MANUAL COMPUTATION

DEADLOAD

S1 (T&B)
Floor and Floor Finishes= 1.10 kPa
kN 150
Slab = 24 × =3.6 kPa
m
3
1000

Ceiling = Table 204-2 (Plaster on tile or concrete) = 0.24 kPa


Utilities = Table 204-2 (utilities) = 0.2 kPa
Internal Walls = 2.69+ ( 2 ×0.24 )=3.17 kpa
IW × L × H 3.17 ×5.5991 ×3.4
qIW = = =4.5968 kPa
A slab 3 x 4.376
qDL = 9.7468 kPa

S1 (BEDROOM)
Thickness of Ceramic Finish = 28 mm
k Pa
Floor Finish = 0.023 ×28=0.644 kPa
mm
kN 150
Slab = 24 × =3.6 kPa
m
3
1000

Ceiling = Table 204-2 (Plaster on tile or concrete) = 0.24 kPa


Utilities = Table 204-2 (utilities) = 0.2 kPa
qDL= 4.684 kPa

S1 (LIVING ROOM)
Thickness of Ceramic Finish = 28 mm
kPa
Floor Finish = 0.023 ×28=0.644 kPa
mm
kN 150
Slab = 24 × =3.6 kPa
m
3
1000

Ceiling = Table 204-2 (Plaster on tile or concrete) = 0.24 kPa


Utilities = Table 204-2 (utilities) = 0.2 kPa
qDL= 4.684 kPa

LOAD DISTRIBUTION
S = 4.376 W(TDL) = ¿6.194483 kN/m
L = 3.000

S 4.376
= =1.46>0.5 : TWO-WAY
L 3.000

B1
3.2
W(IW) = 3.17 × =5.072 kN /m
2
W(slab) =
qDL × L 9.7368 ×3
= =9.7368 kN /m
3 3
W(TDL) = 14.8088 kN/m

B2
W(slab) =
2
9.7368 ×4.376 3− (1.458667 )
× =¿ 6.19448
3 2
3 kN/m
LIVE LOAD
S1 (T&B) = Table 205-1 = 1.9 kPa
S1 (Bedroom) = Table 205-1 = 1.9 kPa
S1 (Living Room) = Table 205-1 = 1.9 kPa

LOAD DISTRIBUTION (T & B, Bedroom, Living Room)


As = S × L=4.376 ×3=13.128
1.9× 4.376
W(TLL) = =2.771467
3

LOAD COMBO
S1 (T&B)
kN
1.4 D=1.4 ×14.8088 = 20.7323
m
kN
1.2 D+ 1.6 L=1.2 ( 14.8088 ) +1.6 (1.9) = 20.8106
m
kN
1.2 D+ 1.6 L=1.2 ( 14.8088 ) +0.5 ( 1.9 ) =18.7206
m

kN
Wu=20.8106
m
S1 (BEDROOM)

kN
.4 D=1.4 ×14.8088 = 20.7323
m
kN
1.2 D+ 1.6 L=1.2 ( 14.8088 ) +1.6 (1.9) = 20.8106
m
kN
1.2 D+ 1.6 L=1.2 ( 14.8088 ) +0.5 ( 1.9 ) =18.7206
m
kN
Wu=20.8106
m
S1 (LIVING ROOM)

kN
.4 D=1.4 ×14.8088 = 20.7323
m
kN
1.2 D+ 1.6 L=1.2 ( 14.8088 ) +1.6 (1.9) = 20.8106
m
kN
1.2 D+ 1.6 L=1.2 ( 14.8088 ) +0.5 ( 1.9 ) =18.7206
m
kN
Wu=20.8106
m