MS For LV SWGR & MCC

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 22

SWCC STAMP: CONTRACTOR’S STAMP:

Signature:

A Issued for Information Ibrahim Kamal Zhang Mingjun Zhang Jishou 31-OCT-2017

REV DESCRIPTION PREPARED CHECKED APPROVED DATE

KINGDOM OF SAUDI ARABIA ‫الـممـلـكــة العــربـيــة‬


‫الســعـوديـــة‬
‫المـؤســســــة العــامــة لتحــلـية الـمــيــاه الـمــالــحــة‬
SALINE WATER CONVERSION CORPORATION
‫ المرحلة‬-‫محطة ينبع لتحلية المياه المالحة وتوليد الطاقة الكھربائية‬
‫ الثالثة‬YANBU POWER AND DESALINATION
PLANT-PHASE-III

FICHTNER GMBH & CO. KG

SEPCOIII ELECTRIC POWER CONSTRUCTION


CORPORATION

PROJECT:
20314 TITLE:
LOCATION: Method Statement
West Coast
For
PACKAGE:
“P” Power Plant Electric Test ForL LV SWGR & MCC
SCALE: DOCUMENT No.: REV:

None S E P - 0 1 - Z A A - 6 D C - 0 1 3 A

SUBCONTRACTOR Sheet 1 of 22
PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :2 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

TABLE OF CONTENTS

1.0 PURPOSE 4
2.0 SCOPE 4
3.0 REFERENCE STANDARDS 4
4.0 DEFENITIONS & ABBREVIATIONS 5
5.0 RESPONSIBILITIES 5
6.0 PROCEDURES & WORK SEQUENCE 8
7.0 QUALITY CONTROL 24
8.0 HSE CONTROL 25
9.0 ATTACHMENTS OF SAFETY RISK ASSESSMENT 25

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :3 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

REVISION INDEX

A Issued for Information


Rev Description of Changes/Revision

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :4 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

1- PURPOSE
The main purpose of this document is to define the Low Voltage Switchgear (LV
SWGR) & MCC Site Acceptance Test (SAT) general sequence of Test Procedures for the
Saline Water Conversion Company.

2- SCOPE

This procedure shall apply to all type of Electrical LV SWGR [400 V] electrical test
procedure specified on the approved specification and relevant standards. This method
statement does not supersede the Vendor testing procedure, specification and safety pro-
cedure

3- REFERENCE STANDARDS
3-1- Project Engineering Specification
3-2- ANSI – American National Standards Institute
3-3- IEC – International Electro-technical Commission.
3-4- NEC – National Electrical Code
3-5- NEMA – National Electrical Manufacturing Association
3-6- NFPA – National Fire Protection Authority
3-7- Approved AFC and IFC Drawings

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :5 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

4- DEFINITIONS & ABBREVIATIONS

4-1- P.M. - Project Manager


4-2- C.M. - Construction Manager
4-3- Q.M. - QA/QC Manager/Delegate
4-4- Q.C.S - Quality Control Supervisor
4-5- C.S - Construction Supervisor
4-6- Q.C. - Quality Control
4-7- P&C - Planning and Control
4-8- Company - SWCC
4-9- Project - Yanbu Phase-3 Power Plant (Package-P)
4-10- Contractor - SPECO III
4-11- Sub-Contractor - Al Fanar T&C

5- RESPONSIBILITIES

5-1- Site Manager

Site manager has the final responsibility for the Electrical Components Testing and
safety control of Electrical Equipment Commissioning and entirely responsible for control of
progress and subcontractors.

5-2- Electrical Superintendent

Electrical Superintendent will be responsible for Preparation, Revision and Implemen-


tation of installation Method Statement., Establishment and execution of termination sched-
ule and sequence, review of work procedure and approval, Control of Document and
Drawings and to check Schedule and Material.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :6 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

5-3- Electrical Supervisor

Electrical Supervisor shall be responsible of Ensuring that the construction work is

carried out as per the project Specifications and Standards, Controls of materials and work-
ers at site, Notifies to Electrical Manager the completion of the preparation of site for inspec-
tion, Preparation of site for inspection, Initiates RFI for material receiving inspection, Checks

that construction work is ready for inspection and prepares RFI, Assist for inspection and
testing when required at site, Check for PPE in accordance with site condition, Check for the
equipment and material which are required for work.

5-4- Site Quality Manager

Site Quality Manager shall be responsible for Informing to company representatives

of the official inspection request when their presence is required to carry out inspection, En-
suring that inspections are performed in a timely manner and recorded as per specifications
and standard detailed drawings, as per ITP and/or inspection records requirements, Sub-

mission of inspection and test record to company for approval.

5-5- Site QC Inspector

Site QC inspector shall be responsible for conducting surveillance and inspection

duties for material receiving, all electrical & instrument works and ensure efficient recording
and reporting of results as required, Review all relevant documents and certificates, Raise
NCR for any discrepancies and shall receive all internal requests for inspection from Electri-

cal & Instrument Department, Facilitate invitation to company representatives that require

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :7 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

their presence, Control quality of whole work process, arranging the field inspection and re-

viewing required inspection documents, Control the work in accordance with SWCC stand-
ards and specifications.

5-6- Subcontractor Testing & Commissioning Manager

Subcontractor Testing & Commissioning Manager shall be responsible for Prepara-


tion and Revision of work schedule, checking the availability of testing equipment which is
required for work, reviewing all testing documents and certificates, controlling Sub-

contractor testing and commissioning team according to site condition, representing the test-
ing team in all meetings, preparing of daily activities report and the overall progress of test-
ing, reviewing of work procedure and site test format, submission of test reports and

drawings at the end of project, submission of NCR for any defective material to Contractor.

5-7- Subcontractor Testing and Commissioning Engineer

Subcontractor T&C Engineer shall be responsible for testing for the whole devices & equip-
ment that is included in SEPCO III contract, delivering daily activities and progress report to
Sub-Contractor project manager, delivering test format after being signed to Sub-Contractor

project manager, writing NCR for any defect materials and deliver it to Sub-Contractor pro-
ject manager.

5-8- Manufacturer / Vendor Representative

Manufacturer / Vendor Representative shall be responsible for supervising the Test


and making sure it is safe and will not defect the device under test, checking the NCRs from

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :8 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

Sub-Contractor and fix the technical difficulties, supporting the Sub-Contractor with the re-

quired Technical data and specification for the device under test, Confirmation for the Sys-
tem is ready for Energization.

6- PROCEDURES & WORK SEQUENCE

6-1- Current transformer (CT) test procedure

a- Test objective:

- This test is considered as one of the main test, it’ s aimed to test:

 Current transformer ratio.


 Current transformer polarity.
 Burden of current transformer.
 Knee point of current transformer.
 Current transformer winding resistance.
 Magnetization curve of current transformer.
 Insulation Test.

b- Required Equipment:

 Current transformer (CT) analyzer.


 Insulation Tester.

c- Mechanical check and visual inspection:

 Check tightness of all connection.


 Check ferrules.

d- Current transformer analyzer connection:

 CT analyzer has 4 leads, two should be connected to primary side which contains primary side
of CT and other two should be connected to secondary side of CT which you want to check its ra-
tio.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :9 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

 After connecting CT analyzer through laptop and using CT analyzer software, test can be started
and result can be printed out for CT ratio, CT polarity, CT burden, CT knee point & CT winding
resistance.
 This result should be compared with current transformer factory test and be sure that result within
acceptable tolerance.
 To measure the burden: Inject 1 ampere on secondary side of CT, and using multi-meter you can
measure voltage calculate burden by multiply voltage and current and compare it with CT burden.
 To test insulation: Using Insulation Tester by 1 kV injection for 1 minute, this test should be done
between primary to secondary and secondary to secondary But for Primary to Ground 5 kV injec-
tion for 1 minute.
 See figure.1 which shows CT analyzer connection for CT TEST.

Figure.1 CT analyzer connection

6-2- Voltage transformer (VT) test procedure:

a- Test objective:

- This test also is considered as one of the main test and its purpose is to test:

 Voltage transformer ratio.


 Voltage transformer polarity.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :10 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

 Voltage transformer winding resistance.


 Insulation Resistance Tester.

b- Required equipment:

 CPC100. (VT Tester)


 Multi-meter (Fluke).
 Insulation Tester

c- Mechanical checked and visual inspection:

 Check tightness of connection.


 Check ferrules.

d- Voltage transformer test connection:

 Connect two leads from CPC device to primary side of voltage transformer and other two lead of
CPC with secondary side of VT, then press start from VT page of CPC.
 Using CPC with same connection but from different page, you can measure winding resistance.
 To check the loop burden: inject the rated secondary voltage and measure the current. Burden
will be the injected voltage * measured current and then compare it with VT burden.
 Insulation test: Using Insulation Tester to test insulation by 1 kV injection for 1 minute, this test
should be done between primary to secondary and secondary to ground, But for primary to
ground 5 kilo volt injection for 1 minute.(Primary and Secondary Grounding will be removed in
that test)
 See figure.2 which shows connection of VT Test.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :11 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

Figure.2 show CPC100 connection to test

6-3- Contact Resistance Test for Busbar and ACB / MCCB:

a- Test objective:

 This test is aimed to measure the resistance of bus bar and for circuit breaker after being installed
in the site to avoid high resistive spots which may be results from welding or installing in the site.

b- Required equipment:

 Contact resistance Tester.

c- Contact resistance test connection

 Contact resistance device has 4 leads, two for current and others for voltage, it depend on cur-
rent injection on bus bar or circuit breaker then sense the voltage and calculate resistance by di-
vide voltage on current (ohm’ s law)
 Check the BB torqueing of all bolts and confirms the torque value as per factory inspection.
 Connect current leads between the device which you want to measure its resistance, connect
voltage leads on the same terminals (but Inside not outside) of current then adjust 100A injection
then hold your hand on contact resistance pushbutton, after few second the result will be dis-
played.
 See figure.3 which shows connection of Contact Resistance Test.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :12 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

Figure.3 shows contact resistance equipment connection

6-4- Miniature Circuit Breaker Test (MCB) and Fuse Link Rating.

a- Test objective:

 This test aimed to test the trip time characteristic of MCB if it is within limits or no and check MCB
auxiliary contact if it is available.

b- Required equipment:

 Current Source (Usually Sverker).


 Multi-meter.

c- Mechanical checked and visual inspection:

 Check tightness for all wires.


 Check ferrules.
 Check for physical damage or defect.

d- Test connection and procedure:

 Connect the Current Source (Sverker) direct to MCB, check MCB type and its rated current value.
 Inject from Sverker twice of its rated current and measure the trip time in which MCB will be
tripped, compare the measured trip time with its acceptable limit from MCB manual depending on
its type.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :13 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

 Auxiliary contact should be checked in both condition of MCB (open/close) and check that auxilia-
ry contact change its status from being open to close and vice versa, depending on its nature
Normally open or Normally close.
 If Fuse is used make sure that its connectivity is OK and confirm its Blowing Current Value is as
per drawing or no

6-5- Auxiliary relay/Trip& Lockout Relay/Timers Test:

a- Test objective:

 This test aimed to test relay’ s output contact, pick-up and drop off voltage, operating and reset-
ting time.

b- Required equipment :

 Controlled Voltage source [Usually Sverker]


 Multi-meter [used as Ammeter].
 Miniature Circuit Breaker 2Pole [MCB].

c- Mechanical check and visual inspection:

 Check tightness for all wires.


 Check ferrules.
 Check for physical damage or defect.

d- Test connection:

I. Check output contact:

 Our Auxiliary relay/Lockout Relay/Timer has several points, 2 used for Coil, before injecting any
voltage on Auxiliary relay's Coil, check contacts at its normal condition which mean Normally
Open (NO) contact is being opened and Normally Closed (NC) contact is being closed, Inject the
desired control voltage of Aux. coil (which is normally 220 volt DC), at which Aux. relay will pick
up that’ s mean its contact will change its position i.e NO contact will be closed and NC contact
will be opened.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :14 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

II. Pick-up and drop off current and voltage:

 Pick up voltage can be measured using voltmeter when the coil voltage is increased gradually
from Zero, the Aux. relay will operate (i.e Contacts change its normal status No will be closed and
vice versa) at a certain voltage. This voltage is called pick-up voltage, Record the reading of
voltmeter and Ammeter which is pick-up voltage and current.
 Drop-off voltage can be measured using voltmeter when the coil voltage on an operate relay is
decreased gradually, the relay will release (i.e its contact will return to its normal status) at a cer-
tain voltage. This voltage is called drop-off voltage, Record the reading of Ammeter which is drop-
off current.

III. Operating and resetting time:

 Adjust voltage source at the coil operation voltage of Aux. relay (in our case 220 V DC), To get
operating time, adjust sverker at (on+time location) and switched MCB ON, To get resetting time,
readjust voltage source at 220 volt DC and switch MCB OFF, For Timers the contacts operation
will happen after the Pick up by the desired Time Setting if it’ s on ON-Delay Mode and will
dropp off after losing the voltage by desired Time Setting if it’ s on OFF-Delay Mode.

IV. Burden test:

 Adjust voltage source (sverker) at 220 volt DC, select on position and make MCB ON.
 Record reading of Ammeter.
 Calculate burden by multiplying coil operated voltage and reading of Ammeter

6-6- Meters (Digital/Analogue) test:

a- Test objective:

 This test is aimed to calibrate and adjust the reading of Meters (Voltage, Current , Power, .. etc)

b- Required equipment:

 FREJA 300.

c- Mechanical checked and visual inspection:

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :15 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

 Checked tightness of all connections.


 Checked ferrules.
 Inspection for physical damage or defects.

d- Test connection and procedure:

 Set the VT ratio (for voltmeter) and CT ratio (for ammeter).


 Inject different values (min. 3 values) of current (in case of ammeter) and voltage (in case of
voltmeter) and compare the injected values with reading values, calculate error in each reading
and check that its percentage error within the acceptable range.

6-7- Current Transformer Secondary Loop by Secondary Injection:

a- Test objective:

 This test aimed to check all current transformer loop, starting from first panel and distributed in
the whole switchgear depending on scheme, check shorting facility in terminal block [if exist].

b- Required equipment:

 FREJA (used as current injection).


 Multi-meter.
 Mini-clamp.

c- Mechanical check and visual inspection:

 Check tightness of all connection.


 Check ferrules for the whole looping.
 Check the single earth point.

d- Test connection

 Connect three phase current from FREJA to secondary side of current transformer, inject three
phase current by different values and use mini-clamp to measure current in each phase and fol-
low the loop until the last point.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :16 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

 Check the whole loop burden by Injecting the rated secondary current (Usually 1 amp) at every
phase and measure the voltage for confirmation of the loop burden VA is small Value.

6-8- Voltage Transformer loop:

a- Test objective:

 This test is aimed to check the whole loop of VT starting from first panel and distributed in the
whole substation depending on scheme (i.e. metering or protection purpose)

b- Required equipment:

 FREJA.
 Multi-meter.

c- Mechanical check and visual inspection:

 Check all voltage transformer loops.

d- Test connection:

 Connect FREJA which considered as voltage source to secondary side of VT, inject three phase
voltage with different values on each phase and then use multi-meter to measure the voltage on
the whole loop starting from first panel to different location depending on the function of each VT.

6-9- CT Secondary Loop Test by Primary Injection:

Test objective:

 This test aimed to check that the selected ratio of current transformer is correct and current trans-
former relay setting is OK and considered as back-up test of CT loop.

Required equipment:

 Primary Injection Tester.


 Multi-meter.
 Mini-clamp.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :17 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

 Power-clamp meter.

Mechanical check and visual inspection:

 Check that all current transformer terminal block is tightened and normalized.

Test connection:

 Connect Primary Injection Tester to inject current on bus bar including current transformer.
 Start injection of current then using of mini-clamp, we can measure the current at each point of
the loop and read the primary current value on each relay as we did in the CT secondary Loop
Before

6-10- Switchgear Function Check and Schematic Wiring Diagrams:

a- Test objective:

 This test is considered as a major test or combined test for the whole work in switchgear panels
and a final phase for switchgear panels to confirm that everything on the Switchgear component
is working ok as per the expected function and to confirm that the wiring ferrules/tagging is as per
the Drawing.

b- Required equipment:

 Multimeter.

c- Mechanical check and visual inspection:

 Inspect for the whole panel if any missing or damage device which can be resulted from installa-
tion.

d- Test procedure:

 Segregation of DC loop inside panel, by switching on only one MCB and follow its loop and so on
for other DC MCB.
 DC Mix by Switching on all MCBs and Switching off one every time and confirm no DC is mixed
on its loop after switching off the MCB.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :18 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

 Check the circuit of closing command for circuit breaker.


 Check the circuit of opening command for circuit breaker.
 Check mechanical interlock.
 Check interlock of circuit breaker from close switch (CS) and bay control unit between CB and
earth switch.
 Check alarm signal from source up to relay.
 Check inter trip between Upstream and Lowstream CB
 Confirm the relay logic.
 Check the CB functional like (travelling contact, manual charging, manual close & open, CB Rack
in & out ,CB counter operation before and after test also check the CB Trip coil and close coil.
 Check the Internal and External wiring Ferrules/ tagging is as per the expected from the drawing.

6-11- Protection relay (Main relay):

a- Test objective:

 This test aimed to test function of main relay according to approved final setting for each one, but
here we generally discussed main function which should be exist in most of approved final set-
ting.

b- Required Equipment:

 FREJA 300.
 Multi-meter.
 Wires.

c- Mechanical check and visual inspection:

 Check for physical damage or defects.


 Check case earth.
 Check indication and LEDs.
 Check test switch for correct operation either shorting CT if exist or isolation of binary in-
puts/outputs.

d- Burden test

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :19 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

 Adjust voltage source at 220 volt DC.


 Record reading of Ammeter in case of all binary output deactivated and in case of binary output
activation.
 Calculate burden in case of normal operation (all binary output deactivated) and abnormal opera-
tion (in case of binary output activated) by multiplying voltage and reading of ammeter.
 Compare the result with existing burden exist in relay manual.

e- Test connection and test procedure:

i. Binary input/output check:

 To test binary input: Apply rated binary input DC voltage on each input and verify the status of the
input through relay’ s software or from relay’ s LCD [if exist].
 To test binary output: Using relay’ s software you can force binary output to close for certain time
and using multi-meter you can measure binary output contact resistance it should be around zero
which indicates binary output being closed.

ii. Measurements

 Set CT ratio and VT ratio which used to the relay by studying the scheme.
 By using FREJA we inject secondary rated voltage and secondary rated current
 Record the primary value reading at relay’ s screen.

iv. Relay Main Protection Function

 Refer to the manual of every relay type that will be under test.
 As per the approved final setting check every setting from the protection function
 By using FREJA we inject the required value of Current or/and Voltage required to cause the trip
and we confirm the pickup value as per the expected or not.
 For Timing Check we inject a value that is for sure in the tripping zone of the trip function and we
confirm the relay tripping is as per the expected/pre-calculated time of operation for the tripping
contacts.
 The Disturbance recorder of the relay to be checked for every Function tested to confirm the
recording capability of the device for fault analysis later if happened.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :20 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

6-12- Transducers Test:

Test objective:

 This test aimed to check that the Transducers used to report the Current/Voltage/Power Reading
to the DCS (Control System) is Ok and Transferring the expected value by 4~20 mA

f- Required equipment:

 Freja 300 For Injecting Voltage/Current/Power values as per the Transducer Type
 Multimeter with mA measurement.

g- Mechanical Check and Visual Inspection:

 Check for Physical Damage or Defects

h- Test connection:

 Connect the FREJA 300 Kit Voltage or/and Current terminals to the Transducers IN Terminals
using leads.
 Convert the Transducers Full Scale to Equivalent mA Current Value from 4 mA for Zero Injected
value up to 20mA for Sull Scale Injected Value.
 Take the reading of the Transducers OUT Terminals through Multimeter on mA mode and con-
firm the results are OK

6-13- General Procedures Points:

 For contact resistance test, applied current is 100 amperes.


 Contact resistance shall be tested section by section.
 The test voltage of the insulation resistance shall be 5 KV DC for 13.8 KV equipment and 2.5 KV
DC for 6.6 KV equipment.
 The voltage level of the hi-pot test shall be as per the vendor recommendation.
 During hi-pot test, the substation shall be free from scaffolding and only authorized parsons shall
be allowed to enter the substation.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :21 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

 All the power cables shall be disconnected from the switchgear during high-pot or insulation re-
sistance test.
 The test location shall be barricaded. also, when performing the test, safety Tags required and
watch man shall be available at the remote end of the equipment.
 CT terminals shall be return back to the correct one before starting the bus bar or transformer
differential stability test.
 Check all available field signals coming from the motors or transformers or other equipment in the
field.

7- QUALITY CONTROL

7-1- The complete Electrical Equipment Installation systems shall be checked and
tested as follows:
7-2- An advance written request / notice to inspect must be given by initiating and ob-
taining Request for Inspection (RFI) form in accordance with Inspection Test Plan
7-3- Confirm correct material sizes / type and other associated materials available that
would meet the requirement of the project specifications, codes and standards
7-4- All material shall be physically checked and inspected upon receipt at the site
prior to installation.
7-5- 7.4All inspections being conducted shall be recorded on approved forms, signed,
dated and approved by authorized Contractor and Owner representatives
7-6- Check if all materials are available to complete the testing process.
7-7- Ensure that qualified inspector with approved tools and equipment shall carry out
the testing processes.
7-8- Where physical damage or non-compliance with the specification had been found,
a Non Conformance Report (NCR) shall be issued.

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017


PACKAGE “P” POWER PLANT
YANBU POWER AND DESALINATION PLANT – PHASE-III

Subject: Method Statement For Electric test for LV SWGR & MCC Page :22 of 22
Doc Rev. A
S E P - 0 1 - Z A A - 6 D C - 0 1 3
No.:

8- HSE CONTROL

8-1- All staff, supervisors and workers must abide to all safety and security regulations
on and off site.
8-2- Safety Officer on site will be implementing the strict adherence of the employees
with regards to the safety regulation as being mentioned in the drawn safety pro-
gram of the company.
8-3- Safety procedures will be monitored as per the specification of the Main Contrac-
tor and ensure the implementation as well.
8-4- Safety Officer on site will be directly dealing with the contractors HSE Officer for
the compliance of the procedure as provided and for any applicable revisions in-
volving HSE matters.
8-5- The company shall adhere with all the given standards agreed upon relating to
safety and security issues as the project commences and up to the completion.

9- ATTACHMENTS OF SAFETY RISK ASSESSMENT

See Attachment

SEP-01-ZAA-6DC-013_MS For ElectricTest For LV SWGR & MCC 31-OCT-2017

You might also like