows:
1. Educational buildings - Except for nursery schools, the open space shall not be
less than 6 meters
2.Institutional buildings - open space shall not be less than 6 meters.
3. Assembly building - Except in front, open space shall not be less than 6 meter
and front open space shalll not be less than 12 meters.
4.Business/Mercantile & storage building - Open space around the building shall
not be less than 4.5meters. It can be relaxed in certain circumstances.
5, Industrial/Hazardous building - Minimum 4.5 meters open space shall be kept
around the building for the height up tolé meters. Open space shall be
increased by 0.25meters for next each 1 meter height of the building.5. BUILDING FIRE
PROTECTION DESIGNTHE BASICS OF BUILDING FIRE PROTECTION DESIGN
1.Understand which Codes Govern Fire Protection Systems.
2. Determine What Fire Protection Systems are Required On Design Projects.
3.Evaluate the Water Supply.
4.Which Fire Protection Systems are in General Use and There Principles of Operation.
5.Required Testing & Records.|
CLASSIFICATION OF BUILDING BASED ON OCCUPANCY
All buildings, whether existing or hereafter erected shall be classified according to
the use or the character of occupancy in one of the following groups:
+ Group A Residential
+ Group B Educational
+ Group C Institutional
+ Group D Assembly
+ Group E Business
+ Group F Mercantile
+ Group G Industrial
+ Group H Storage
+ Group 3 HazardousMINIMUM REQUIREMENTS FOR FIRE FIGHTING INSTALLATIONS
Sg |= "—s 22 2 =
=|=|2) = |S
ee | |
= =
seMINIMUM REQUIREMENTS FOR FIRE FIGHTING INSTALLATIONS
S| See | |e |
cre SheeMINIMUM REQUIREMENTS FOR FIRE FIGHTING INSTALLATIONS
eee) Seas | ES | See | Sos
=" =MINIMUM REQUIREMENTS FOR FIRE FIGHTING INSTALLATIONS
iil eekeels os fe k aehel
sais | EE) +
aj pide of 8 aha
Aree + be ba
Wi fe EO ek
mt HEE | [+E
mu TEE = aH
1H fee RF ae
i nn a |
aay fe ~~ = = i
iHMINIMUM REQUIREMENTS FOR FIRE FIGHTING INSTALLATIONS
Same Same | | |
PS ae aie
aMINIMUM REQUIREMENTS FOR FIRE FIGI
z
5S, || See | ES | ES | os
Pr Sa
a ae
aMINIMUM REQUIREMENTS FOR FIRE FIGHTING INSTALLATIONS
Sooo swomee See
se aa od er
eee
al a aA
coeff pe |e | me | ae fee)
TsMINIMUM REQUIREMENTS FOR FIRE FIGHTING INSTALLATIONSMINIMUM REQUIREMENTS FOR FIRE FIGHTING INSTALLATIONSMINIMUM REQUIREMENTS FOR FIRE FIGHTING INSTALLATIONS6. CASE STUDIES|
CASE STUDY-1
MAPLE HIGH STREETMethod of working of Fire Pumps
+ There is master pump when the
pressure gets down first 6kg one starts
+ Incase a big fire accident occurs then
hydrant pump starts which is 1Shp
pump
+ How we distinguish the pump? They
depend on hp and kilo watts
+ Hydrant pump is also called as spare
pump
+ They come in 5 nomes only and its
7ohp
+ Jockey capacity is 15 hp
+ Sprinkler pump is having a separate
pump incase if it is damaged
Control PanelMethod of working of Fire Pumps
+ Dg pump - Diesel Generator Pump its
of 94hp
Incase the fire occurs electricity cuts
then dg pump activates itself
+ 15-20 meters space is provided which is
must
Also 10-15 meters is must left around
the building for fire vehicle to go
around
+ The pipes will be connected to the total
building in all floors
Fire Hose Cabinet+ Depending upon the water body like
fire hydrant needs more water?
+ On basis of nomes 8kg pressure for
24mteres is must if it needs more
height the we can increase the
pressure
+ There are three types of pipes are there
one is sprinkler pipe-150, fire hydrant
pipe-100, riser is of 150
+ Sprinkler pipe is distributed into two
types one 6inch and one is 4 inch but
main will be 6inch onlySteps in extinguishing fire
+ One tank will be given top which
is called over head tank it of
60,000-80,000 liters as per this
building
* If ground tank fails tp supply
water then over head tank will be
used and if this also fails to
supply water then back of the
building there is provided a pipe
which the fire vehicle comes and
connects which gives water
supplyhi
gfire
Steps in extingu'
* Everything is automatic not
manually maintained
+ This is the other method of supply
of water which are placed so that
the fire fighting vehicle would
attach to the pipes and supply the
water takes placeThere are three types of water supply
Rrovided for fire extinguishing_
+ lakh litre of water tank is provided
underground and is circulated through
pump system
+ If this system fails overhead water tank of
60,000 lit is provided which is directly
connected to the system
+ If this system also fails water from the fire
fighting vehicles can be supplied into the
main system by the pipes given outside
the building which connects externally
Standpipes Provided Outside The BuildingCASE STUDY-2
PEOPLE'S HOSPITALMethod Of Working.
Fire Exits: 9 - of which 8 staircases, 1 ramp
Staircase width - (standard)
Fire Control Room: Storage of building
plans, Hose pipes, Hose reel, Officer’s desk
Fire pump house: Panel for control of
water pumps, 2 water pumps 25 and 75
horsepower respectively, pressure gauge
to display water pressure through pumps,
underground water storage tank
Pumps are tested weekly to ensure they
are in proper working condition.
They have a separate pipeline system that
is wholly automatic and is spread
throughout the building.
‘Once activated through the main panels,
no other fire fighting equipment is
required.Method Of Working_
+ Fire pump house: Panel for control of
water pumps, 2 water pumps 25 and 75
horsepower respectively, pressure gauge
to display water pressure through pumps,
underground water storage tank.Plan Showing Way To Exit In Case Of Fire