MINUTES OF PRE-BID MEETING, HELD ON 13.02.

2023 AT IOCL PANIPAT REFINERY CONTRACT CELL


THROUGH WEB/PHYSICALLY

Subject : Tender No. RPRC235034


(Name of work: SITC of Wireless FDA System in PRPC Township.)

With the reference to the subject Tender following points were discussed:

• The participating bidders were asked to raise the points for clarifications if any.
• Based on the raised queries, the tender scope was briefed to the vendors. After prolong discussion, it
was decided that additional information if any on technical scope against the raised queries from the
bidder shall be given as technical corrigendum / addendum. So all the bidders were suggested to keep
track of the same. However, detail of clarification against the raised query has been attached as
Annexure-1.
• On request of extension of the tender due date from the bidder, IOCL replied that the same shall be
looked into by IOCL management for further extension if any. However, bidders are suggested to
submit their offer within tender due date.
• Then the vendors were suggested to submit all necessary documents as asked in the tender at the time
of bidding.

On behalf of IOCL

1 Mr. N N Mit, CMNMEL

2. Mr. A K Mahajan, CM(CC)

3 Mr. Saurabh Jain, FM

On behalf of M/s Innovative Engineers.

Mr. Ketan Shah

On behalf of M/s Lambda Technologies.

Mr. Dhaval Chitara


Annexure-1

Document Cluase Page Type of Tender description Query by IE Reply by


No query IOCL

SCC_Technical 3.1.1 5 Technical 100% redundant Fire Understanding Pls follow


control Panel control is that mean the tender
panels (Depending on the each FACP, two conditions.
bidder’s design and hot swap FACP
Architecture) – panel along with
Redundancy at various dislay along
levels ie. CPU, Loop Card, with separate
Display, power supply is
required. Kindly
confirm

SCC_Technical 3.4.2 6 Technical The FACP should have The very Pls follow
facility to program with purpose of open the tender
Addressable Wireless protocol is it conditions.
Devices protocol and becomes brand
should be of the same agnostic and
make as Wireless Devices. standards
abiding. Sensor
vs Wireless
technology
along with
panel both
work on
completley
different
technologies. If
entire system
abides to said
fire standards,
Panel and
sensors can be
of different
make?

SCC_Technical 3.4.6 7 Technical The FACP shall support up Understanding Pls follow
to 240 Devices on the is that, this the tender
signalling loop in any wired system is conditions.
combination. The FACP required only
shall fully support the sub- when hybrid
addressing capabilities of wired-wireless
the relevant input and system is used.
output devices. If during design
SCC_Technical 3.4.7 7 Technical The FACP shall contain of stage Pls follow
one to four signalling loop architecutre is the tender
drivers depending on the approved where conditions.
system design entire system
requirements. Each can work
signalling loop shall be wirelessly this
capable of supplying at wired looping
least 500mA of power for will not be
loop-based sounders or required. Kindly
other output devices. The confirm
Fire Alarm Control Panel
software and hardware
loop driver, without
modification, shall be
compatible with the
analogue detection, call
points, input and output
devices.

SCC_Technical 3.4.11 9 Technical Panel Indications a) The What if FACP Minimum


Fire Alarm Control Panel has touch specs given
shall be equipped with a screen display? n tender to
white backlit display This can change be followed.
(240x64 pixels) as the the structure of
primary indicator giving at the displays.
least 6-lines of Understanding
information. The display is client will not
shall illuminate upon any have any
event (excluding mains problem with
failure) or button press. this and any
The display must provide precise display
an energy efficient will not be
software adjustment and mandatory as
be able to be dimmed and far as it is as per
provide the option of the standards.
giving the facility of ‘More
Alarms’. b) The primary
display shall be
simultaneously capable of
indicating the presence of
Fire Alarms, Faults,
Disablements and Tests c)
In addition, the following
minimum LED indicators
shall be provided:

SCC_Technical 3.9.1 12 Technical It shall be possible to Undertanding is


configure ALL basic if panel can be
configuration parameters configured from
and settings from either any standard
the FACP front panel or physical port-
from the PC Configuration serial or USB as
Tool. Both serial and USB well LAN or wifi
connections from the client is OK with
FACP to the PC are to be it
available.

SCC_Technical 3.15.4 14 Technical The form of All kinds of Minimum


communication between wireles specs given
Translator and wireless solutions do not n tender to
devices shall be require be followed.
bidirectional for enhanced translators and
monitoring and control sensors or
functionality. control
elements can
directly
communicate
with FCAP.
Also if
translators are
required will not
be as per the
ratio of sensors
mentioned and
translator
nececssarily do
not mean it
translates
wireless to
wired, it can be
wireless
aggreegator
too, aggregating
and
transmitting.
Understanding
is client is Ok
with it as this
will be decided
ruing approval
of architecture
during design
stage

SCC_Technical 2.3.0, 4 Technical PRPC Guest House and How much area May visit
Sr BOQ PRPC Hospital covered in PRPC Site as per
No.1 Guest House Tender
and PRPC Conditions.
Hospital ? How
many storey
building of both
locations?
SCC_Technical 3.6.1 10 Technical The IP Gateway connects Internet Internet
to an existing fire panel Connectivity will connectivity
network, and provides a be scope of not
gateway to the network IOCL ? envisaged.
from any remote location
over the internet.