3343 (10) Prueba Final-200 HP

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Equipment Test Report

Prepared for

INOPHOS

Equipment Tested:
U.s
200 hp

Job #: 3343 - 10

Test Description: Final a estator


Test Stage:
Test Operator: LUIS ENRIQUE CUPIL RODRIGUEZ
Equipment Test Report
Customer: INOPHOS

Equipment Information
Motor ID 200 hp Operating Volts 460
Equipment Tag 1800 RPM 1800
Location Innophos Power 200 HP
Manufacturer U.s AC/DC AC

Test Information
Test Date/Time: 23/12/2021 - 14:33:08
Winding Temp: 30 °C
Job # 3343 - 10
Test Description Final a estator
Test Stage
Operator LUIS ENRIQUE CUPIL RODRIGUEZ
Test Equipment # ITIG II DIMISA
PP ID#

Off-line Test Data


Winding Resistance @20 °C
Lead 1-2 Ohms 0.018773
Lead 2-3 Ohms 0.018740
Lead 1-3 Ohms 0.018748
Max Delta R (%) 0.2
Volts µAmps MOhms@40°C
Meg. @1min. 500 0.00 5000
DAR DAR = NC
PI PI = NC
Volts µAmps
Hipot 1920 0.00

Pass/Fail Results
Surge PASS
MegOhm PASS
Hipot PASS
Hipot Step Test PASS
Ohms Balance PASS
Off-line Equip. Rating PASS

Low Voltage AC Test Data


Capacitance (nF) Cap D Factor Inductance (mH) Impedance Phase Angle Q Factor
Lead 1-2 53.830 0.008 1.351 8.53 84.8 10.91
Lead 2-3 1.351 8.52 84.8 11.06
Lead 1-3 1.348 8.51 84.7 10.71
Balance 0.2% 0.2% 0.1% 3.2%

iTIG Test Report Pro by Electrom Instruments 7.3.0 27/12/2021 - 11:05:25 a. m.


Equipment Test Report

Hipot Step Test


Step # Volts µAmps
1 195 0.00
2 385 0.00
3 575 0.00
4 765 0.00
5 960 0.00
6 1150 0.00
7 1345 0.00
8 1535 0.00
9 1725 0.00
10 1920 0.00

Hipot Step Test


0.10

0.09

0.08

0.07
23/12/2021
0.06
14:33:08

µAmps 0.05

0.04

0.03

0.02

0.01

0.00
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Volts

iTIG Test Report Pro by Electrom Instruments 7.3.0 27/12/2021 - 11:05:25 a. m.


Equipment Test Report

Multi-Step Meg. Test


Mins. Volts µAmps MOhms@40°C
0.5 500 0.00 5000
1.0 500 0.00 5000
1.1 500 0.00 5000

Multi-Step Meg. Test


6000

5000

Test Voltage: 500


4000
23/12/2021
14:33:08

MOhms 3000

2000

1000

0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
Time (Min.)

iTIG Test Report Pro by Electrom Instruments 7.3.0 27/12/2021 - 11:05:25 a. m.


Equipment Test Report

AC Off-line Surge - Summary

Recommended Voltage: 1920


Voltage Reached:
1898 / 1898 / 1898
Wave Difference L1-L2: 1.5% 1
Wave Difference L2-L3: 2.1%
Wave Difference L3-L1: 2.0%
2

Surge Result: PASS 3

0 40 80 120 160 200 240 280 320 360 400


µSecs

Lead 1-2

1
2

0 40 80 120 160 200 240 280 320 360 400


µSecs

Lead 2-3

2
3

0 40 80 120 160 200 240 280 320 360 400


µSecs

Lead 3-1

3
1

0 40 80 120 160 200 240 280 320 360 400


µSecs

iTIG Test Report Pro by Electrom Instruments 7.3.0 27/12/2021 - 11:05:25 a. m.